UNITED STATES OF AMERICA
BEFORE THE
FEDERAL ENERGY REGULATORY COMMISSION

North American Electric Reliability
Corporation

)
)

Docket No. ____________

PETITION OF THE
NORTH AMERICAN ELECTRIC RELIABILITY CORPORATION
FOR APPROVAL OF PROPOSED RELIABILITY STANDARD
TPL-007-2
Charles Berardesco
Interim President and Chief Executive Officer
North American Electric Reliability
Corporation
1325 G Street, N.W., Suite 600
Washington, DC 20005
(202) 400-3000
(202) 644-8099 – facsimile
[email protected]

Shamai Elstein
Senior Counsel
Lauren A. Perotti
Counsel
Candice Castaneda
Counsel
North American Electric Reliability
Corporation
1325 G Street, N.W., Suite 600
Washington, DC 20005
(202) 400-3000
(202) 644-8099 – facsimile
[email protected]
[email protected]
[email protected]

Counsel for the North American Electric
Reliability Corporation

January 22, 2018

TABLE OF CONTENTS

I. EXECUTIVE SUMMARY .................................................................................................... 3
II. NOTICES AND COMMUNICATIONS ................................................................................ 5
III. BACKGROUND .................................................................................................................... 5
A.
Regulatory Framework .................................................................................................... 5
B.

NERC Reliability Standards Development Procedure .................................................... 6

C.

Procedural History of Proposed Reliability Standard TPL-007-2 ................................... 7
1.

History of Reliability Standard TPL-007-1 and Order No. 830 ................................... 7

2.

Project 2013-03 Geomagnetic Disturbance Mitigation ................................................ 9

IV. JUSTIFICATION FOR APPROVAL................................................................................... 10
A.
The Supplemental GMD Event ...................................................................................... 11
B.
New and Revised Requirements to Perform GMD Vulnerability Assessments Based on
the Supplemental GMD Event .................................................................................................. 14
1.

Proposed Requirement R8 .......................................................................................... 14

2.

Proposed Requirements R9 and R10 .......................................................................... 16

C.

New Requirements for the Collection of GMD Data (R11 and R12)............................ 18

D.

Revised Deadlines for Corrective Action Plans in Requirement R7 ............................. 19

E.

Enforceability of Proposed Reliability Standard TPL-007-2......................................... 24

V. EFFECTIVE DATE .............................................................................................................. 25
VI. UPDATE ON NERC’S ONGOING GMD RESEARCH WORK PLAN AND SECTION
1600 GMD DATA REQUEST ACTIVITIES ...................................................................... 26
VII. CONCLUSION ..................................................................................................................... 28
Exhibit A

Proposed Reliability Standard TPL-007-2 – Transmission System Planned
Performance for Geomagnetic Disturbance Operations

Exhibit B

Implementation Plan for Proposed Reliability Standard TPL-007-2

Exhibit C

Analysis of Violation Risk Factors and Violation Severity Levels

Exhibit D

Summary of Development History and Complete Record of Development

Exhibit E

Order No. 672 Criteria for Proposed Reliability Standard TPL-007-2

Exhibit F

Standard Drafting Team Roster for Project 2013-03

Exhibit G

Transformer Thermal Impact Assessment White Paper

i

TABLE OF CONTENTS
Exhibit H

Screening Criterion for Transformer Thermal Impact Assessment White Paper

Exhibit I

Supplemental GMD Event Description White Paper

Exhibit J

Consideration of Directives

ii

UNITED STATES OF AMERICA
BEFORE THE
FEDERAL ENERGY REGULATORY COMMISSION

North American Electric Reliability
Corporation

)
)

Docket Nos. ____________

PETITION OF THE
NORTH AMERICAN ELECTRIC RELIABILITY CORPORATION
FOR APPROVAL OF PROPOSED RELIABILITY STANDARD TPL-007-2
Pursuant to Section 215(d)(1) of the Federal Power Act (“FPA”) 1 and Section 39.5 of the
regulations of the Federal Energy Regulatory Commission (“FERC” or “Commission”), 2 the
North American Electric Reliability Corporation (“NERC”) 3 hereby requests Commission
approval of proposed Reliability Standard TPL-007-2 (Transmission System Planned
Performance for Geomagnetic Disturbance Events) (Exhibit A), the associated implementation
plan (Exhibit B), the Violation Risk Factors (“VRFs”) and Violation Severity Levels (“VSLs”)
(Exhibit C), and the retirement of currently-effective Reliability Standard TPL-007-1. The
NERC Board of Trustees (“Board”) adopted proposed Reliability Standard TPL-007-2 on
November 9, 2017.
Proposed Reliability Standard TPL-007-2 requires owners and operators of the Bulk
Power System (“BPS”) to conduct initial and on-going vulnerability assessments of the potential
impact of defined geomagnetic disturbance (“GMD”) events on BPS equipment and the BPS as a
whole. The modifications in the proposed standard address the Commission’s directives in Order
No. 830. 4 The modifications also improve upon the currently-effective version of the standard by

1

16 U.S.C. § 824o (2012).
18 C.F.R. § 39.5 (2017).
3
The Commission certified NERC as the electric reliability organization (“ERO”) in accordance with
Section 215 of the FPA on July 20, 2006. N. Am. Elec. Reliability Corp., 116 FERC ¶ 61,062 (2006).
4
Reliability Standard for Transmission System Planned Performance for Geomagnetic Disturbance Events,
Order No. 830, 156 FERC ¶ 61,215, P 1 (2016), reh’g denied, Order No. 830-A, 158 FERC ¶ 61,041 (2017).
2

1

using the latest developments in GMD research to provide enhanced criteria and requirements to
address reliability risks arising from GMDs, including the risks posed by severe, localized
events.
NERC requests that the Commission approve the proposed Reliability Standard and
related elements as just, reasonable, not unduly discriminatory or preferential, and in the public
interest. NERC requests that the Commission approve the proposed standard effective on the first
day of the first calendar quarter that is three months after the effective date of the Commission’s
order approving the proposed standard in accordance with the proposed implementation plan
(Exhibit B). As described in further detail herein, the proposed implementation plan is intended
to integrate the new requirements in TPL-007-2 with the GMD Vulnerability Assessment 5
process that is currently being implemented through the currently-effective version of the
standard.
Pursuant to Section 39.5(a) of the Commission’s regulations, 6 this Petition presents the
technical basis and purpose of proposed Reliability Standard TPL-007-2 (Exhibits A – D and
Exhibits G – J), a summary of the development history (Exhibit D), and a demonstration that the
proposed Reliability Standard meets the criteria identified by the Commission in Order No. 672
(Exhibit E). 7

5
Unless otherwise designated, all capitalized terms shall have the meaning set forth in the Glossary of Terms
Used in NERC Reliability Standards, available at http://www.nerc.com/files/Glossary_of_Terms.pdf.
6
18 C.F.R. § 39.5(a).
7
The Commission specified in Order No. 672 certain general factors it would consider when assessing
whether a particular Reliability Standard is just and reasonable. See Rules Concerning Certification of the Electric
Reliability Organization; and Procedures for the Establishment, Approval, and Enforcement of Electric Reliability
Standards, Order No. 672, FERC Stats. & Regs. ¶ 31,204, at PP 262, 321-37, order on reh’g, Order No. 672-A,
FERC Stats. & Regs. ¶ 31,212 (2006).

