FRS Form 1 (in BAL-003 Reliability Std)

FRS_FORM_1 (BAL-003 Reliability Std).xls

FERC-725R (NOPR in RM13-11) Mandatory Reliability Standards: Reliability Standard BAL-003-1.

FRS Form 1 (in BAL-003 Reliability Std)

OMB: 1902-0268

Document [xlsx]
Download: xlsx | pdf

Overview

Instructions
Data Entry
Form 714 Data
Adjustments
Variable Bias Supplemental Info
BA Form 2 Event Data
TimeZone Ref
Event Frequency Graphs
Frequency Response Initiative


Sheet 1: Instructions

Instructions














Step 1 Enter data in all green cells on the "Data Entry" worksheet. Cell G1 with the BA name. Cells R11 through R13 with contact information. Cell R24 with BA Bias Type, Fixed or Variable.









Step 2 For identified events in column C of the "Data Entry" worksheet, collect data and complete one FRS Form 2 workbook for each event in the list.

Detailed Instructions for utilizing the "Adjustments" are located on the "Adjustments" worksheet below the table.















Step 3 PasteSpecial/Values data from FRS Form 2 "Form 1 Summary Data" worksheet into "BA Form 2 Event Data" worksheet of this workbook. Do this for each event in the list.









Step 4 Enter FERC Form 714 data from the most recent completed Form 714 in the worksheet "Form 714 Data" in cells C7 through D18. Use Copy/PasteSpecial/Values to enter data.







Your current year's Frequency Response Obligation will be calculated in cell R20 of the "Data Entry" worksheet.















Step 5 a) If a Fixed Bias was selected, cell R27 will calculate the minimum Bias (least negative) allowed based on your Peak Demand or Peak Generation for Generation only BAs.







b) If a Fixed Bias was selected, cell R28 will calculate the minimum (in absolute terms) Bias allowed based on 100% of your FRM.







c) If a Fixed Bias was selected, cell R29 will calculate the maximum Bias (in absolute terms) allowed based on 125% of your FRM.







d) If R29 was more negative than the value in R27, you may choose a Bias setting that is between R29 and the lesser of R27 or R28 and enter it here. Based on your choice, your Bias Setting will appear in cell R33.















Step 6 a) If a Variable Bias was selected, cell R27 will indicate "not applicable" where there is no maximum or minimum Bias Setting.







b) If a Variable Bias was selected, enter "Variable" in cell R31.







c) If a Variable Bias was selected, cell R30 will calculate the minimum Bias (in absolute terms) allowed based on your FRM and Peak Demand/Peak Generation. Calculate your monthly one minute average Variable Bias setting when frequency is lower than 59.964 Hz or higher than 60.036 Hz and enter these monthly values on the "Variable Bias Supplemental Info" worksheet in cells B2 through D13.







d) If the "average annual Variable Bias Setting" in cell D14 on the "Variable Bias Supplemental Info" worksheet is less negative than cell E14 of this worksheet, R3 of the standard has not been met and cell D14 on the "Variable Bias Supplementa Info" worksheet will turn red. The average minimum Bias Setting will cover two different reporting periods and Cells J3 through K10 require past year's data from those year's Form 1s for this evaluation.







e) Depending on when the Implementation date is each year for the annual Bias Setting, the ERO may be required to edit the selection of each months' minimum average FBS value. This should be completed by the ERO before each year's FRS Form 1 is published.







f) The comparison to the FBS minimum will be from two previous year's analysis prior to the current year and the dates in the table starting at J3 will indicate the appropriate year's data to use. For example, if it is Feb 1, 2013 and you are calculating your 2012 FBS time weigted average, the minimum FBS value will be determined from your FRM that you calculated in Feb of 2012 and based on the Peak Demand/Peak Gen reported in June of 2011 for 2010 data. Enter each field in green using the appropriate year's data.















Step 7 Two FRMs are calculated. One for the BA Bias Setting and one for meeting R1 of the standard.







The FRM for the BA Bias Setting will use all selected events and all SEFRD values will use the delta frequency as measured.







