Heat Tapes Guidelines

OMB0029_2010_17_heat tapes.pdf

Follow-Up Activities for Product-Related Injuries

Heat Tapes Guidelines

OMB: 3041-0029

Document [pdf]
Download: pdf | pdf
OMB Control Number 3041-0029

INVESTIGATION GUIDELINES

Appendix 11
October 1, 1991

HEAT TAPES

I.

INTRODUCTION
A.

Background Information

Heating tapes and cables, commonly called heat tapes, are specialized electrical heaters
that are used primarily to prevent freezing of water pipes, drain pipes, gutters and down spouts.
There are different heat tape designs for different applications (e.g., the design of heat tapes
intended to protect water pipes differs from that of heat tapes intended for gutters.) Customarily,
they are plugged into 120-V conventional receptacle outlets. Some manufacturers recommend
that they not be used with extension cords. Other manufacturers specify that, if an extension cord
is necessary, it must be properly sized, grounded, and certified for outdoor use.
Fires associated with heat tapes occur especially during the winter when the tapes are
actively heating protected devices (i.e., pipes and gutters). We are seeking information that
identifies the underlying causes of these fires so that appropriate corrective-action options can be
selected.
Beginning in the fall of 1990, a high proportion of heat
tapes and cables sold in the U. S. have been "listed" -certified to recognized voluntary safety standards by Underwriters Laboratories (UL), Canadian
Standards Association (CSA), or Factory Mutual (FM). There are differences among these
standards, but we do not yet have indications that any one of these standards is superior to the
others. Formerly, unlisted tapes were commonly available and used. If a heat tape ignition has
occurred, it is important to determine if the tape was listed or not. Listed tapes bear a label that
identifies the laboratory
that performed the qualification tests.
B.

Product Description

Heat cables and tapes are available in a wide variety of lengths and configurations.
Typical shapes vary from round or oval cables to relatively flat wide tapes. Listed tapes have a
braided metal shield covering the whole cable or tape; some metal shields are exposed, others are
covered by a jacket of electrical insulation. It is important to determine if the heat tape associated
with a fire was shielded or not. Not all shielded heat tapes Are listed.

As used in typical residential applications, pipe heat tapes are wound around a pipe or
fastened along its length and then covered with some form of insulation(s) to limit the heat loss
from the pipe. Usually moisture resistant tape is then wound over the glass-fiber strip. In
determining possible causes of ignition, it is important to know the kind of material, if any, used
to insulate the pipe and the heat tape. The instructions provided by the heat tape manufacturers
specify the material, such as glass fiber, the thickness, and the kind of over wrapping tape to be
used to protect the insulating strip from water and moisture.
There is no universal "correct" way of installing a heat
tape. The criterion for any particular tape is the manufacturer's instruction. When the
circumstances permit, photographs that illustrate the installation technique can be helpful in
determining the cause of ignition. Differences in appropriate installation practices are particularly
noted in the contrast between "resistance" type tapes and "self-regulating" tapes.
1.

Resistance vs Self-Regulating

Resistance heat tapes (See Attachment, Figure l) incorporate thin wires of electrical
resistance metals (similar to those in an electric blanket) and generate almost the same amount of
heat power regardless of temperature of the tape. Many resistance heat tapes are equipped with
thermostat switches that turn off the power to the heat tape at a temperature at which heat is no
longer required to protect the pipe or gutter. Some thermostats are intended to be fastened in
close contact with the pipe and covered with thermal insulation; others, to be mounted exposed to
air, as determined by the manufacturer and stated in the instructions.
Self-regulating heat tapes (See Attachment, Figure 2) incorporate two copper wires that
extend for the full length of the tape. When the tape is plugged into a 120-V a-c supply, the two
wires have this voltage applied and current flows between them through a black plastic
semiconducting material that also extends the full length of the tape or cable. This heating plastic
varies in electrical resistance in response to temperature. It is intended to increase in resistance at
warm temperatures so that it draws a very small current and generates very little heat. At
temperatures below freezing, however, it should decrease in resistance, draw substantial current,
and heat the pipe so that the contents will not freeze.
Self-regulating tapes may be installed in ways that resistance types may not. Because of
series resistance characteristics, resistance tapes manufacturers' instructions forbid wrapping one
turn over another, because overheating and damage may occur. On the other hand, installation of
self-regulating tapes with over-wrapped turns is not expected to cause any problem.
The same difference between the operating characteristics of these tapes permits the use of
thicker or more efficient thermal insulation over self-regulating tapes than over resistance tapes.
For instance, molded tubular insulation is recommended for use over some self-regulating tapes,
but not for resistance tapes.