2

I.

EXECUTIVE SUMMARY
Proposed Reliability Standard TPL-007-2 adds enhancements to the currently-effective

GMD planning standard, Reliability Standard TPL-007-1, to better address risks to reliability
posed by GMDs and to implement the Commission’s directives in Order No. 830. In Order No.
830, the Commission approved Reliability Standard TPL-007-1 and directed NERC to modify
the standard as follows:
•

revise the benchmark GMD event used for GMD Vulnerability Assessments so
that the reference peak geoelectric field amplitude component is not based solely
on spatially-averaged data; 8

•

revise Requirement R6 to require entities to apply spatially averaged and nonspatially averaged peak geoelectric field values, or some equally efficient and
effective alternative, when conducting transformer thermal impact assessments; 9

•

require entities to collect data from geomagnetically induced current (“GIC”)
monitors and magnetometers as necessary to enable model validation and
situational awareness; 10 and

•

require entities to develop any necessary Corrective Action Plans within one year
from the completion of the GMD Vulnerability Assessment, include a two-year
deadline for the implementation of non-hardware mitigation, and include a fouryear deadline to complete hardware mitigation. 11

Proposed Reliability Standard TPL-007-2 reflects the latest in GMD understanding and
provides a technically sound and flexible approach to addressing the items of concern noted by
the Commission in Order No. 830. The proposed standard addresses the Commission’s directives
by:

8
9
10
11

See Order No. 830 at P 44.
Id. at P 65.
Id. at P 88.
Id. at P 101-102.

3

•

requiring entities to perform supplemental GMD Vulnerability Assessments based
on the supplemental GMD event, a second defined event that accounts for
localized peak effects of GMDs and which is based on individual station
measurements (i.e. not spatially-averaged data);

•

requiring entities to perform supplemental thermal impact assessments of
applicable power transformers based on GIC information for the supplemental
GMD event;

•

requiring entities to implement process(es) to obtain GIC monitor and
magnetometer data; and

•

implementing the deadlines specified by the Commission in Order No. 830 for the
development and completion of any necessary Corrective Action Plans to address
system performance issues resulting from the benchmark GMD event.

As discussed in detail below, these revisions would enhance reliability by expanding
GMD Vulnerability Assessments to include severe, localized impacts and by implementing new
deadlines and processes to maintain accountability in the development, completion, and revision
of entity Corrective Action Plans developed to address identified vulnerabilities. Further, the
proposed revisions would improve the availability of GMD monitoring data that may be used to
inform GMD Vulnerability Assessments. Through its ongoing GMD work, including the GMD
Research Work Plan 12 and a forthcoming Request for Data or Information pursuant to Section
1600 of the NERC Rules of Procedure (“Section 1600 GMD Data Request”), 13 NERC expects to
obtain useful inputs for continued evaluation of the technical basis that underpins the proposed
standard.

12

In accordance with Order No. 830, NERC filed a preliminary work plan to conduct research on topics
related to GMDs and their impacts on the reliability of the BPS (the “GMD Research Work Plan”). See
Geomagnetic Disturbance Research Work Plan of the North American Electric Reliability Corporation, Docket No.
RM15-11-002 (May 30, 2017). In accordance with the Commission’s October 19, 2017 Order on GMD Research
Work Plan, NERC will file a final or otherwise updated GMD Research Work Plan on or before April 2018.
13
NERC Rules of Procedure Section 1600. The NERC Rules of Procedure are available at
http://www.nerc.com/AboutNERC/Pages/Rules-of-Procedure.aspx.

4

For these reasons and as discussed more fully in this Petition, NERC respectfully requests
that the Commission approve the proposed standard as just, reasonable, not unduly
discriminatory or preferential, and in the public interest.
II.

NOTICES AND COMMUNICATIONS
Notices and communications with respect to this filing may be addressed to: 14

Shamai Elstein*
Senior Counsel
Lauren Perotti*
Counsel
Candice Castaneda*
Counsel
North American Electric Reliability
Corporation
1325 G Street, N.W., Suite 600
Washington, DC 20005
(202) 400-3000
(202) 644-8099 – facsimile
[email protected]
[email protected]
[email protected]
III.

Howard Gugel*
Senior Director of Standards
North American Electric Reliability
Corporation
3353 Peachtree Road, N.E.
Suite 600, North Tower
Atlanta, GA 30326
(404) 446-2560
[email protected]

BACKGROUND
A.

Regulatory Framework

In the Energy Policy Act of 2005, 15 Congress entrusted the Commission with the duties
of approving and enforcing rules to ensure the reliability of the BPS. Congress also entrusted the
Commission with certifying an Electric Reliability Organization (“ERO”) charged with
developing and enforcing mandatory Reliability Standards, subject to Commission approval.
Section 215(b)(1) of the FPA states that all users, owners, and operators of the BPS in the United

14

Persons to be included on the Commission’s service list are identified by an asterisk. NERC respectfully
requests a waiver of Rule 203 of the Commission’s regulations, 18 C.F.R. § 385.203, to allow the inclusion of more
than two persons on the service list in this proceeding.
15
16 U.S.C. § 824o.

5

States will be subject to Commission-approved Reliability Standards. 16 Section 215(d)(5) of the
FPA authorizes the Commission to order the ERO to submit a new or modified Reliability
Standard. 17 Section 39.5(a) of the Commission’s regulations requires the ERO to file with the
Commission for its approval each Reliability Standard that the ERO proposes should become
mandatory and enforceable in the United States and each modification to a Reliability Standard
that the ERO proposes should be made effective. 18
The Commission is vested with the regulatory responsibility to approve Reliability
Standards that protect the reliability of the BPS and to ensure that such Reliability Standards are
just, reasonable, not unduly discriminatory or preferential, and in the public interest. Pursuant to
Section 215(d)(2) of the FPA 19 and Section 39.5(c) of the Commission’s regulations, “the
Commission will give due weight to the technical expertise of the Electric Reliability
Organization” with respect to the content of a Reliability Standard. 20
B.