The FRM for the BA compliance to R1 will limit the delta frequency to no greater than those listed in Table 2 of Attachment A for each Interconnection. (Eastern +/-0.500 Hz, Western +/-0.500 Hz, ERCOT +/-0.700 Hz and HQ +/-1.500 Hz.)















Step 7 Save this workbook using the following file name format:NYISO_yyyy_FRS_Form_1.9.xlsx. (where NYISO is replaced with your Balancing Authority abbreviation). See cell "G74" on the Data Entry worksheet for your exact file name.















Step 8 Send completed Form 1 and each Form 2 to NERC.



















Sheet 2: Data Entry






Balancing Authority MyBA
NERC FRS FORM 1 20 to 52 second Value B
Enter Addition Data in column W ==>

Information Select Reason(s) for adjustment



























Columns BA, BB, BC, BD, BE, BF and BG are reserved for calculation of the linear regression.
Event UTC (t-0) Date/Time (t-0) Time Date/Time (t-0) BA
BA BA Relay Lmt Value "A" Information Value "B" Information SEFRD (FRM) Exclude for
Enter Data in Green Highlighted Cells

Value "A" Value "B"




























BA Delta 10 X BA 10 X BA SEFRDB SEFRDR Regression





Time

Bias R1



for Bias for R1



































NAI DelFreq DelFreq (MW/0.1Hz) (MW/0.1Hz) Statistics
Number Date / Time
(MM/DD/YY HH:MM:SS)
(Central Prevailing) Zone BA Time Zone DelFreq Time DelFreq DelFreq NAI Adjustment NAI Adjustment (MW/0.1Hz) (MW/0.1Hz) data error * 0.9 Send copy to: [email protected]
Load Load Reason(s)




























For Bias For R1

For Bias
1 12/30/1899 6:00:00
CST 12/30/1899 0:00:00 CST
0:00:00 0.000 0.000 0.0 0.0 0.0 0.0 #DIV/0! 0.0 N 0.0


0.0 0.0
















-0.058 23.2

Dynamic schedules for joint-owned units (DS)


0 0 595 #DIV/0! 0 #VALUE! #VALUE!
2 12/30/1899 6:00:00
CST 12/30/1899 0:00:00 CST
0:00:00 0.000 0.000 0.0 0.0 0.0 0.0 #DIV/0! 0.0 N 0.0


0.0 0.0
















-0.066 27.7

Nonconforming load (NL)


0 0 595 #DIV/0! 0 #VALUE! #VALUE!
3 12/30/1899 6:00:00
CST 12/30/1899 0:00:00 CST
0:00:00 0.000 0.000 0.0 0.0 0.0 0.0 #DIV/0! 0.0 N 0.0


0.0 0.0
















-0.040 10.7

Pumped hydro (PH)


0 0 595 #DIV/0! 0 #VALUE! #VALUE!
4 12/30/1899 6:00:00
CST 12/30/1899 0:00:00 CST
0:00:00 0.000 0.000 0.0 0.0 0.0 0.0 #DIV/0! 0.0 N 0.0 1900 Bias Calculation Form 1 for Year
0.0 0.0
















-0.052524929954899 80.6608905519758

Invalid Data (ID)


0 0 595 #DIV/0! 0 #VALUE! #VALUE!
5 12/30/1899 6:00:00
CST 12/30/1899 0:00:00 CST
0:00:00 0.000 0.000 0.0 0.0 0.0 0.0 #DIV/0! 0.0 N 0.0 Eastern Interconnection
0.0 0.0
















-0.070905231294198 -26.8976089613778

Transfered Frequency Response (TFR)


0 0 595 #DIV/0! 0 #VALUE! #VALUE!
6 12/30/1899 6:00:00
CST 12/30/1899 0:00:00 CST
0:00:00 0.000 0.000 0.0 0.0 0.0 0.0 #DIV/0! 0.0 N 0.0 MyBA Balancing Authority
0.0 0.0
















-0.051906767345699 9.95544917881489

Contingent BA adjustment for loss of units (CBA)


0 0 595 #DIV/0! 0

7 12/30/1899 6:00:00
CST 12/30/1899 0:00:00 CST
0:00:00 0.000 0.000 0.0 0.0 0.0 0.0 #DIV/0! 0.0 N 0.0
Contact Name
0.0 0.0
















