HVAC Commissioning Checklist 1, 2
ENERGY STAR Certified Homes, Version 3 / 3.1 (Rev. 08)
HVAC Commissioning Contractor Responsibilities:
The commissioning contractor must be credentialed by an HVAC oversight organization to complete this checklist. One
checklist must be completed and signed by the commissioning contractor for each HVAC system that is commissioned.
The completed checklist for each commissioned system, along with the corresponding HVAC Design Report, shall be retained
by the contractor for quality assurance purposes. Furthermore, the contractor shall provide the completed checklist to the
builder, the Home Energy Rater responsible for certifying the home, and the HVAC oversight organization upon request.
Visit www.energystar.gov/newhomeshvac for information about the credential requirement and this checklist.
1. Commissioning Overview
1.1 Contractor name____________________________ Contractor company________________________________
ACCA
1.2 Organization that your company is credentialed with:
Advanced Energy
Date___________
NYSERDA
1.3 Builder client name: __________________________________________________________________________
1.4 Home address: __________________________________
City: __________________________
State: ______ Zip code: ________
Contractor-verified
1.5 HVAC Design Report corresponding to this system has been collected from designer or builder.
1.6 Area that system serves, per Item 1.4 of HVAC Design Report: Whole-house Upper-level Lower-level Other ______________
1.7 House plan, per Item 1.6 of HVAC Design Report:_____________________________ Site-specific design Group design #: ________
2. Refrigerant Charge - Run system for 15 minutes before testing. If outdoor ambient temperature at the condenser is < 55°F or,
if known, below the manufacturer-recommended minimum operating temperature for the cooling cycle, then the system shall include
a TXV, the outdoor temperature shall be recorded in Item 2.1, and the contractor shall check “N/A” in this Section. 3
Contractor
Verified
N/A
2.1 Outdoor ambient temperature at condenser:
________ °F DB
-
-
2.2 Return-side air temperature inside duct near evaporator, during cooling mode:
________ °F WB
-
2.3 Liquid line pressure:
________ psig
-
2.4 Liquid line temperature:
________ °F DB
-
2.5 Suction line pressure:
________ psig
-
2.6 Suction line temperature:
________°F DB
-
For System with Thermal Expansion Valve (TXV):
2.7 Condenser saturation temperature:
_____
°F DB (Using Item 2.3)
-
2.8 Subcooling value:
_____
°F DB (Item 2.7 - Item 2.4)
-
2.9 OEM subcooling goal:
_____
°F DB
-
2.10 Subcooling deviation:
_____
°F DB (Item 2.8 – Item 2.9)
-
For System with Fixed Orifice:
2.11 Evaporator saturation temperature:
____
°F DB (Using Item 2.5)
-
2.12 Superheat value:
____
°F DB (Item 2.6 – Item 2.11)
-
2.13 OEM superheat goal:
____
°F DB (Using superheat tables and Items 2.1 & 2.2)
-
2.14 Superheat deviation:
____
°F DB (Item 2.12 – Item 2.13)
-
2.15 Item 2.10 is ± 3°F or Item 2.14 is ± 5°F
2.16 An OEM test procedure (e.g., as defined for a ground-source heat pump) has been used in place of the sub-cooling or
super-heat process and documentation has been attached that defines this procedure
-
-
Test hole location for return external static pressure: Plenum Cabinet Transition Other: ____________
-
-
Test hole location for supply external static pressure: Plenum Cabinet Transition Other: ____________