NERC Reliability Standards Development Procedure

The proposed Reliability Standard was developed in an open and fair manner and in
accordance with the Commission-approved Reliability Standard development process. 21 NERC
develops Reliability Standards in accordance with Section 300 (Reliability Standards
Development) of its Rules of Procedure and the NERC Standard Processes Manual. 22

16

Id. § 824o(b)(1).
Id. § 824o(d)(5).
18
18 C.F.R. § 39.5(a).
19
16 U.S.C. § 824o(d)(2).
20
18 C.F.R. § 39.5(c)(1).
21
Rules Concerning Certification of the Electric Reliability Organization; and Procedures for the
Establishment, Approval, and Enforcement of Electric Reliability Standards, Order No. 672 at P 334, FERC Stats. &
Regs. ¶ 31,204, order on reh’g, Order No. 672-A, FERC Stats. & Regs. ¶ 31,212 (2006).
22
The ROP is available at http://www.nerc.com/AboutNERC/Pages/Rules-of-Procedure.aspx. The NERC
Standard Processes Manual is available at
http://www.nerc.com/comm/SC/Documents/Appendix_3A_StandardsProcessesManual.pdf.
17

6

In its order certifying NERC as the Commission’s ERO, the Commission found that
NERC’s proposed rules provide for reasonable notice and opportunity for public comment, due
process, openness, and a balance of interests in developing Reliability Standards, 23 and thus
satisfy certain of the criteria for approving Reliability Standards. 24 The development process is
open to any person or entity with a legitimate interest in the reliability of the BPS. NERC
considers the comments of all stakeholders, and stakeholders must approve, and the NERC
Board of Trustees must adopt, a Reliability Standard before the Reliability Standard is submitted
to the Commission for approval.
C.

Procedural History of Proposed Reliability Standard TPL-007-2

This section summarizes the development history of proposed Reliability Standard TPL007-2.
1. History of Reliability Standard TPL-007-1 and Order No. 830
On January 21, 2015, NERC filed a petition requesting Commission approval of
Reliability Standard TPL-007-1, the second-stage GMD Reliability Standard contemplated by
the Commission in Order No. 779. 25 Reliability Standard TPL-007-1 requires applicable entities
to conduct initial and ongoing assessments of the potential impact of a 1-in-100 year benchmark
GMD event on BPS equipment and the BPS as a whole. The Commission approved Reliability
Standard TPL-007-1 in Order No. 830, issued on September 22, 2016, stating that the standard
“constitutes an important step in addressing the risks posed by GMD events to the Bulk-Power

23

N. Am. Elec. Reliability Corp., 116 FERC ¶ 61,062 at P 250 (2006).
Order No. 672 at PP 268, 270.
25
Petition of the North American Electric Reliability Corporation for Approval of Reliability Standard TPL007-1 Transmission System Planned Performance for Geomagnetic Disturbance Events, Docket No. RM15-11-000
(Jan. 21, 2015); Reliability Standards for Geomagnetic Disturbances, Order No. 779, 78 Fed. Reg. 30,747 (May 23,
2013), 143 FERC ¶ 61,147, reh’g denied, 144 FERC ¶ 61,113 (2013) (directing the development of Reliability
Standards to address GMDs in two stages).
24

7

System.” 26 The Commission also directed four revisions to the standard to address areas of
concern noted in the order and underlying proceeding.
First, noting its concerns with the reliance on spatially averaged data in the TPL-007-1
benchmark GMD event definition, the Commission directed NERC to “develop revisions to the
benchmark GMD event definition so that the reference peak geoelectric field amplitude
component is not based solely on spatially-averaged data.” 27 The Commission also directed
NERC to revise Requirement R6 “to require registered entities to apply spatially averaged and
non-spatially averaged peak geoelectric field values, or some equally and efficient alternative,
when conducting thermal impact assessments.” 28
Next, the Commission directed NERC to revise TPL-007-1 to require entities “to collect
GIC monitoring and magnetometer data as necessary to enable model validation and situational
awareness, including from any devices that must be added to meet this need.” 29 The Commission
stated that “additional collection and disclosure of GIC monitoring and magnetometer data is
necessary to improve our collective understanding of the threats posed by GMD events.” 30
Lastly, the Commission directed NERC to modify TPL-007-1 requirements for Corrective
Action Plans to include: (i) a one-year deadline for the development of any necessary Corrective
Action Plans; (ii) a two-year deadline for the implementation of non-hardware mitigation; and
(iii) a four-year deadline for the implementation of hardware mitigation. 31

26
27
28
29
30
31

Order No. 830 at P 1.
Order No. 830 at P 44.
Id. at P 65.
Id. at P 88.
Id.
Id. at PP 101-102.

8

In addition to these standard modification directives, the Commission also directed
NERC to undertake certain activities to improve understanding of GMDs and their potential
impacts on power systems. First, the Commission directed NERC to submit a work plan
describing how NERC would research specific GMD-related topics identified by the
Commission and other topics at NERC’s discretion. 32 Second, the Commission directed NERC
to collect GIC and magnetometer data pursuant to Section 1600 of the NERC Rules of
Procedure, including existing data for the period beginning May 2013 and new data going
forward, and to make that information available to support ongoing GMD research and
analysis. 33
This filing describes how proposed Reliability Standard TPL-007-2 addresses the
standard modification directives described above. NERC continues its efforts to address the
Commission’s work plan and data collection directives and provides a status update on those
efforts for the Commission’s information in Section VI, below. NERC anticipates that the results
of these efforts will inform future reviews of the proposed Reliability Standard.
2. Project 2013-03 Geomagnetic Disturbance Mitigation
Shortly after the issuance of Order No. 830, NERC initiated a new phase of Project 201303 to address the Commission’s directives to modify Reliability Standard TPL-007-1. As with
prior phases of the project, the standard drafting team for this phase consisted of individuals with
extensive planning, engineering, and scientific knowledge and experience. To provide technical
support for proposed Reliability Standard TPL-007-2, the standard drafting team developed new
and updated supporting materials, including the Supplemental GMD Event Description White

32
33

See generally id. at P 77.
Order No. 830 at PP 89, 93.

