Download:
pdf |
pdfExhibit B
Implementation Plans
Exhibit B-1a
Implementation Plan PRC-005-6
Implementation Plan
Project 2007-17.4 PRC-005 FERC Order No. 803 Directive
PRC-005-6
Standards Involved
Approval:
PRC‐005‐6 – Protection System, Automatic Reclosing, and Sudden Pressure Relaying
Maintenance
Retirement:
PRC‐005‐5 – Protection System, Automatic Reclosing, and Sudden Pressure Relaying
Maintenance
PRC‐005‐4 Protection System, Automatic Reclosing, and Sudden Pressure Relaying Maintenance
PRC‐005‐3 (ii) Protection System and Automatic Reclosing Maintenance
PRC‐005‐3 (i) Protection System and Automatic Reclosing Maintenance
PRC‐005‐3 Protection System and Automatic Reclosing Maintenance
PRC‐005‐2 (ii) Protection System Maintenance
PRC‐005‐2 (i) Protection System Maintenance
PRC‐005‐1.1b – Transmission and Generation Protection System Maintenance and Testing
PRC‐008‐0 – Implementation and Documentation of Underfrequency Load Shedding Equipment
Maintenance Program
PRC‐011‐0 – Undervoltage Load Shedding System Maintenance and Testing
PRC‐017‐0 – Special Protection System Maintenance and Testing
Prerequisite Approvals:
N/A
Background:
In Order No. 803, FERC approved Standard PRC‐005‐3 and, in Paragraph 31, directed NERC to:
"...develop modifications to PRC‐005‐3 to include supervisory devices
associated with auto‐reclosing relay schemes to which the Reliability
Standard applies. Further, we clarify that NERC’s proposal regarding the
scope of supervisory devices is an acceptable approach to satisfy the
Commission directive. Specifically, NERC proposed in its NOPR comments,
and we find acceptable, that the scope of the supervisory devices to be
encompassed in the Reliability Standard are those providing voltage
supervision, supervisory inputs associated with selective autoreclosing,
and sync‐check relays that are part of a reclosing scheme covered by PRC‐
005‐3."
This Implementation Plan addresses:
The implementation of changes relating to maintenance and testing of supervisory relays and
associated voltage sensing devices related to Automatic Reclosing.
The phased implementation approach included in the approved PRC‐005‐2(i) (PRC‐005‐2 has
been retired by PRC‐005‐2(i)) will remain as‐is and is carried forward and incorporated by
reference.
Because PRC‐005‐6 incorporates all revisions to date, this implementation plan will supersede
the implementation plans for PRC‐005‐2(ii), PRC‐005‐3, PRC‐005‐3(i), PRC‐005‐3(ii), PRC‐005‐4
and PRC‐005‐5 when PRC‐005‐6 becomes effective. PRC‐005‐2(i) will remain in effect and not be
retired until entities are required to be compliant with R1, R2, and R5 of the PRC‐005‐6 standard
under this implementation plan.
The Implementation Plan reflects consideration of the following:
1.
The requirements set forth in the proposed standard, which carry forward requirements from PRC‐
005‐2, PRC‐005‐2(i), PRC‐005‐2(ii), PRC‐005‐3, PRC‐005‐3(i), PRC‐005‐3(ii), PRC‐005‐4 and PRC‐005‐
5, establish minimum maintenance activities for Protection System, Automatic Reclosing, and
Sudden Pressure Relaying Component Types as well as the maximum allowable maintenance
intervals for these maintenance activities.
2.
The maintenance activities established in the various PRC‐005 versions may not be presently
performed by some registered entities and the established maximum allowable intervals may be
shorter than those currently in use by some entities. Therefore, registered entities may not be
presently performing a maintenance activity or may be using longer intervals than the maximum
allowable intervals established in the PRC‐005 standards. For these registered entities, it is
unrealistic to become immediately compliant with the new activities or intervals. Further,
registered entities should be allowed to become compliant in such a way as to facilitate a
continuing PRC‐005 maintenance program. The registered entities that have previously been
Project 2007‐17.4 PRC‐005 FERC Order No. 803 Directive
Implementation Plan
2
performing maintenance within the newly specified intervals may not have all the documentation
needed to demonstrate compliance with all of the maintenance activities specified.
3.