2.

Shielded vs Unshielded

Another important difference among heat tapes and cables is the presence or absence of a
metal braid or stranded metal shield. Many shielded tapes are readily identified, because the
braided metal shield encloses the entire tape on the outside. Other versions also shield the entire
tape or cable, but have an additional insulating jacket covering the shield. Some resistance tape
constructions are made with two shields, one covering each of the two active conductors on
either side of the tape. In order to be listed by UL or CSA, heat tapes must be shielded.
3.

Pre-assembled vs "Do-it-yourself"

Self-regulating heat tapes are available made up to various standard lengths with
factory-assembled end seals and power cords. However, for the convenience of users who may
want to keep a substantial heat-tape supply on hand to be made up to various lengths as needed,
bulk reels of self-regulating cable are marketed, along with end seals and power plugs for field
assembly~ Detailed instructions for making up and installing these heat tapes are provided by the
manufacturer. Self-regulating heat tapes of this kind will be found with different end-seals And
plugs that represent steps in the evolution of this product. Virtually all of the self-regulating heat
tapes now being sold employ an end seal which consists of a plastic cap sealed with silicone gel
and a plug fitted with a small cartridge fuse similar to an automotive fuse.
C.

Installation, Instructions, Installers and Inspectors
1.

Improper Installations

While other factors also are involved in causing heat-tape related incidents, improper
installation or application were involved in many of the incidents reported in the FY 1991 Pilot
study. In spite of clear warnings in the instructions and packaging, pipe-heating tapes were
installed in gutters, pipe thermostats were mounted so as to measure ambient air temperature and
tubular insulation was installed over tapes intended only for use with glass fiber strip insulation.
To determine what can be done to diminish this problem, information is needed to determine
when installations were made and the causes for improper installations.
2.

Instructions

In situations where a fire incident has occurred, we need to know what instructions were
available, if they were read, and if the resulting installation followed the I instructions provided. If
the installation was improper how was it improper and what are the indications that something
went wrong?
3. Installers
It appears that part of the improper installation problem may be a mis-match between the
instructions and the people who are trying to use them. Past investigations how that installation
may be performed by mobile-home park maintenance personnel, employees of mobile home

dealers or installation contractors, plumbers, electricians, untrained friends or the resident.
Heat-tapes are a relatively complex product. A computer program was used to estimate the
educational level required to comprehend typical heat-tape instructions. All of them were
estimated at 9th-grade or higher. We need to identify the people who are doing the installing and
to try to determine if they have the instructions available, can use the instructions and use other
sources of information (Retail sales people, foremen, managers?). A significant factor in some
areas may be the installer's native language (Spanish?).
4.

Inspectors

To correct improper installations, some municipalities and large mobile-home parks
require that the heat-tape installation be inspected before electric power is connected to the home.
Particularly in cases where there has been a heat-tape related fire, we need to know if there was
an inspection and who the inspector was. It would help to know how he obtained the information
to perform the inspection.
It is equally important to find out if the installation was altered significantly after the
inspection and what alterations were performed.
D.

Operating Environment
1.

Grounds, Fuses, and Circuit-breakers

Metal shields and sheaths should be connected to the electrical system earth ground. This
connection is provided by the round pin of the three conductor a-c plug and the third-wire
grounding conductor of the residential electrical system. When this ground system is complete, it
can provide important protection against electrical fires. If some mechanical or overheating injury
to the heat tape insulation creates a "short" circuit between "live" conductors of the cable and the
shield, the resulting excessive current may cause the branch fuse or circuit to open and atop the
current to the heat tape and thus disconnect the energy source that could support ignition.
The same fuse or circuit breaker, usually located back at the residence' electrical service
panel, provides some degree of protection against fires that can be caused by a "short" circuit
between the two power connections, line or "hot," and neutral. If the current through the
line-to-line fault is great enough, the fuse or circuit breaker will disconnect the energy that is
driving the ignition source.
To determine the role of the standard 15- or 20-ampere branch circuit protection in
preventing heat-tape related fires, we need to know the level of protection (Did someone
substitute a 30-ampere fuse?) at the time, whether or not the device opened the circuit, and any
other related details. (Was the heat tape plugged into an active power circuit?)
An innovation in heat-tape technology is the provision, in self-regulating heat tapes, of
individual fuses for heat tapes integral to the a-c plug body. When these tapes are involved in a
fire incident, we need to know the fuse ratings and whether or not the fuses opened.