9

Paper (Exhibit I), Screening Criterion for Transformer Thermal Impact Assessment White Paper
(Exhibit H), and Transformer Thermal Impact Assessment White Paper (Exhibit G).
Proposed Reliability Standard TPL-007-2 was posted for initial ballot from June 28, 2017
to August 11, 2017 and for final ballot from October 20, 2017 to October 30, 2017. The NERC
Board of Trustees adopted the proposed standard on November 9, 2017. The complete
development history of proposed Reliability Standard TPL-007-2 is attached as Exhibit D.
IV.

JUSTIFICATION FOR APPROVAL
As discussed below and in Exhibit E, proposed Reliability Standard TPL-007-2 satisfies

the Commission’s criteria in Order No. 672 and is just, reasonable, not unduly discriminatory or
preferential, and in the public interest. The proposed Reliability Standard contains significant
benefits for the BPS and addresses the Commission’s directives from Order No. 830.
The purpose of proposed Reliability Standard TPL-007-2, which remains unchanged
from currently-effective Reliability Standard TPL-007-1, is to “[e]stablish requirements for
Transmission system planned performance during geomagnetic disturbance (GMD) events.” The
applicability of the proposed standard also remains unchanged from TPL-007-1: the proposed
standard would continue to apply to: (1) Planning Coordinators and Transmission Planners
whose planning areas have a Facility that includes a power transformer with a high side, wyegrounded winding with terminal voltage greater than 200 kV 34; and (2) Transmission Owners
and Generator Owners that own a Facility that includes such equipment.
Currently-effective Reliability Standard TPL-007-1 requires entities to conduct initial and
on-going assessments of the potential impact of the defined benchmark GMD event on BPS
equipment and the BPS as a whole. Proposed Reliability Standard TPL-007-2 builds upon these

34

A power transformer with a “high side wye-grounded winding” refers to a power transformer with
windings on the high voltage side that are connected in a wye configuration and have a grounded neutral connection.

10

Requirements and adds new Requirements for entities to assess their vulnerabilities to a second
defined event, the supplemental GMD event. This supplemental GMD event is designed to
account for the localized peak effects of severe GMD events on systems and equipment. The
proposed standard also contains new Requirements for the collection of GIC and magnetometer
data. Lastly, the proposed standard revises Requirement R7 to include deadlines for the
development and completion of any necessary Corrective Action Plans. Each of these revisions
and how they address the Commission’s directives from Order No. 830 is discussed below.
A.

The Supplemental GMD Event

Proposed Reliability Standard TPL-007-2 contains new Requirements for entities to
assess their vulnerabilities to a second defined GMD event, the supplemental GMD event. As
described in the Supplemental GMD Event Description White Paper (Exhibit I), geomagnetic
fields during severe GMD events can be spatially non‐uniform with higher and lower strengths
across a geographic region. The supplemental GMD event, which was derived using individual
station measurements rather than spatially averaged measurements, includes localized
enhancement of field strength above the average value. As such, the proposed standard addresses
the Commission’s directive in Order No. 830 to revise the GMD standard to account for the
effects of localized peaks that could potentially affect reliable operations. 35
The benchmark GMD event and the supplemental GMD event are similar in structure but
the supplemental GMD event contains several differences to account for localized impacts. Like

35

See Order No. 830 at P 44 (“The Commission…directs NERC to develop revisions to the benchmark GMD
event definition so that the reference peak geoelectric field amplitude component is not based solely on spatiallyaveraged data.”). See also Order No. 830 at P 47 (“Without pre-judging how NERC proposes to address the
Commission’s directive, NERC’s response to this directive should satisfy the NOPR’s concern that reliance on
spatially-averaged data alone does not address localized peaks that could potentially affect the reliable operation of
the Bulk-Power System.”)

11

the benchmark GMD event, the supplemental GMD event defines the geomagnetic and
geoelectric field values used to compute GIC flows for use in a GMD Vulnerability Assessment.
The benchmark GMD event is composed of the following components:
•

a reference peak geoelectric field amplitude of 8 V/km derived from statistical
analysis of historical magnetometer data;

•

scaling factors to account for local geomagnetic latitude;

•

scaling factors to account for local earth conductivity; and

•

a reference geomagnetic field time series or waveform to facilitate time-domain
analysis of GMD impact on equipment.

The supplemental GMD event has the same components, except that the reference peak
geoelectric field amplitude is 12 V/km over a localized area (compared to 8 V/km) and the
geomagnetic field time series or waveform includes a local enhancement. 36 These distinguishing
characteristics of the supplemental GMD event are intended to represent conditions associated
with localized enhancement of the geomagnetic field during a severe GMD event for use in
assessing GMD impacts.
In developing the supplemental GMD event, the standard drafting team used data and
information so that the peak geoelectric field does not rely on spatial averaging of geomagnetic
field data. Like the value in the approved benchmark GMD event, the supplemental GMD event
peak geoelectric field is a 1-in-100 year extreme value determined using statistical analysis of
historical geomagnetic field data. The fundamental difference in the supplemental GMD event
amplitude is that it is based on geomagnetic field observations taken at individual observation
stations (i.e., localized measurements), instead of the spatially averaged geoelectric fields used in

36
See proposed Reliability Standard TPL-007-2 Attachment 1. See also Supplemental GMD Event
Description White Paper (Exhibit I). The addition of a local enhancement to the supplemental GMD event waveform
also causes some small changes in earth conductivity scaling factors, as explained in the white paper. These earth
conductivity scaling factors for the supplemental GMD event are included in proposed TPL-007-2 Attachment 1.

12

the benchmark GMD event. The result of the extreme value analysis shows that the supplemental
GMD event peak of 12 V/km is above the upper limit of the 95 percent confidence interval for a
100‐year return interval, while the same confidence interval with spatially-averaged data (i.e., the
benchmark GMD event) is 8 V/km. Thus, GMD Vulnerability Assessments based on the 12
V/km peak geoelectric field of the proposed supplemental GMD event are considering extreme
localized conditions associated with a 1-in-100 year severe GMD event.
Similar to the benchmark GMD event, the supplemental GMD event includes a
waveform for assessing transformer thermal impacts from a severe GMD event. Both the
benchmark and supplemental GMD event waveforms are based on 10-second sampling interval
magnetic field data from the Ottawa observatory recorded during the March 13-14, 1989 GMD
event. The supplemental GMD event waveform is more severe than the benchmark GMD event
waveform because it includes a five-minute duration enhanced peak up to 12 V/km for the
reference earth model and 60 degree geomagnetic latitude. This synthetic enhancement
represents the observed localized, rapid magnetic field variation periods associated with
ionospheric sources during some severe GMD events. Such GMD conditions could result in
increased transformer heating for short durations during a severe GMD event due to increased
GIC flows.
The supplemental GMD event provides a technically justified method of assessing
vulnerabilities to the localized peak effects of severe GMD events, thereby addressing the
Commission’s Order No. 830 directive. Together, the approved benchmark GMD event and the
proposed supplemental GMD event provide a high threshold for assessing GMD impacts.