The implementation schedule set forth below carries forward and incorporates by reference the
implementation schedules contained in the currently‐effective PRC‐005‐2(i) implementation plan
(which in turn incorporates by reference the PRC‐005‐2 implementation plan)), and combines the
implementation schedules for PRC‐005‐2(ii), PRC‐005‐3, PRC‐005‐3(i), PRC‐005‐3(ii), PRC‐005‐4 and
PRC‐005‐5. In addition, the implementation schedule includes changes needed to address the
addition of Automatic Reclosing supervisory relays and associated voltage sensing devices in PRC‐
005‐6.
General Considerations:
Each Transmission Owner, Generator Owner, and Distribution Provider shall maintain documentation to
demonstrate compliance with PRC‐005‐1.1b, PRC‐008‐0, PRC‐011‐0, and PRC‐017‐0 until that entity
meets all of the requirements of the currently effective PRC‐005‐2(i), or its combined successor
standards, in accordance with this implementation plan.
While registered entities are implementing the requirements of PRC‐005‐2(i) or its combined successor
standards, each registered entity must be prepared to identify whether its applicable Protection
System, Automatic Reclosing, and Sudden Pressure Relaying Components were last maintained
according to PRC‐005‐2(i) (or its combined successor standards), PRC‐005‐1.1b, PRC‐008‐0, PRC‐011‐0,
PRC‐017‐0, or a combination thereof.
Effective Date
PRC‐005‐6 shall become effective on the first day of the first calendar quarter after the date that the
standard is approved by an applicable governmental authority or as otherwise provided for in a
jurisdiction where approval by an applicable governmental authority is required for a standard to go
into effect. Where approval by an applicable governmental authority is not required, the standard shall
become effective on the first day of the first calendar quarter after the date the standard is adopted by
the NERC Board of Trustees or as otherwise provided for in that jurisdiction.
Retirement of Existing Standards:
Standards PRC‐005‐1.1b, PRC‐008‐0, PRC‐011‐0, and PRC‐017‐0 shall remain enforceable throughout
the phased implementation period set forth in the PRC‐005‐2(i) implementation plan, incorporated
herein by reference, and shall be applicable to a registered entity’s Protection System Component
maintenance activities not yet transitioned to PRC‐005‐2(i) or its combined successor standards.
Standards PRC‐005‐1.1b, PRC‐008‐0, PRC‐011‐0, and PRC‐017‐0 shall be retired at midnight of March 31,
2027 or as otherwise made effective pursuant to the laws applicable to such Electric Reliability
Organization (ERO) governmental authorities; or, in those jurisdictions where no regulatory approval is
required, at midnight of March 31, 2027.
Project 2007‐17.4 PRC‐005 FERC Order No. 803 Directive
Implementation Plan
3
PRC‐005‐2(i) shall be retired at midnight of the day immediately prior to the first day of the first
calendar quarter that is twelve (12) calendar months following applicable regulatory approval of PRC‐
005‐6, or as otherwise made effective pursuant to the laws applicable to such ERO governmental
authorities; or, in those jurisdictions where no regulatory approval is required, the first day of the first
calendar quarter following the date of Board of Trustees’ adoption.
If approved by the applicable ERO governmental authority prior to the approval of PRC‐005‐6, PRC‐005‐
2(ii), PRC‐005‐3, PRC‐005‐3(i), PRC‐005‐3(ii), PRC‐005‐4 and PRC‐005‐5 shall be retired on the date
immediately prior to the first day of the first calendar quarter following regulatory approval of PRC‐005‐
6.
Implementation Plan for Definitions:
This section includes all newly defined or revised terms used in the proposed standard. Terms already
defined in the Reliability Standards Glossary of Terms (Glossary) are not repeated here. New or revised
definitions listed below become approved when the proposed standard is approved by applicable
governmental authority or as otherwise provided for in a jurisdiction where approval by an applicable
governmental authority is required for a standard to go into effect. When the standard becomes
effective, the Glossary definition will be removed from the individual standard and added to the
Glossary. The definitions of terms used only in the standard will remain in the standard.
Glossary Definition:
Protection System Maintenance Program (PSMP) ‐ An ongoing program by which Protection System,
Automatic Reclosing, and Sudden Pressure Relaying Components are kept in working order and proper
operation of malfunctioning Components is restored. A maintenance program for a specific
Component includes one or more of the following activities:
Verify — Determine that the Component is functioning correctly.
Monitor — Observe the routine in‐service operation of the Component.
Test — Apply signals to a Component to observe functional performance or output
behavior, or to diagnose problems.
Inspect — Examine for signs of Component failure, reduced performance or
degradation.