2.

Ground Fault Circuit Interrupters (GFCIs)

Incidents that may have involved a ground-fault-circuit interrupter (GFCI) can provide
valuable information about heat tapes, and about mobile homes. Older technology GFCIs may
have been overly sensitive to spurious signals. Also, a GFCI located under a mobile home did not
provide any alarm in the home, if it tripped. The resident would not be aware that the heat tape
was disconnected until a water pipe was frozen. As a result, the federal standard governing
mobile-home construction forbids GFCI protection of the heat-tape outlet intended for protection
of the water supply pipe.
GFCIs can provide protection at much lower ground-fault current levels than standard
branch circuit protection. Incidents where a heat tape was plugged into a GFCI-protected circuit
are of special interest in this project.
3.

Extension Cords and Receptacle Outlets

UL requires that the label for listed heat tapes warn against the use of an extension cord to
connect the tape. There are several reasons for this warning, but the overriding reason is that the
use of a flexible cord as a substitute for residential fixed wiring is a violation of the National
Electrical Code. In effect, this means that extension cords are only intended for temporary use.
In practice, heat tapes are connected by means of extension cords because the distance
from the receptacle outlet to the pipe that is to be protected maybe longer than the power-cord
section of the heat tape. The home-owner does not want to pay to rearrange the wiring or
plumbing, so an extension cord maybe used as permanent wiring.
Some, usually older-technology, extension cords and receptacle outlets have been
involved in heat-tape overheating incidents. Sometimes it is difficult or impossible to determine if
overheating commenced in the heat-tape power plug and cable or the extension-cord outlet or the
receptacle outlet. Before ignition occurs, both - components involved may have suffered
overheating damage. Some extension cords have been subject to overheating of the connections
between the wire conductor and the metal connector; some receptacle outlets overheat because of
deterioration of the spring-edge contact of back-wired connections or because screw-type
terminals were not tightened properly. Also, aluminum wire has been involved in overheating
connections.
If the ignition occurred at the plug end of the heat tape, we need information about the
extension cord, if one was in use, or the receptacle outlet. When possible, these should be
sampled or photographed. It is important to observe the condition of these components whether
they did or did not contribute to overheating.

II.

INSTRUCTIONS FOR COLLECTING SPECIFIC INFORMATION
A.

Summary

Describe the incident, its results, any injuries, the damage, the sequence of events leading
to the incident, and the apparent role of the heat-tape or cable in the incident.
B.

Specific Objectives

Identify and describe the heat tape, including:
Make, model number, length, power(watts)
Listed, by whom, shielded or unshielded
Resistance type or self-regulating
Pre-assembled or "do-it-yourself"
Materials, construction, condition of end seal and
sketches)
Labeling and instructions

power plug (photo's or

Describe the environment of the heat tape and its installation including annual use pattern;
exposure to weather; means of connecting to 120-V electric power; heat tape wrapped around
pipe or fastened parallel to pipe, extent, thickness and over covering of pipe insulation, if present,
failures or damage to related equipment, material, etc. Verify that the heat tape was plugged in at
the time of the incident.
Describe observable damage to heat tape sustained prior to incident, during incident. Did
the damage appear to be related to incident? What are the specific indications of this? was the
heat tape buried, immersed, or exposed to salt spray or atmosphere?
When possible, support description with captioned photographs.
Identify the installer of the heat tape and determine what sources of information he used to
determine the method and details of installing the heat tape. Try to determine the education,
relevant training and experience level of the installer. Determine the date of installation.
If the installation was inspected after completion, determine who performed the
inspection, his authority or agency, his education, training and experience. Where did he obtain
information about correct method of installation?
Determine the extent of knowledge of the heat tape and installation of the residents of the
residence. Were the residents responsible for maintaining the heat tape, or the mobile-home-park
manager, the landlord, or someone else?