13

B.

New and Revised Requirements to Perform GMD Vulnerability Assessments
Based on the Supplemental GMD Event

Proposed TPL-007-2 adds new Requirements R8, R9, and R10 to require responsible
entities to assess the potential implications of the supplemental GMD event described above on
their equipment and systems in accordance with the Commission’s directives in Order No. 830. 37
The proposed Requirements are structured and worded similarly to approved Requirements R4
through R6, which require entities to assess the impact of the benchmark GMD event. With the
addition of these new Requirements, NERC proposes minor revisions to Requirements R4
through R6 to clarify that those existing Requirements pertain to assessments based on the
benchmark GMD event. NERC also proposes revisions to Requirements R1 through R3 to
include appropriate references to the supplemental GMD event. These minor revisions are shown
in Exhibit A (redline).
1. Proposed Requirement R8
Proposed Requirement R8 would require responsible entities to complete a supplemental
GMD Vulnerability Assessment of the Near-Term Transmission Planning Horizon at least once
every five years. The proposed Requirement reads as follows:
R8.

Each responsible entity, as determined in Requirement R1, shall complete a supplemental
GMD Vulnerability Assessment of the Near‐Term Transmission Planning Horizon at least
once every 60 calendar months. This supplemental GMD Vulnerability Assessment shall
use a study or studies based on models identified in Requirement R2, document
assumptions, and document summarized results of the steady state analysis.
8.1.
The study or studies shall include the following conditions:
8.1.1. System On‐Peak Load for at least one year within the Near‐Term
Transmission Planning Horizon; and
8.1.2. System Off‐Peak Load for at least one year within the Near‐Term
Transmission Planning Horizon.
8.2.
The study or studies shall be conducted based on the supplemental GMD
event described in Attachment 1 to determine whether the System meets the

37

See Order No. 830 at P 44 (benchmark GMD event definition) and P 65 (transformer thermal impact
assessments).

14

8.3.

8.4.

performance requirements for the steady state planning supplemental GMD
event contained in Table 1.
If the analysis concludes there is Cascading caused by the supplemental
GMD event described in Attachment 1, an evaluation of possible actions
designed to reduce the likelihood or mitigate the consequences and adverse
impacts of the event(s) shall be conducted.
The supplemental GMD Vulnerability Assessment shall be provided: (i) to
the responsible entity’s Reliability Coordinator, adjacent Planning
Coordinators, adjacent Transmission Planners within 90 calendar days of
completion, and (ii) to any functional entity that submits a written request
and has a reliability‐related need within 90 calendar days of receipt of such
request or within 90 calendar days of completion of the supplemental GMD
Vulnerability Assessment, whichever is later.
8.4.1. If a recipient of the supplemental GMD Vulnerability Assessment
provides documented comments on the results, the responsible
entity shall provide a documented response to that recipient within
90 calendar days of receipt of those comments.

Proposed Requirement R8 mirrors Requirement R4, which requires entities to complete a
GMD Vulnerability Assessment based on the benchmark GMD event, but with one key
difference. Proposed Requirement R8 contains an additional Part, Part 8.3, which provides that if
analysis concludes there would be Cascading caused by the supplemental GMD event, the
responsible entity must then evaluate possible actions to reduce the likelihood or mitigate
consequences and adverse impacts of the event. As discussed more fully in Section IV.D below,
the standard drafting team determined that requiring such an evaluation of possible actions, as
opposed to a formal Corrective Action Plan, would provide a more prudent approach in light of
the limitations of currently-available tools for modeling localized GMD effects.
New language is reflected in proposed Requirement R8 Part 8.4 to clarify the timeframe
for providing completed supplemental GMD Vulnerability Assessments to the Reliability
Coordinator, neighboring Planning Coordinators and Transmission Planners, and to the other
functional entities with a reliability-related need that submit a request. To provide for

15

consistency across similar Requirements, conforming revisions are proposed in TPL-007-2
Requirement R4 Part 4.3 pertaining to benchmark GMD Vulnerability Assessments.
2. Proposed Requirements R9 and R10
Proposed Requirements R9 and R10 pertain to supplemental transformer thermal impact
assessments. As these Requirements are based on the supplemental GMD event described above,
they address the Commission’s directive to revise the standard to require entities to apply non
spatially-averaged peak geoelectric field values when conducting thermal impact assessments. 38
Proposed Requirement R9 would require responsible entities to provide GIC flow
information based on the supplemental GMD event to owners of applicable BES power
transformers in the planning area. The proposed Requirement mirrors existing Requirement R5
pertaining to GIC flow information for the benchmark GMD event. Proposed Requirement R9
reads as follows:
R9.

Each responsible entity, as determined in Requirement R1, shall provide GIC flow
information to be used for the supplemental thermal impact assessment of transformers
specified in Requirement R10 to each Transmission Owner and Generator Owner that owns
an applicable Bulk Electric System (BES) power transformer in the planning area. The GIC
flow information shall include:
9.1.
The maximum effective GIC value for the worst case geoelectric field
orientation for the supplemental GMD event described in Attachment 1.
This value shall be provided to the Transmission Owner or Generator
Owner that owns each applicable BES power transformer in the planning
area.
9.2.
The effective GIC time series, GIC(t), calculated using the supplemental
GMD event described in Attachment 1 in response to a written request from
the Transmission Owner or Generator Owner that owns an applicable BES
power transformer in the planning area. GIC(t) shall be provided within 90
calendar days of receipt of the written request and after determination of the
maximum effective GIC value in Part 9.1.

38

Order No. 830 at P 65.

16

Proposed Requirement R10 would require each Transmission Owner and Generator
Owner to conduct a supplemental thermal impact assessment for solely and jointly owned
applicable BES power transformers where the maximum effective GIC value resulting from
Requirement R9 is above a specific threshold. The proposed Requirement reads as follows:
R10.