-0.058047703334303 3.36702401297433

DS & NL


0 0 595 #DIV/0! 0 For R1
8 12/30/1899 6:00:00
CST 12/30/1899 0:00:00 CST
0:00:00 0.000 0.000 0.0 0.0 0.0 0.0 #DIV/0! 0.0 N 0.0
Contact Phone #
0.0 0.0
















-0.075572422572499 36.3344268798828

DS & PH


0 0 595 #DIV/0! 0 0 0
9 12/30/1899 6:00:00
CST 12/30/1899 0:00:00 CST
0:00:00 0.000 0.000 0.0 0.0 0.0 0.0 #DIV/0! 0.0 N 0.0
Contact e-mail
0.0 0.0
















-0.056380498976999 0.488253044359624

DS & ID


0 0 595 #DIV/0! 0 0 #N/A
10 12/30/1899 6:00:00
CST 12/30/1899 0:00:00 CST
0:00:00 0.000 0.000 0.0 0.0 0.0 0.0 #DIV/0! 0.0 N 0.0
Attachment A page 2. MWh Annual GenBA is the annual "Net Generation (MWh)", FERC Form 714, line 13, column c of Part II - Schedule 3.
0.0 0.0
















-0.057332901727598 2.75803693135579

DS & TFR


0 0 595 #DIV/0! 0 1 0
11 12/30/1899 6:00:00
CST 12/30/1899 0:00:00 CST
0:00:00 0.000 0.000 0.0 0.0 0.0 0.0 #DIV/0! 0.0 N 0.0
Attachment A Page 2. MWh Annual LoadBA is the annual "Net Energy for Load (MWh)", FERC Form 714, line 13, column e of Part II - Schedule 3.
0.0 0.0
















-0.051760900588299 13.6434168815613

DS & CBA


0 0 595 #DIV/0! 0 #N/A 11
12 12/30/1899 6:00:00
CST 12/30/1899 0:00:00 CST
0:00:00 0.000 0.000 0.0 0.0 0.0 0.0 #DIV/0! 0.0 N 0.0 FRSDT: NERC will update these values in the 3rd quarter of each year after completed Form 714s are available. This data is used to calculate "next" year's Frequency Response Obligation, FRO. Attachment A, page 3.
MWh Annual GenINT is the Sum of all Annual GenBA values in this interconnection
0.0 0.0
















-0.049999237060547 11.1007459163666

DS & NL & PH


0 0 595 #DIV/0! 0 0 0
13 12/30/1899 6:00:00
CST 12/30/1899 0:00:00 CST
0:00:00 0.000 0.000 0.0 0.0 0.0 0.0

Y

MWh Annual LoadINT is the Sum of all Annual LoadBA values in this interconnection
0.0 0.0
















-0.052 -19.9068464835485

DS & NL & ID









14 12/30/1899 6:00:00
CST 12/30/1899 0:00:00 CST
0:00:00 0.000 0.000 0.0 0.0 0.0 0.0

Y
-964 Interconnection Frequency Response Obligation (FRO) MW/0.1 Hz. Determined by ERO.
0.0 0.0
















-0.055999755859375 12.3254643016391

JOU DS & NL & TFR









15 12/30/1899 6:00:00
CST 12/30/1899 0:00:00 CST
0:00:00 0.000 0.000 0.0 0.0 0.0 0.0

Y
1899 Current data year (December thru November)
0.0 0.0
















-0.058498382568359 0.750191847483315

DS & NL & CBA









16 12/30/1899 6:00:00
CST 12/30/1899 0:00:00 CST
0:00:00 0.000 0.000 0.0 0.0 0.0 0.0

Y
#DIV/0! 1900 BA Frequency Response Obligation (FRO) for next year's FRM
0.0 0.0
