Calibrate — Adjust the operating threshold or measurement accuracy of a measuring
element to meet the intended performance requirement.
Definitions of Terms Used in the Standard:
Automatic Reclosing – Includes the following Components:
Reclosing relay
Project 2007‐17.4 PRC‐005 FERC Order No. 803 Directive
Implementation Plan
4
Supervisory relay(s) or function(s) – relay(s) or function(s) that perform voltage and/or
sync check functions that enable or disable operation of the reclosing relay
Voltage sensing devices associated with the supervisory relay(s)
Control circuitry associated with the reclosing relay or supervisory relay(s)
Component Type –
Any one of the five specific elements of a Protection System.
Any one of the four specific elements of Automatic Reclosing.
Any one of the two specific elements of Sudden Pressure Relaying.
Component – Any individual discrete piece of equipment included in a Protection System,
Automatic Reclosing, or Sudden Pressure Relaying.
Countable Event – A failure of a Component requiring repair or replacement, any condition
discovered during the maintenance activities in Tables 1‐1 through 1‐5, Table 3, Tables 4‐1
through 4‐3, and Table 5, which requires corrective action or a Protection System Misoperation
attributed to hardware failure or calibration failure. Misoperations due to product design
errors, software errors, relay settings different from specified settings, Protection System
Component, Automatic Reclosing, or Sudden Pressure Relaying configuration or application
errors are not included in Countable Events.
Sudden Pressure Relaying ‐ A system that trips an interrupting device(s) to isolate the
equipment it is monitoring and includes the following Components:
Fault pressure relay – a mechanical relay or device that detects rapid changes in gas
pressure, oil pressure, or oil flow that are indicative of Faults within liquid‐filled, wire‐
wound equipment
Control circuitry associated with a fault pressure relay
Implementation Plan for New or Revised Definitions:
The revised definitions (Protection System Maintenance Program, Automatic Reclosing, Component
Type, Component, Countable Event and Sudden Pressure Relaying) become effective upon the effective
date of PRC‐005‐6.
Implementation Plan for PRC-005-2(i) and PRC-005-6
All Components with existing requirements under currently effective PRC‐005‐2(i) will continue to
follow the PRC‐005‐2(i) implementation plan, which is incorporated herein by reference. Those
Project 2007‐17.4 PRC‐005 FERC Order No. 803 Directive
Implementation Plan
5
Components and/or Facilities newly introduced by PRC‐005‐2(ii),* PRC‐005‐3, PRC‐005‐3(i), PRC‐005‐
3(ii),* PRC‐005‐4, PRC‐005‐5 and PRC‐005‐6 (including Sudden Pressure Relaying, Automatic Reclosing
Components, and dispersed generation resources) will be covered by the following Implementation
Plan:
Requirements R1, R2, and R5:
PRC‐005‐6: For Automatic Reclosing Components, Sudden Pressure Relaying Components, and
dispersed generation resources, entities shall be 100% compliant on the first day of the first calendar
quarter twelve (12) months following applicable regulatory approvals of PRC‐005‐6 or, in those
jurisdictions where no regulatory approval is required, on the first day of the first calendar quarter
twenty‐four (24) months following NERC Board of Trustees’ adoption of PRC‐005‐6 or as otherwise
made effective pursuant to the laws applicable to such ERO governmental authorities.
Implementation Plan for Requirements R3 and R4:
PRC‐005‐6:
1. For Automatic Reclosing Components, Sudden Pressure Relaying Components, and dispersed
generation resources maintenance activities with maximum allowable intervals of six (6) calendar
years, as established in Tables 4‐1, 4‐2(a), 4‐2(b), 4‐3, and 5:
The entity shall be at least 30% compliant on the first day of the first calendar quarter thirty‐six
(36) months following applicable regulatory approval of PRC‐005‐6 (or, for generating plants
with scheduled outage intervals exceeding three years, at the conclusion of the first succeeding
maintenance outage) or, in those jurisdictions where no regulatory approval is required, on the
first day of the first calendar quarter forty‐eight (48) months following NERC Board of Trustees’
adoption of PRC‐005‐6 or as otherwise made effective pursuant to the laws applicable to such
ERO governmental authorities.
The entity shall be at least 60% compliant on the first day of the first calendar quarter sixty (60)
months following applicable regulatory approval of PRC‐005‐6 or, in those jurisdictions where
no regulatory approval is required, on the first day of the first calendar quarter seventy‐two
(72) months following NERC Board of Trustees’ adoption of PRC‐005‐6, or as otherwise made
effective pursuant to the laws applicable to such ERO governmental authorities.