Each Transmission Owner and Generator Owner shall conduct a supplemental thermal
impact assessment for its solely and jointly owned applicable BES power transformers
where the maximum effective GIC value provided in Requirement R9, Part 9.1, is 85 A
per phase or greater. The supplemental thermal impact assessment shall:
10.1. Be based on the effective GIC flow information provided in Requirement
R9;
10.2. Document assumptions used in the analysis;
10.3. Describe suggested actions and supporting analysis to mitigate the impact
of GICs, if any; and
10.4. Be performed and provided to the responsible entities, as determined in
Requirement R1, within 24 calendar months of receiving GIC flow
information specified in Requirement R9, Part 9.1.
Proposed Requirement R10 mirrors existing Requirement R6 pertaining to transformer

thermal impact assessments based on the benchmark GMD event. However, for the supplemental
thermal impact assessment, the threshold is a maximum effective GIC value of 85 A per phase or
greater (compared to the benchmark threshold of 75 A per phase or greater). As described in
greater detail in the Screening Criterion for Transformer Thermal Impact Assessment White
Paper (Exhibit H), the threshold value is determined using the same methods employed for the
benchmark thermal impact assessments and provides that assessments be performed on all
applicable power transformers that could potentially exceed emergency loading temperature
guidelines. 39

39

See generally Exhibit H and Institute of Electrical and Electronic Engineers (IEEE) Standard C57.91‐2011
– Guide for Loading Mineral‐Oil‐Immersed Transformers and Step‐Voltage Regulators.

17

C.

New Requirements for the Collection of GMD Data (R11 and R12)

In Order No. 830, the Commission directed NERC to “develop revisions to Reliability
Standard TPL-007-1 to require responsible entities to collect GIC monitoring and magnetometer
data as necessary to enable model validation and situational awareness, including from any
devices that must be added to meet this need.” 40 Consistent with this directive, proposed TPL007-2 contains two new Requirements, Requirements R11 and R12, that would require
responsible entities to implement a process to obtain GIC monitor and geomagnetic field data for
their planning area or system model area. The Requirements apply to Planning Coordinators and
Transmission Planners, as determined in Requirement R1, because these entities are responsible
for maintaining GIC System models (Requirement R2). Entities may use the data for validating
GIC system models as well as for awareness of local geomagnetic conditions and measured GIC
levels.
Proposed Requirement R11 would require responsible entities to implement a process to
obtain GIC monitor data as follows:
R11.

Each responsible entity, as determined in Requirement R1, shall implement a process to
obtain GIC monitor data from at least one GIC monitor located in the Planning
Coordinator’s planning area or other part of the system included in the Planning
Coordinator’s GIC System model.
Consistent with the Commission’s guidance, 41 collection criteria are included in the

Supplemental Material section of the proposed standard to promote consistency and provide
entities with flexibility to tailor procedures to their planning area. The guidance for GIC data
collection addresses monitor locations, monitor specifications, sampling interval, collection
periods, data format, and data retention.

40

Order No. 830 at P 88.
See id. at P 91 (regarding criteria for NERC to consider in developing a requirement for the collection of
GIC monitoring data).
41

18

Proposed Requirement R12 would require responsible entities to implement a process to
obtain geomagnetic field data as follows:
R12.

Each responsible entity, as determined in Requirement R1, shall implement a process to
obtain geomagnetic field data for its Planning Coordinator’s planning area.
By requiring responsible entities to obtain geomagnetic field data for their planning areas,

the proposed Requirement would ensure that data is obtained from diverse geographic areas of
the North American BPS. Entities are advised to obtain data from the nearest accessible
magnetometer. Sources of magnetometer data include government observatories, installed
equipment owned or operated by the entity, and third party sources, including research
institutions and universities. Entities that choose to install their own magnetometers are referred
to the INTERMAGNET Technical Reference Manual for equipment specifications and data
format protocols.
Proposed Reliability Standard TPL-007-2 supports future data collection across the North
American BPS by requiring planning entities to implement processes for obtaining GMD data
for each planning area. NERC, pursuant to the pending Section 1600 GMD Data Request, 42 will
collect GMD data from entities and make that data available to support ongoing research and
analysis of GMD risk. The proposed standard, together with the pending Section 1600 GMD
Data Request, would thus satisfy the Commission’s data collection directives in Order No. 830
and provide data to help address the potential reliability risks posed by GMDs.
D.

Revised Deadlines for Corrective Action Plans in Requirement R7

NERC proposes to revise Requirement R7 to include the Commission-directed deadlines
for the development and completion of any required Corrective Action Plans to address system

42

See Section VI infra.

19

performance issues for the benchmark GMD event. In Order No. 830, the Commission directed
NERC to modify the TPL-007 standard to include the following deadlines:
•

one year from the completion of the GMD Vulnerability Assessment to complete
the development of a Corrective Action Plan;

•

two years after the development of the Corrective Action Plan to complete the
implementation of non-hardware mitigation; and

•

four years after the development of the Corrective Action Plan to complete
hardware mitigation.” 43

Proposed TPL-007-2 Requirement R7 revises the existing standard to incorporate these
directives as follows:
R7.

Each responsible entity, as determined in Requirement R1, that concludes, through the
benchmark GMD Vulnerability Assessment conducted in Requirement R4, that their
System does not meet the performance requirements of for the steady state planning
benchmark GMD event contained in Table 1, shall develop a Corrective Action Plan
(CAP) addressing how the performance requirements will be met. The Corrective Action
Plan CAP shall:
7.1.
List System deficiencies and the associated actions needed to achieve
required System performance. Examples of such actions include:
• Installation, modification, retirement, or removal of Transmission
and generation Facilities and any associated equipment.
• Installation, modification, or removal of Protection Systems or
Special Protection Systems Remedial Action Schemes.
• Use of Operating Procedures, specifying how long they will be
needed as part of the Corrective Action Plan CAP.
• Use of Demand‐Side Management, new technologies, or other
initiatives.
7.2.
Be reviewed in subsequent developed within one year of completion of the
benchmark GMD Vulnerability Assessments until it is determined that the
System meets the performance requirements contained in Table 1.
7.3.
Include a timetable, subject to revision by the responsible entity in Part 7.4,
for implementing the selected actions from Part 7.1. The timetable shall:
7.3.1. Specify implementation of non‐hardware mitigation, if any, within
two years of development of the CAP; and
7.3.2. Specify implementation of hardware mitigation, if any, within four
years of development of the CAP.

43

Order No. 830 at PP 101-102.

20

7.4.