-0.048500061035156 2.23005777994791

DS & NL & PH & ID









17 12/30/1899 6:00:00
CST 12/30/1899 0:00:00 CST
0:00:00 0.000 0.000 0.0 0.0 0.0 0.0

Y

1899 BA Frequency Response Obligation (FRO) for this year's FRM from your last year's Form 1.
0.0 0.0
















-0.045000076293945 9.47785933017731

DS & NL & PH & TFR









18 12/30/1899 6:00:00
CST 12/30/1899 0:00:00 CST
0:00:00 0.000 0.000 0.0 0.0 0.0 0.0

Y



0.0 0.0
















-0.037502288818359 0.355309009552002

DS & NL & PH & CBA









19 12/30/1899 6:00:00
CST 12/30/1899 0:00:00 CST
0:00:00 0.000 0.000 0.0 0.0 0.0 0.0

Y

BA Bias Type and Bias Setting
0.0 0.0
















-0.047500610351563 2.17070185343425

DS & NL & PH & ID & TFR









20 12/30/1899 6:00:00
CST 12/30/1899 0:00:00 CST
0:00:00 0.000 0.000 0.0 0.0 0.0 0.0

Y
Fixed Bias Type utilized.
0.0 0.0
















-0.055500030517578 29.3820742766062

DS & NL & PH & ID & CBA









21 12/30/1899 6:00:00
CST 12/30/1899 0:00:00 CST
0:00:00 0.000 0.000 0.0 0.0 0.0 0.0

Y
0.90% Interconnection Minimum Fixed Frequency Bias Setting % of Peak Demand or Peak Generation (Set by ERO)
0.0 0.0
















-0.047 4.60138130187988

DS & NL & PH & ID & TFR & CBA









22 12/30/1899 6:00:00
CST 12/30/1899 0:00:00 CST
0:00:00 0.000 0.000 0.0 0.0 0.0 0.0

Y
621018 The Sum of the Non-Coincident peak demands for all Bas on the interconnection from FERC Form No. 714, provided by ERO.
0.0 0.0
















-0.060000000000002 1.59351487954458

NL & PH









23 12/30/1899 6:00:00
CST 12/30/1899 0:00:00 CST
0:00:00 0.000 0.000 0.0 0.0 0.0 0.0

Y
#DIV/0! Your BA's lowest absolute Fixed Frequency Bias Setting based on interconnection non-coincident peak demand.
0.0 0.0
















-0.059999999999995 52.3709077835083

NL & ID









24 12/30/1899 6:00:00
CST 12/30/1899 0:00:00 CST
0:00:00 0.000 0.000 0.0 0.0 0.0 0.0

Y
#DIV/0! Your BA's lowest absolute Fixed Frequency Bias Setting based on 100% of FRM.
0.0 0.0
















-0.051000000000002 33.9478736718496

NL & TFR









25 12/30/1899 6:00:00
CST 12/30/1899 0:00:00 CST
0:00:00 0.000 0.000 0.0 0.0 0.0 0.0

Y
#DIV/0! Your BA's highest absolute Fixed Bias Setting: 125% of FRM.
0.0 0.0
















-0.1 100

NL & CBA









26 12/30/1899 6:00:00
CST 12/30/1899 0:00:00 CST
0:00:00 0.000 0.000 0.0 0.0 0.0 0.0

Y
n/a Balancing Authority lowest absolute Variable Bias Setting (least negative one minute average Bias while frequency is less than 59.964 or greater than 60.036 Hz).
0.0 0.0




















NL & PH & ID









27 12/30/1899 6:00:00
CST 12/30/1899 0:00:00 CST
0:00:00 0.000 0.000 0.0 0.0 0.0 0.0

Y
-20.87 Balancing Authority desired Bias Setting: May be set to a value between 100% to 125% of its FRM if this value is more negative than the minimum Bias based on Peak Demand. If not more negative, then the Bias must be the minimum Bias based on Peak Demand. If variable Bias is used, enter "Variable".
0.0 0.0




















NL & PH & TFR









28 12/30/1899 6:00:00
CST 12/30/1899 0:00:00 CST
0:00:00 0.000 0.000 0.0 0.0 0.0 0.0

Y

0.0 0.0




















NL & PH & BAA









29 12/30/1899 6:00:00
CST 12/30/1899 0:00:00 CST
0:00:00 0.000 0.000 0.0 0.0 0.0 0.0

Y
#DIV/0! 1900 Frequency Bias Setting - (minimum of 100% to 125% of FRM, or 0.9% of Historical Peak Demand if not Variable)
0.0 0.0




