The entity shall be 100% compliant on the first day of the first calendar quarter eighty‐four (84)
months following applicable regulatory approval of PRC‐005‐6 or, in those jurisdictions where
no regulatory approval is required, on the first day of the first calendar quarter ninety‐six (96)
months following NERC Board of Trustees’ adoption of PRC‐005‐6 or as otherwise made
effective pursuant to the laws applicable to such ERO governmental authorities.
*The proposed Implementation Plan for the Revised Definition of “Remedial Action Scheme” developed as part of Project
2010‐05.2 – Special Protection Systems shall continue to govern implementation of the revised Remedial Action Scheme
definition, including implementation for entities with newly classified “Remedial Action Scheme.”
Project 2007‐17.4 PRC‐005 FERC Order No. 803 Directive
Implementation Plan
6
2. For Automatic Reclosing Components, Sudden Pressure Relaying Components, and dispersed
generation resources maintenance activities, with maximum allowable intervals of twelve (12)
calendar years, as established in Table 4‐1, 4.2(a), 4.2(b), 4‐3, and 5:
The entity shall be at least 30% compliant on the first day of the first calendar quarter sixty (60)
months following applicable regulatory approval of PRC‐005‐6 or, in those jurisdictions where
no regulatory approval is required, on the first day of the first calendar quarter seventy‐two
(72) months following NERC Board of Trustees’ adoption of PRC‐005‐6 or as otherwise made
effective pursuant to the laws applicable to such ERO governmental authorities.
The entity shall be at least 60% compliant on the first day of the first calendar quarter following
one hundred eight (108) months following applicable regulatory approval of PRC‐005‐6 or, in
those jurisdictions where no regulatory approval is required, on the first day of the first
calendar quarter one hundred twenty (120) months following NERC Board of Trustees’
adoption of PRC‐005‐6 or as otherwise made effective pursuant to the laws applicable to such
ERO governmental authorities.
The entity shall be 100% compliant on the first day of the first calendar quarter one hundred
fifty‐six (156) months following applicable regulatory approval of PRC‐005‐6 or, in those
jurisdictions where no regulatory approval is required, on the first day of the first calendar
quarter one hundred sixty‐eight (168) months following NERC Board of Trustees’ adoption of
PRC‐005‐6 or as otherwise made effective pursuant to the laws applicable to such ERO
governmental authorities.
Applicability:
This standard applies to the following functional entities:
Transmission Owner
Generator Owner
Distribution Provider
Project 2007‐17.4 PRC‐005 FERC Order No. 803 Directive
Implementation Plan
7
Exhibit B-1b
Implementation Plan Rationale PRC-005-6
Alignment of PRC‐005 Compliance Dates
I.
PRC‐005 Compliance Issue and Proposal to Align Compliance Dates
Since the approval of PRC‐005‐2, a number of standards development projects have resulted in either
including or excluding devices from the scope of PRC‐005. Currently, there are eight approved or
currently proposed PRC‐005 versions, and each Version comes with a separate implementation
schedule. Version PRC‐005‐2(i) is the current mandatory and enforceable version as of the date of this
posting. Depending on the type of device and specific requirement in some of the PRC‐005 versions, the
implementation is divided into phases, requiring registered entities to gradually ensure compliance of a
percentage of their devices until they reach 100% compliance.
Versions ‐3, ‐4, and ‐6 will require three consecutive updates to the registered entities’ Protection
System Maintenance Programs (PSMP), which is expected to be a time‐consuming task for many
entities. Based on the implementation plans for these three versions, the required PSMP updates would
have to be completed within one (1) year to eighteen (18) months. According to the PRC‐005 drafting
team, which represents various industry members, this short period of time for review and identification
of all assets subject to the revised PRC‐005 versions could lead to errors and misidentification of devices.
Further, the existence of eight implementation plans could lead to misinterpretations and
inconsistencies in the compliance and auditing practices throughout the Electric Reliability Organization
(ERO) Enterprise.