Be revised if situations beyond the control of the responsible entity
determined in Requirement R1 prevent implementation of the CAP within
the timetable for implementation provided in Part 7.3. The revised CAP
shall document the following, and be updated at least once every 12
calendar months until implemented:
7.4.1. Circumstances causing the delay for fully or partially implementing
the selected actions in Part 7.1;
7.4.2. Description of the original CAP, and any previous changes to the
CAP, with the associated timetable(s) for implementing the selected
actions in Part 7.1; and
7.4.3. Revisions to the selected actions in Part 7.1, if any, including
utilization of Operating Procedures if applicable, and the updated
timetable for implementing the selected actions.
7.37.5. Be provided within 90 calendar days of completion: (i) to the responsible
entity’s Reliability Coordinator, adjacent Planning Coordinator(s), adjacent
Transmission Planner(s), and functional entities referenced in the
Corrective Action Plan CAP within 90 calendar days of development or
revision, and (ii) to any functional entity that submits a written request and
has a reliability‐related need within 90 calendar days of receipt of such
request or within 90 calendar days of development or revision, whichever
is later.
7.3.17.5.1. If a recipient of the Corrective Action Plan CAP provides
documented comments on the results, the responsible entity shall
provide a documented response to that recipient within 90 calendar
days of receipt of those comments.
Revised Requirement R7 Part 7.2 would require responsible entities to develop a
Corrective Action Plan within one year of the benchmark GMD Vulnerability Assessment, if the
entity concludes that its System does not meet the performance requirements for the steady state
planning benchmark GMD event. Under new Requirement R7 Part 7.3, the Corrective Action
Plan shall include a timeline that specifies the completion of non-hardware and hardware
mitigation within two and four years of development of the Corrective Action Plan, respectively.
In accordance with the Commission’s directive, the proposed standard requires entities to
take prompt action to address any vulnerabilities they identify in their systems. The proposed
standard recognizes, however, that there may be circumstances outside of an entity’s control that
could prevent the completion of a mitigation activity by the specified timetable. Such events
21

could include, for example: delays due to the regulatory or legal processes, such as permitting;
delays from stakeholder processes required by tariffs; delays resulting from equipment lead
times; or delays resulting from the inability to acquire necessary right-of-way. In such
circumstances, an entity may maintain compliance with the standard by revising its Corrective
Action Plan in accordance with Requirement R7 Part 7.4.
Under Part 7.4, the entity shall revise its Corrective Action Plan if events beyond its
control prevent implementation of the Corrective Action Plan within the original timetable. In
the revised Corrective Action Plan, the responsible entity must provide justification for its
revised timetable by documenting: (1) the circumstances causing the delay; (2) description of the
original Corrective Action Plan and any changes; and (3) revisions to selected actions, including
the use of any operating procedures if applicable, along with an updated timetable for
completion. The revised Corrective Action Plan shall be updated at least annually. The
responsible entity must then provide its revised Corrective Action Plan to recipients of the
original Corrective Action Plan (i.e., Reliability Coordinator, adjacent Planning Coordinator(s),
adjacent Transmission Planner(s), functional entities referenced in the Corrective Action Plan,
and any functional entity that submits a written request and has a reliability related need for the
information.) Thus, Requirement R7 would implement the Commission directed deadlines for
Corrective Action Plans and mitigation, along with a process to maintain accountability and
communication with affected entities when circumstances beyond a responsible entity’s control
affect the entity’s ability to complete implementation within the original deadlines.
This approach is consistent with other Commission-approved Reliability Standards. For
example, Reliability Standard FAC-003-4 Requirement R7 provides that an entity may modify
its annual vegetation work plan in light of circumstances beyond the entity’s control, such as a

22

natural disaster or other circumstance. (FAC-003-4 Requirement R7 also specifies other
acceptable reasons for modifying an annual work plan, including permitting delays.) Reliability
Standard PRC-004-5(i) Requirement R5 states that a responsible entity that owns a Protection
System component that caused a Misoperation shall either develop a Corrective Action Plan or
explain in a declaration why corrective actions are beyond the entity’s control or would not
improve reliability. In light of the potential planning, siting, budgeting approval, and regulatory
uncertainties associated with transmission projects that are outside of an entity’s control, it is
appropriate to include such a flexible approach to GMD Corrective Action Plan deadlines in
proposed TPL-007-2.
As noted above, proposed Requirement R7 continues to apply only where an entity has
identified system performance issues through the benchmark GMD Vulnerability Assessment.
Mitigation considerations for vulnerabilities identified through the supplemental GMD
Vulnerability Assessment are addressed in proposed Requirement R8 Part 8.3. Under this Part, if
a responsible entity concludes that there would be Cascading caused by the supplemental GMD
event, the entity shall conduct an analysis of possible actions to reduce the likelihood or mitigate
the impacts of the event.
The standard drafting team determined that requiring formal Corrective Action Plans
based on assessments of the supplemental GMD event would not be appropriate at this time. As
discussed in the Supplemental GMD Event Description white paper, the supplemental GMD
event is based on a small number of observed localized enhanced geoelectric field events that
provide only general insight into the geographic size of localized events during severe solar
storms. Additionally, currently available modeling tools do not provide entities with capabilities
to model localized enhancements within a severe GMD event realistically. As a result, entities

23

may need to employ conservative approaches when performing the supplemental GMD
Vulnerability Assessment, such as applying the localized peak geoelectric field over an entire
planning area. For these reasons, requiring mandatory mitigation may not provide effective
reliability benefit or use resources optimally. The approach used in the proposed standard for the
supplemental GMD event provides entities with flexibility to consider and select mitigation
actions based on their circumstances and is similar to the approach used in Reliability Standard
TPL-001-4 Requirement R3 Part 3.5 for extreme events.
E.