NL & PH & ID & TFR









30 12/30/1899 6:00:00
CST 12/30/1899 0:00:00 CST
0:00:00 0.000 0.000 0.0 0.0 0.0 0.0

Y

0.0 0.0

















N

NL & PH & ID & CBA









31 12/30/1899 6:00:00
CST 12/30/1899 0:00:00 CST
0:00:00 0.000 0.000 0.0 0.0 0.0 0.0

Y
#DIV/0! 1899 FRM - Average Estimated Frequency Response MW/0.1 Hz using SEFRD for Bias
0.0 0.0

















Y

NL & PH & ID & TFR & CBA









32





0:00:00 0.000 0.000 0.0 0.0 0.0 0.0

Y
#VALUE! 1899 FRM - Regression Estimated Frequency Response MW/0.1Hz using SEFRD for Bias
0.0 0.0




















PH & ID









33





0:00:00 0.000 0.000 0.0 0.0 0.0 0.0

Y
#DIV/0! 1899 FRM - Median Estimated Frequency Response MW/0.1Hz using SEFRD for Bias
0.0 0.0




















PH & TFR









34





0:00:00 0.000 0.000 0.0 0.0 0.0 0.0

Y
0.00 1899 FRM - Average Estimated Frequency Response MW/0.1 Hz using SEFRD for R1
0.0 0.0




















PH & CBA









35





0:00:00 0.000 0.000 0.0 0.0 0.0 0.0

Y
0.00 1899 FRM - Regression Estimated Frequency Response MW/0.1Hz using SEFRD for R1
0.0 0.0




















PH & ID & TFR









36





0:00:00 0.000 0.000 0.0 0.0 0.0 0.0

Y
0.00 1899 FRM - Median Estimated Frequency Response MW/0.1Hz for BA Compliance to R1, minimum Frequency Response
0.0 0.0




















PH & ID & CBA









37





0:00:00 0.000 0.000 0.0 0.0 0.0 0.0

Y
N Do you RECEIVE Overlap regulation?
0.0 0.0




















PH & TFR









38





0:00:00 0.000 0.000 0.0 0.0 0.0 0.0

Y

If Yes, list the BA name and the associated Bias of that BA in the table below.
0.0 0.0




















PH & CBA









39





0:00:00 0.000 0.000 0.0 0.0 0.0 0.0

Y



0.0 0.0




















PH & ID & TFR









40





0:00:00 0.000 0.000 0.0 0.0 0.0 0.0

Y
Bias -MW/0.1 Hz Balancing Authority
0.0 0.0




















PH & ID & CBA









41





0:00:00 0.000 0.000 0.0 0.0 0.0 0.0

Y



0.0 0.0




















PH & TFR









42





0:00:00 0.000 0.000 0.0 0.0 0.0 0.0

Y



0.0 0.0




















PH & CBA





















































PH & ID & TFR & CBA





















































RU & TFR





















































RU & CBA





















































RU & TFR & CBA





















































TFR & CBA












































































































































































































N Do you PROVIDE Overlap regulation?

























































If Yes, list the BA name and the associated Bias of that BA




















N

























































Y


































Bias -MW/0.1 Hz Balancing Authority





































































































































































































Fixed
























































Variable












































































Instructions





































Relay Limits























































Eastern 59.5 60.5
















Step 1


Enter data in all green cells on this "Data Entry" worksheet.

























Western 59.5 60.5























































ERCOT 59.3 60.7
















Step 2


For identified events in column B, collect data and complete FRS Form 2.9 for each event in the list.

























HQ 58.5 61.5











































































Step 3


PasteSpecial/Values data from FRS Form 2.9 "Form 1 Summary Data" into "BA Form 2 Data" worksheet of this workbook. Do this for each event in the list.








































































































Step 4


Save this workbook using the following file name format:NYISO_yyyy_FRS_Form_1.9.xlsm and send a copy of this workbook and all FRS_Form 2 workbooks to NERC. (where NYISO is replaced with your BA name)












































































































MyBA_1900_FRS_Form_1.9.xlsm



































































































































































Sheet 3: Form 714 Data

Report 714 Data (in MW)



Part II Schedule 3









Column (b) Column (j)



Month Peak Demand



January




February



Peak Demand: (Your BA from Form 714, column j of Part II - Schedule 3)
March




April




May




June




July




August




September




October




November




December










Average #DIV/0!