To address this compliance issue, the PRC‐005 drafting team requested that NERC align the effective
dates of all outstanding PRC‐005 Versions, thus simplifying the implementation schedule for this
Reliability Standard. In response to the drafting team’s request, NERC plans to petition the Federal
Energy Regulatory Commission (FERC) to delay the implementation of approved versions PRC‐005‐3 and
PRC‐005‐4. Because PRC‐005‐6 reflects the new applicability that has been introduced by PRC‐005‐2(ii),
PRC‐005‐3, PRC‐005‐3(i), PRC‐005‐3(ii), PRC‐005‐4, PRC‐005‐5, and PRC‐005‐6, when PRC‐005‐6 becomes
effective, all new applicability will become effective and aligned to the same dates. NERC proposes that
the phased in implementation of PRC‐005‐2 continue in accordance with the PRC‐005‐2 implementation
plan, which is incorporated by reference into the implementation plan for currently‐effective PRC‐005‐
2(i).The phased implementation approach will remain but the effective dates for each phase will align
applicability.
This proposal is reflected in the implementation plan for PRC‐005‐6. If supported by industry members
and adopted by the NERC Board of Trustees, the implementation plan will be included in the PRC‐005‐6
petition to be filed with FERC for approval.
II.
PRC‐005 Versions Overview
The draft PRC‐005‐6 incorporates all revisions made to PRC‐005‐2 as a result of the development of PRC‐
005‐2(i) (the currently‐effective version), PRC‐005‐2(ii), PRC‐005‐3, PRC‐005‐3(i), PRC‐005‐3(ii), PRC‐005‐
4, and PRC‐005‐5, and PRC‐005‐6. Version ‐3 added Automatic Reclosing devices; versions 2(i), 3(i), and
‐5 exclude individual dispersed generation resources from the applicability of the standard; versions 2(ii)
and 3(ii) replace the term “Special Protection System” with the term “Remedial Action Scheme”; version
‐4 added Sudden Pressure Relays; and version ‐6 will add supervisory relays and exclude individual
dispersed generation resources from the applicability of this Reliability Standard.
Implementation Plan Rationale: October 9, 2015
Page 1 of 3
From this list of all PRC‐005 versions, versions 2(i), 3, 3(i), and 4 are approved by FERC; PRC‐005‐2(ii) and
PRC‐005‐3(ii) are pending regulatory approval; PRC‐005‐5 has not yet been filed for approval with FERC;
and PRC‐005‐6 is currently under development.
III.
Impact on the Reliability of the Bulk Power System and on Compliance with PRC‐005
Based on the implementation schedule for the FERC‐approved PRC‐005‐3, PRC‐005‐3(i), and PRC‐005‐4,
and estimated approval and effective dates for the remaining versions, the delay in the implementation
of PRC‐005‐3 and PRC‐005‐4 created by this proposal is anticipated to be approximately one year.
The proposed changes described here and in the proposed PRC‐005‐6 implementation plan will not
affect the immediate implementation of version 2(i). This version excludes certain dispersed generation
resources from the definition of Bulk Electric System, and from the applicability of PRC‐005. Thus,
registered entities that own and operate dispersed generation resources will remain unaffected by the
proposed changes.
PRC‐005‐2(ii) and PRC‐005‐3(ii), which as of this writing are pending before the Commission, reflect
enhancements to the NERC Glossary of Terms related to Special Protection Systems and Remedial
Action Schemes. A potential delay in implementation of the revised definition of Remedial Action
Scheme would not present a risk to the reliability of the Bulk Power System (BPS). Finally, the
anticipated changes related to Remedial Action Schemes are minor in nature and are unlikely to
introduce an actual reliability risk.
Because the Automatic Reclosing devices and Sudden Pressure Relays brought in by versions ‐3 and ‐4
are limited in scope, a potential delay in the implementation of these versions of PRC‐005 is also unlikely
to increase risk to the BPS. Many of these devices are already monitored by industry in anticipation of
the upcoming compliance requirements, but may not be specifically included in the registered entities’
PSMPs at this time.
IV.
Benefits to Registered Entities
The proposal aims to simplify the compliance efforts of all registered entities subject to PRC‐005 and
give industry additional time to comply with versions ‐3, ‐4, and ‐6, which require PSMP updates. Having
PRC‐005‐2(ii), PRC‐005‐3, PRC‐005‐3(i), PRC‐005‐3(ii), PRC‐005‐4, PRC‐005‐5, and PRC‐005‐6 essentially
become effective at the same time through a single, unified PRC‐005‐6 Reliability Standard and
associated implementation plan minimizes the possibility of misinterpretations of multiple PRC‐005
versions and associated compliance obligations, thus limiting the compliance risk for registered entities.
In addition, the proposed changes will not affect the anticipated exclusion of certain dispersed
generation resources from the scope of the standard.