-
-
3.3 Measured return external static pressure (Enter value only, without negative sign): ______ IWC
-
-
3.4 Measured supply external static pressure (Enter value only, without positive sign): ______ IWC
-
-
3. Indoor HVAC Fan Airflow
3.1 The mode with the higher design HVAC fan airflow used, per Item 5.2 of HVAC Design Report: Heating
Cooling
3.2 Static pressure test holes have been created, and test hole locations are well-marked and accessible.
3.5 Measured total external static pressure = Value-only from Item 3.3 + Value-only from Item 3.4 =
-
-
3.6 Measured (Item 3.5) - Design (Item 5.4 on HVAC Design Report) total external static pressure = __________ IWC
___________ IWC
-
-
3.7 Measured HVAC fan airflow, using Item 3.5 and fan speed setting:
-
-
-
_______ CFM
3.8 Measured HVAC fan airflow (Item 3.7) is ± 15% of design HVAC fan airflow (Item 5.2 on HVAC Design Report)
4. Air Balancing of Supply Registers & Return Grilles (Recommended, but not Required)
4
4.1 Balancing report attached with room-by-room design airflows from Item 5.5 on HVAC Design Report, and contractormeasured airflow using ANSI / ACCA 5 QI-2015 protocol
4.2 Room-by-room airflows verified by contractor to be within the greater of ± 20% or 25 CFM of design airflow
Required for homes permitted 5 starting 07/01/2016
EPA Form 5900-426
Revised 09/15/2015
Page 1 of 2
HVAC Commissioning Checklist 1, 2
ENERGY STAR Certified Homes, Version 3 / 3.1 (Rev. 08)
Footnotes
1.
This Checklist is designed to align with the requirements of ANSI / ACCA’s 5 QI-2015 protocol, thereby improving the performance of HVAC
equipment in new homes when compared to homes built to minimum code. However, these features alone cannot prevent all ventilation,
indoor air quality, and HVAC problems (e.g., those caused by a lack of maintenance by occupants). Therefore, this Checklist is not a
guarantee of proper ventilation, indoor air quality, or HVAC performance.
This Checklist applies to split air conditioners, unitary air conditioners, air-source heat pumps, and water-source (i.e., geothermal) heat
pumps up to 65 kBtuh with forced-air distribution systems (i.e., ducts) and to furnaces up to 225 kBtuh with forced-air distribution systems
(i.e., ducts). All other permutations of equipment (e.g., boilers, mini-split / multi-split systems) and distribution systems are exempt.
2.
For a home certified in the State of ID, MT, OR, or WA, the following alternatives and exemptions apply:
a.
For a home with an air-source heat pump up to 65 kBtuh with a forced-air distribution system (i.e., ducts), the contractor is permitted to
complete the 2011 PTCS® Commissioned Heat Pump Certificate and Startup Form in lieu of this Checklist.
b.
For a home with a split air conditioner or unitary air conditioner up to 65 kBtuh with a forced-air distribution system (i.e., ducts), the
contractor is permitted to complete the Northwest Central AC Commissioning & Startup Form in lieu of this Checklist.
c.
For a home in a location with < 600 CDD, the completion of this Checklist is recommended, but not required.
3.
Either factory-installed or field-installed TXV’s may be used. For field-installed TXV’s, ensure that sensing bulbs are insulated and tightly
clamped to the vapor line with good linear thermal contact at the recommended orientation, usually 4 or 8 o’clock.
4.
Air balancing of supply registers and return grilles is highly recommended to improve the performance of the HVAC system and comfort of
the occupants, but is not required at this time for certification. When air balancing is completed, balancing dampers or proper duct sizing
shall be used instead of looped or coiled ductwork to limit flow to diffusers. When balancing dampers are used, they shall be located at the
trunk to limit noise unless the trunk will not be accessible when the balancing process is conducted. In such cases, Opposable Blade Dampers
(OBD) or dampers located in the duct boot are permitted to be used.
5.
This Revision of the HVAC Commissioning Checklist is required to certify all homes permitted after 07/01/2016, but is allowed to be used for
any home permitted or completed prior to this date. The Home Energy Rater certifying the home may define the ‘permit date’ as either the
date that the permit was issued or the date of the contract on the home. In cases where permit or contract dates are not available, Providers
have discretion to estimate permit dates based on other construction schedule factors.
The public reporting and recordkeeping burden for this collection of information is estimated to average 30 minutes per response. Send comments on the Agency's need
for this information, the accuracy of the provided burden estimates, and any suggested methods for minimizing respondent burden, including through the use of
automated collection techniques to the Director, Collection Strategies Division, U.S. Environmental Protection Agency (2822T), 1200 Pennsylvania Ave., NW, Washington,
D.C. 20460. Include the OMB control number in any correspondence. Do not send the completed form to this address.
Required for homes permitted 5 starting 07/01/2016
Revised 09/15/2015
Page 2 of 2