Maximum 0




Sheet 4: Adjustments


Balancing Authority MyBA JOU
Dynamic Schedules

Non conforming Load
Pumped Hydro
Not Used
Transferred Frequency Response
Contingent BA Adjustment
Net Total Adjustments
Event Date/Time (t-0)
Value A Value B
Value A Value B
Value A Value B
Value A Value B
Value A Value B
Value A Value B
Value B 20 to 52 seconds
Number (Central Prevailing) DelFreq Adjustment Adjustment Adjustment Adjustment Adjustment Adjustment Adjustment Adjustment Adjustment Adjustment Adjustment Adjustment
1

0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0
2

0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0
3

0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0
4

0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0
5

0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0
6

0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0
7

0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0
8

0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0
9

0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0
10

0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0
11

0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0
12

0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0
13

0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0
14

0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0
15

0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0
16

0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0
17

0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0
18

0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0
19

0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0
20

0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0
21

0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0
22

0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0
23

0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0
24

0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0
25

0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0
26

0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0
27

0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0
28

0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0
29

0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0
30

0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0
31

0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0
32

0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0
33

0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0
34

0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0
35

0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0
36

0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0
37

0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0
38

0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0
39

0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0
40

0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0
41

0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0
42

0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0 0.0
0.0

Sign Convention for scan data collected in Form 2 Imports: MWs are -
Exports: MWs are +

Loads in MW as -
Load MW as -
Generation MW as +

Enter Gen MW as +
The transactional amount in
MW Receiver enters - Deliverer enters +
on Form 2 Data sheet

Generation MW as +
(If demand occurs due to gen loss, enter MW as - at value B)



Instructions for utilizing Adjustments:




















1) Balancing Authorities making adjustments must retain evidence to verify:
- Adjustment values are determined from scan-cycle data using Value A and Value B averaging periods. Scan-cycle data must be available if adjustments are made.
- Adjustments are necessary to improve accuracy of calculations compared to using Net Actual Interchange solely.
Said differently, unless an adjustment compensates for significant known error, it should not be made. However, as noted in the next item, once a decision to include an
adjustment for one or more of the five types is made for one event, the entity must calculate adjustments for that (those) type(s) for all events except for the Contengent BA Adjustment which is only utilized for the events that you are contengent during that event.
- Adjustments are included consistently for all events (e.g. if adjustments for nonconforming load are made for one event, the load must be included for all events, etc.).



2) Dynamic Schedules:
- Values use schedule sign convention.
- Adjustments should include only dynamic schedules accounting for joint-owned units. Other dynamic schedules should be ignored.



3) Nonconforming Loads:
- Values must be negative numbers.



4) Pumped Hydro:
- Values for pumping must be negative values.
- Values for generating must be positive values.



5) Rampling Units:
- Values are positive values.



6) Transferred Frequency Response:
- This value is the amount agreed upon between the entities expressed in MW/0.1 Hz. Form 2 will adjust this amount for the frequency deviation experienced.
(e.g. if an entity agrees to provide 20 MW/0.1 Hz to another entity and a frequency event with a deviation of 50 mHz occurs, the delivering entity should enter +20 in the
data column of Form 2 and the receiving entity should enter - 20. The spreadsheet will adjust the SEFRD for each entity by the 10 for this event.)
- Values for the entity receiving the response must be entered as a negative number.
- Values for the entity delivering the response must be entered as a positive number.
- Values between entities must sum to zero.



7) Contingent Balancing Authority Adjustment:
- Data for Value A is the pre-contingency scan rate generation (+MW values) from the contingent unit(s).
- Data for Value B is usually 0 MW, but may be the demand (-MW values) that remains on the system that was "netted" out by the now offline generation.



Sheet 5: Variable Bias Supplemental Info

Month Minimum FBS* for month Maximum FBS* for month Time weighted ** average FBS* for month Time weighted ** minimum average FBS* for month

















January







Balancing Authority:
MyBA










Feburary







1898 Reporting period FRS Form 1 data











March







0.00 1898 Reporting period: Balancinig Authority FRM MW/0.1 Hz, enter from FRS Form 1 for that year's FRM. If not know enter zero.