To further facilitate compliance, NERC plans to use the additional time until PRC‐005‐6 becomes
effective to conduct outreach and provide training to ensure that registered entities are well aware and
prepared to meet their obligations under the various PRC‐005 versions.
Implementation Plan Rationale
Page 2 of 3
Effective Date Information
Table 1 provides information regarding each version of the PRC‐005 standard.
Table 1: PRC-005 Effective Date Information
Standard
Effective Date1
PRC‐005‐2
April 1, 2015
Comments
Proposed effective date with
version 2, which was
immediately following FERC
approval.
PRC‐005‐2(i)
May 29, 2015
PRC‐005‐2(ii)
Filed and Pending Regulatory Approval
Proposed to be deferred; will be
replaced with version 6.2
PRC‐005‐3
April 1, 2016
Proposed to be deferred; will be
replaced with version 6.
PRC‐005‐3(i)
April 1, 2016
Proposed to be deferred; will be
replaced with version 6.
PRC‐005‐3(ii)
Filed and Pending Regulatory Approval
Proposed to be deferred; will be
replaced with version 6.
PRC‐005‐4
January 1, 2016
Proposed to be deferred; will be
replaced with version 6.
PRC‐005‐5
Pending Regulatory Filing
Proposed to be deferred; will be
replaced with version 6.
PRC‐005‐6
Pending Regulatory Filing
TBD
The effective date listed is the start date of when the standard becomes effective. This does not include the
phased in approach.
2
The effective date is dependent on when FERC approves PRC‐005‐6, which could be from three (3) months to one
(1) year after submittal of the petition for approval.
1
Implementation Plan Rationale
Page 3 of 3
Exhibit B-2
Implementation Plan PRC-005-5 (Alternative)
Implementation Plan
Project 2014-01 Standards Applicability for Dispersed Power
Producing Resources
PRC-005-5
Standards Involved
Approval:
•
PRC-005-5 – Protection System, Automatic Reclosing, and Sudden Pressure Relaying
Maintenance
Retirement:
•
PRC-005-4 – Protection System, Automatic Reclosing, and Sudden Pressure Relaying
Maintenance
Prerequisite Approvals
N/A
Background
In light of the adoption of a revised “Bulk Electric System” definition by the NERC Board of Trustees
(Board), changes to the applicability sections of certain Reliability Standards, including PRC-005, are
necessary to align with the implementation of the revised BES definition. The Dispersed Generation
Resources Standard Drafting Team (DGR SDT) for Project 2014-01 – Standards Applicability for
Dispersed Power Producing Resources has modified the applicability section of certain Generator
Owner/Generator Operator requirements to recognize the unique technical and reliability aspects of
dispersed power producing resources in order to ensure the applicability of the standards is consistent
with the reliable operation of the BES.
General Considerations
Reliability Standard PRC-005-4, with its associated Implementation Plan, was adopted by the Board on
November 13, 2014. The DGR SDT has revised the applicability section of PRC-005-4 to align the
standard with the revised definition of the BES.
Effective Date
PRC-005-5 shall become effective on the later of the first day following the Effective Date of PRC-005-4
or the first day following approval by an applicable governmental authority or as otherwise provided for
in a jurisdiction where approval by an applicable governmental authority is required for a standard to go
into effect. Where approval by an applicable governmental authority is not required, the standard shall
become effective on the later of the first day following the Effective Date of PRC-005-4 or the first day
of the first calendar quarter after the date the standard is adopted by the Board or as otherwise
provided for in that jurisdiction.
Retirement of Existing Standards
PRC-005-4 shall be retired at midnight of the day immediately prior to the Effective Date of PRC-005-5
in the particular jurisdiction in which the revised standard is becoming effective.
Implementation Plan
PRC-005-5 only modifies the applicability for PRC-005-4. All aspects of the Implementation Plan for
PRC-005-4 will remain applicable to PRC-005-5 and are incorporated here by reference.
Cross References
The Implementation Plan for the revised definition of “Bulk Electric System” is available here.
The Implementation Plan for PRC-005-4 is available here.
Project 2014-01 Standards Applicability for Dispersed Power Producing Resources
Implementation Plan - PRC-005-5
February, 2015
2
File Type | application/pdf |
File Title | Microsoft Word - Exhibit A FAC-003-2 Clean and Redline Version |
Author | baughanc |
File Modified | 2016-03-03 |
File Created | 2015-11-04 |