Enforceability of Proposed Reliability Standard TPL-007-2

Proposed Reliability Standard TPL-007-2 includes Measures in support of each
Requirement to ensure that Requirements are enforced in a clear, consistent, non-preferential
manner, without prejudice to any party. The proposed standard also includes VRFs and VSLs for
each Requirement, which are used to help determine appropriate sanctions if an applicable entity
violates a Requirement. VRFs assess the impact to reliability of violating a specific Requirement,
while VSLs provide guidance on the way that NERC will enforce Requirements.
The proposed standard includes the same VRFs and VSLs for Requirements R1 through
R7, which were approved by the Commission in Order No. 830. Proposed Requirement R8
would apply a High VRF; proposed Requirements R9 and R10 would apply a Medium VRF; and
Requirements R11 and R12 would apply a Lower VRF. Proposed Requirements R8 through R10
would also apply a graduated scale of Lower to Severe VSLs (depending on the extent of the
violation), while proposed Requirements R11 and R12 would only apply a Severe VSL in
recognition of the binary nature of compliance with the data obligations.
These VRFs and VSLs comport with NERC and Commission guidelines. The High VRF
proposed for Requirement R8 is consistent with both Reliability Standard TPL-001-4 (requiring

24

an annual planning assessment) and Reliability Standard TPL-007-1 Requirement R4. Further
failure to complete a supplemental GMD Vulnerability Assessment could, under certain
conditions, place the BES at unacceptable risk. The Medium VRF proposed for Requirements R9
and R10 is similarly consistent with TPL-007-1 Requirements R5 and R6, which require
responsible entities to provide GIC data to Transmission Owners and Generator Owners for
assessments. In addition, failure to provide GIC flow information or conduct a supplemental
transformer impact assessment is unlikely to lead to BES instability, separation, or cascading.
The Lower VRF proposed for Requirements R11 and R12 is also consistent with other standards,
such as the data collection related obligations in Reliability Standards MOD-032-1 Requirement
R1 and IRO-010-2 Requirement R1. Finally, a Lower VRF for both Requirement R11 and R12
would also be appropriate, as an entity’s failure to follow its process to obtain GIC monitor or
geomagnetic field data would not be expected to adversely affect the electrical state or capability
of the BES, or the ability to effectively monitor, control, or restore the BES. Please see Exhibit C
for more detailed analysis of the proposed VRFs and VSLs.
V.

EFFECTIVE DATE
NERC respectfully requests that the Commission approve NERC’s proposed

implementation plan, attached to this Petition as Exhibit B. Under this plan, proposed Reliability
Standard TPL-007-2 would become effective on the first day of the first calendar quarter that is
three months after Commission approval. NERC requests retirement of Reliability Standard
TPL-007-1 immediately prior to the effective date of TPL-007-2.
The proposed TPL-007-2 implementation plan recognizes that several Requirements in
TPL-007-1 are or will soon become effective, and that many entities may now be taking steps to
complete the studies or assessments required by other Requirements in TPL-007-1 that will
become enforceable in the future. The proposed implementation plan thus contains two phased
25

compliance timelines depending on whether proposed Reliability Standard TPL-007-2 standard
becomes effective before January 1, 2021 or on/after January 1, 2021: 44
•

If the proposed standard becomes effective before January 1, 2021, a new phased
compliance schedule would support entities completing Requirements for the
supplemental GMD Vulnerability Assessment concurrently with Requirements for
the benchmark GMD Vulnerability Assessment. 45

•

If the standard becomes effective on or after January 1, 2021, entities would
continue work on benchmark GMD Vulnerability Assessments and complete
supplemental GMD Vulnerability Assessments during the next assessment cycle.

Under either timeline, entities would be required to comply with Requirements for the
collection of GMD monitoring data within 24 months of the effective date of the standard. The
phased-in compliance dates provided in the proposed implementation plan appropriately balance
the reliability need to implement the new and revised Requirements while providing entities with
sufficient time to meet their obligations.
VI.

UPDATE ON NERC’S ONGOING GMD RESEARCH WORK PLAN AND
SECTION 1600 GMD DATA REQUEST ACTIVITIES
As noted earlier in this Petition, NERC is continuing work to address the Commission’s

GMD research and data collection directives from Order No. 830. On May 30, 2017, NERC
submitted a preliminary version of its GMD Research Work Plan in Docket No. RM15-11-002
describing how NERC would oversee research into the specific GMD topics of interest identified
by the Commission. 46 NERC is working with the Electric Power Research Institute (“EPRI”) to

44

Under the TPL-007-1 implementation plan, this is the date by which entities would be required to comply
with TPL-007-1 Requirement R6 pertaining to transformer thermal impact assessments based on the benchmark
GMD event.
45
Depending on the date of Commission approval of TPL-007-2, the phased compliance dates for completing
steps for both benchmark and supplemental GMD Vulnerability Assessments may be slightly delayed from the dates
set forth for benchmark GMD Vulnerability Assessments under the TPL-007-1 implementation plan.
46
Geomagnetic Disturbance Research Work Plan of the North American Electric Reliability Corporation,
Docket No. RM15-11-002 (May 30, 2017).

26

prepare an updated GMD Research Work Plan to submit to the Commission by April 2018 in
accordance with the Commission’s October 19, 2017 Order. 47 NERC and EPRI initiated the
GMD Research Work plan in November 2017 through an EPRI project that is supported by
utility and Independent System Operator participants and involves NERC GMD Task Force,
U.S. national laboratories, equipment manufacturers, and other North American research
partners.
To address the Commission’s Order No. 830 data collection directive, NERC recently
prepared an initial draft Request for Data or Information under Section 1600 of the NERC Rules
of Procedure. The draft was prepared in conjunction with the NERC GMD Task Force under the
oversight of the NERC Planning Committee. In accordance with the NERC Rules of Procedure,
NERC provided the initial draft to Commission’s Office of Electric Reliability on January 8,
2018. NERC expects to post the draft request for a 45-day public comment period on or around
January 30, 2018. Following the close of this comment period, NERC will review the comments
received and revise the draft Section 1600 GMD Data Request as appropriate. NERC will also
continue work to develop the necessary information technology infrastructure and data reporting
specifications to facilitate the collection of GMD data. NERC intends to seek authorization from
the NERC Board of Trustees to issue the Section 1600 GMD Data Request in August 2018.

47

Order on GMD Research Work Plan, 161 FERC ¶ 61,048 (Oct. 19, 2017) (accepting NERC’s preliminary
GMD Research Work Plan).

27

VII.

CONCLUSION
For the reasons set forth above, NERC respectfully requests that the Commission approve

proposed Reliability Standard TPL-007-2 and related elements, the proposed implementation
plan, and the retirement of currently-effective Reliability Standard TPL-007-1 as discussed
herein.

Respectfully submitted,
/s/ Lauren A. Perotti

Shamai Elstein
Senior Counsel
Lauren A. Perotti
Counsel
Candice Castaneda
Counsel
North American Electric Reliability
Corporation
1325 G Street, N.W., Suite 600
Washington, D.C. 20005
(202) 400-3000
(202) 644-8099 – facsimile
[email protected]
[email protected]
[email protected]

Counsel for the North American Electric
Reliability Corporation
Date: January 22, 2018