April







1.00% 1898 Reporting period: Interconnection Minimum Fixed Frequency Bias Setting % of Peak Demand or Peak Generation (Set by ERO)











May








1898 Reporting period: Your BA's Annual Peak Demand or Peak Gen for Gen only BAs from your BA Form 714.











June







0.00 Your BA's lowest absolute Fixed Frequency Bias Setting based on BA Peak Demand (Peak Generation for Generation only BA) MW/0.1 Hz.











July







0.00 Your BA's lowest absolute Fixed Frequency Bias Setting based on 100% of FRM.











August







0.00 1899 Minimum, lowest absolute, conditional average Frequency Bias Setting MW/0.1 Hz.











September








1898 Minimum, lowest absolute, conditional average Frequency Bias Setting MW/0.1 Hz.











October





















November





















December
























0.0 0.0 1899 Average Annual Bias MW/0.1 Hz







































* Frequency Bias Setting (FBS)





















** Based on the one minute values used in BAL 001 when frequency is greater than 60.036 Hz or less than 59.964 Hz.






















Sheet 6: BA Form 2 Event Data




























Average P.U. Performance #DIV/0! #DIV/0! #DIV/0!



#DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0!





PasteSpecial/Values the data copied from FRS Form 2 for each event.




Value A Data
BA Performance







Value B 20 to 52 second Average Period Evaluation












Frequency Response Initiative - Additional Primary Frequency Response Evaluation Points













JOU Non-

Transferred Contingent




JOU Non-

Transferred Contingent





Average Unadjusted Unadjusted Unadjusted Unadjusted Unadjusted Adjusted Adjusted Adjusted Adjusted Adjusted





Date A Point FPointA A Value t(0) Time C Value
Net Dynamic Conforming Pumped Ramping Frequency BA BA BA Bias
Net Dynamic Conforming Pumped Ramping Frequency BA Initial Initial Sustained BA BA Bias Bias While PFR PFR PFR PFR PFR PFR PFR PFR PFR PFR






Time Hz Hz
Hz
Actual Schedules Load Hydro Units Response Lost Generation Bias Load Setting
Actual Schedules Load Hydro Units Response Lost Generation Performance Performance Performance Bias Load Setting Hz > +/-0.036 Performance Performance Performance Performance Performance Performance Performance Performance Performance Performance Maximum Minimum
Event Date/Time






Frequency Interchange Imp(-) Exp (+) Load (-) Load (-) Gen (+) Gen (+) Rec (-) Del (+) Load (-) Gen (+) Setting
EPFR Frequency Interchange Imp(-) Exp (+) Load (-) Load (-) Gen (+) Gen (+) Rec (-) Del (+) Load (-) Gen (+) Adjusted Unadjusted
Setting
EPFR Hz @ T(+46) @ T(+76) @ T(+106) @ T(+136) @ T(+166) @ T(+46) @ T(+76) @ T(+106) @ T(+136) @ T(+166) Bias Setting Bias Setting
Number (Central Prevailing) DelFreq





Hz MW MW MW MW MW MW MW MW/0.1 Hz MW MW Hz MW MW MW MW MW MW MW P.U. P.U. P.U. MW/0.1 Hz MW MW MW/0.1 Hz P.U. P.U. P.U. P.U. P.U. P.U. P.U. P.U. P.U. P.U. MW/0.1 Hz MW/0.1 Hz
1 12/30/1899 0:00 0.000












