C.

Incident Environment

Indicate the location, single family home, mobile home, beach house, etc.
Try to obtain the fire department report of the incident; interview the fire official who
determined the first material ignited to obtain supporting details. Obtain copies of insurance
reports or repair invoices.
Indicate apparent deviations from recommended installation procedures, including
extension cords (flat or round?, listed?, wire specification on cord?)
Describe the electrical supply to the heat tape, two-conductor outlet?, three conductor
outlet? fuse or circuit-breaker rating (amperes). Did heat tape share outlet with other appliances?
Did fuse or circuit breaker open the circuit at the time of the incident? GFCI protected? Did
GFCI open circuit at time of incident? If not, record manufacturer, age, model number and serial
number of GFCI.
Describe the general characteristics of location, including the function, length, size (outer
diameter) and material of covered pipe, the location of the thermostat, type of thermal insulation,
thickness of insulation.
Did materials other than the heat tape ignite? What are the indications as to how the
ignition took place? How did the ignition take place? Were other flammable materials in the
vicinity of the heat tape? What were they?
Determine details of use of the heat tape that might bear on its reliability -- annual
checkup?, summer shut-down?, use on more than one pipe? use of more than one heater tape on a
pipe?, etc.
D.

Other

Identify the first material to ignite.
Was the heat tape assembly exposed to water or moisture?; partially buried?
Identify and report the make, etc. of any heat tape that was installed to replace the incident
tape.

HEAT TAPE DATA FORM
BACKGROUND:
1. Task number:
2. Date of incident: (year, month, day)

____

3. Time of incident:

____a.m.

4. Date of investigation: (year, month, day) ____

____

____
____ p.m.

____

____

5. Date heat tape was installed: (year, month, day) ____

____

____

6. Type of structure where heat tape was installed:
a) under mobile home ____
b) beside mobile home
c) beside built home
d) crawl space built home
e) basement
f) attic/loft
g) gutter
h) downspout
i) plants
j) buried
k) other

____
____
____
____
____
____
____
____
____
____

7. If a mobile home, give make, model and date of manufacture:
______________________________________________________
8. In addition to the heat tape, what other materials ignited?
______________________________________________________
9. Did fire start under a water heater?
a) yes ___

b) no ___

c) don't know ___

d) not available ___

10. Warmest and coldest temperatures in the 24 hours preceding the incident:
warmest __________
coldest __________

PERSONAL AND PROPERTY DAMAGE:
11. Was a victim/s involved in the incident? a) yes ____
12. Victim/s age/s:

b) no ____

______________________

13. Victim/s sex:

a) male/s _____

14. Victim/s height/s:

b) female/s _____

______________________

15. Did the victim/s have any competency reducing factors?
a) impaired vision ___
b) physical handicaps ___
c) medication ___
d) other
___
16. Nature and type of the victim/s injury/ies:
___________________________________________________________________
___________________________________________________________________
___________________________________________________________________
17. What kind of experience and/or knowledge did the victim/s have of the heat tape?
___________________________________________________________________
___________________________________________________________________
___________________________________________________________________
18. Amount of property damage:

______________________________

HEAT TAPE INFORMATION:
19. Type of heat tape involved:
a) self-regulating, shielded
___
b) self-regulating, no shielded ___
c) resistance, shielded ___
d) resistance, no shield
___
e) don't know
___
20. Heat tape age (months and/or years):

_______________________________

21. If a fused plug was used, did it open?
a) yes ___

b) no ___

c) don't know ___

d) not available ___

22. Color of tape:

_________________________________________________

23. Brand name:
a) Easy Heat
b) Frostex
c) Raychem
d) Raychem/Frostex
e) Smith-Gates
f) Smith-Gates/Easy Heat
g) Wrap-On
h) Other

___
___
___
___
___
___
___
___

ATTACHMENT

FIGURE 1 TYPICAL RESISTANCE HEAT TAPE (UNSHIELDED)

FIGURE 2 TYPICAL SELF-REGULATING HEAT TAPE (UNSHIELDED)


File Typeapplication/pdf
File TitleAppendix 11 - Heat Tapes
SubjectHeating cables, or heat tapes, have been known to start fires, primarily in winter when they are actively heating protected devi
AuthorEXHR