2 12/30/1899 0:00 0.000












































3 12/30/1899 0:00 0.000












































4 12/30/1899 0:00 0.000












































5 12/30/1899 0:00 0.000












































6 12/30/1899 0:00 0.000












































7 12/30/1899 0:00 0.000












































8 12/30/1899 0:00 0.000












































9 12/30/1899 0:00 0.000












































10 12/30/1899 0:00 0.000












































11 12/30/1899 0:00 0.000












































12 12/30/1899 0:00 0.000












































13 12/30/1899 0:00 0.000












































14 12/30/1899 0:00 0.000












































15 12/30/1899 0:00 0.000












































16 12/30/1899 0:00 0.000












































17 12/30/1899 0:00 0.000












































18 12/30/1899 0:00 0.000












































19 12/30/1899 0:00 0.000












































20 12/30/1899 0:00 0.000












































21 12/30/1899 0:00 0.000












































22 12/30/1899 0:00 0.000












































23 12/30/1899 0:00 0.000












































24 12/30/1899 0:00 0.000












































25 12/30/1899 0:00 0.000












































26 12/30/1899 0:00 0.000












































27 12/30/1899 0:00 0.000












































28 12/30/1899 0:00 0.000












































29 12/30/1899 0:00 0.000












































30 12/30/1899 0:00 0.000












































31 12/30/1899 0:00 0.000












































32 12/30/1899 0:00 0.000












































33 12/30/1899 0:00 0.000












































34 12/30/1899 0:00 0.000












































35 12/30/1899 0:00 0.000












































36 12/30/1899 0:00 0.000












































37 12/30/1899 0:00 0.000












































38 12/30/1899 0:00 0.000












































39 12/30/1899 0:00 0.000












































40 12/30/1899 0:00 0.000












































41 12/30/1899 0:00 0.000












































42 12/30/1899 0:00 0.000













































Sheet 7: TimeZone Ref

Full name Abbreviation Offset Time zone
Atlantic Daylight Time ADT 3:00 UTC - 3 hours
Atlantic Standard Time AST 4:00 UTC - 4 hours
Central Daylight Time CDT 5:00 UTC - 5 hours
Central Standard Time CST 6:00 UTC - 6 hours
Eastern Daylight Time EDT 4:00 UTC - 4 hours
Eastern Standard Time EST 5:00 UTC - 5 hours
Mountain Daylight Time MDT 6:00 UTC - 6 hours
Mountain Standard Time MST 7:00 UTC - 7 hours
Pacific Daylight Time PDT 7:00 UTC - 7 hours
Pacific Standard Time PST 8:00 UTC - 8 hours

Sheet 8: Event Frequency Graphs




































































































































































































































































































































































Sheet 9: Frequency Response Initiative







FRI - NERC Frequency Response Initiative



The FRI Report made recommendations to evaluate Primary Frequency Response at additional time intervals during the event recovery period.

Additional evaluations have been added to both Form 1 and Form 2 to evaluate PFR delivery for these suggested time periods.

These evaluations utilize Interconnection frequency at specific times during the recovery period and calculates the BA's delivery of PFR for each selection.

These evaluations are not part of BAL-003 and will not impact compliance to R1 of the draft standard.

The following time selections are evaluated: T+46, T+76, T+106, T+136 and T+166.

Each evaluation is a P.U. measure based on the BA's Bias setting at each of these times.

Performance is the "best" performance at the specific time through 10 seconds past each time.

This is intended to account for any delay in data in the measurement. This measurement may be changed as experience in this effort increases.



Also included is the measure of PFR delivery during the T+20 to T+52 second period, the same as R1 of the standard.

The measure (P.U.) here is based on the BA Bias setting and not the FRO. This was done to provide comparison to the additional measurement times.



Some basic observations from this data:



1) If the P.U. value is close to 1.0, the BA delivered the full amount of PFR equal to its Bias setting.

2) The average performance of the Eastern Interconnection in PFR is about 40% of the total Interconnection Bias setting. If the BA's average score is greater

than 0.40 P.U. then they are providing more PFR than the average BA. If the P.U. is less than 40% then they are providing less than average PFR.

3) If the P.U. value at T+46 is consistently less than the P.U. value at T+20 to T+52, then the PFR of the BA is not being sustained.

4) If the P.U. value at later time interval measures is consistently less, then withdrawal of PFR is occurring at a slower rate, but still being withdrawn.

5) If the P.U. value at T+20 to T+52, T+46, or T+76 is consistently greater than 1.0, this indicates that the BA Bias setting is too low.
































































































































































































































































































































































































































































































































































































File Typeapplication/vnd.ms-excel
File Modified2012-10-01
File Created1970-01-01

© 2024 OMB.report | Privacy Policy