U.S. NUCLEAR REGULATORY COMMISSION |
||
|
DRAFT REGULATORY GUIDE, DG-1407
Proposed Revision 5 to Regulatory Guide 1.192
|
|
Issue Date: Month 2022 Technical Lead: T. Scarbrough
|
OPERATION AND MAINTENANCE CODE CASE ACCEPTABILITY, ASME OM CODE
Purpose
This regulatory guide (RG) lists Code Cases associated with the American Society of Mechanical Engineers (ASME) Operation and Maintenance of Nuclear Power Plants, Division 1, OM Code: Section IST (OM Code) (Ref. 1), that the U.S. Nuclear Regulatory Commission (NRC) has approved for use as voluntary alternatives to the mandatory ASME OM Code provisions that are incorporated by reference into Title 10 of the Code of Federal Regulations (10 CFR) Part 50, “Domestic Licensing of Production and Utilization Facilities” (Ref. 2). The editions and addenda of the ASME OM Code have had different titles from 2005 to 2020 and are referred to as the OM Code collectively in this RG.
Applicability
This RG applies to reactor licensees and applicants subject to 10 CFR Part 50, Section 50.55a, “Codes and standards.”
Applicable Regulations
General Design Criterion (GDC) 1, “Quality Standards and Records,” of Appendix A, “General Design Criteria for Nuclear Power Plants,” to 10 CFR Part 50 requires, in part, that structures, systems, and components important to safety be designed, fabricated, erected, and tested to quality standards commensurate with the importance of the safety function to be performed. Where generally recognized codes and standards are used, GDC 1 requires that they be identified and evaluated to determine their applicability, adequacy, and sufficiency and be supplemented or modified as necessary to ensure a quality product in keeping with the required safety function.
10 CFR Part 50, Appendix A, GDC 30, “Quality of Reactor Coolant Pressure Boundary,” requires, in part, that components that are part of the reactor coolant pressure boundary be designed, fabricated, erected, and tested to the highest quality standards practical.
10 CFR Part 50, Appendix B, “Quality Assurance Criteria for Nuclear Power Plants and Fuel Processing Plants,” requires, in part, a program for inspection of activities affecting quality to verify conformance with documented instructions and procedures.
10 CFR 50.55a(f) requires, in part, that Class 1, 2, and 3 components and their supports meet the requirements of the ASME OM Code or equivalent quality standards.
10 CFR 52.79(a)(11) (Ref. 3) requires the final safety analysis report to include “a description of the program(s), and their implementation, necessary to ensure that the systems and components meet the requirements of the ASME Boiler and Pressure Vessel Code and the ASME Code for Operation and Maintenance of Nuclear Power Plants in accordance with 50.55a of this chapter.”
Related Guidance
RG 1.84, “Design, Fabrication, and Materials Code Case Acceptability, ASME Section III” (Ref. 4), lists the ASME Boiler and Pressure Vessel Code (BPV Code), Section III, Code Cases that the NRC has approved for use as voluntary alternatives to the mandatory ASME BPV Code provisions that are incorporated into 10 CFR 50.55a.
RG 1.147, “Inservice Inspection Code Case Acceptability, ASME Section XI, Division 1” (Ref. 5), lists the ASME BPV Code, Section XI, Code Cases that the NRC has approved for use as voluntary alternatives to the mandatory ASME BPV Code provisions that are incorporated into 10 CFR 50.55a.
RG 1.193, “ASME Code Cases Not Approved for Use” (Ref. 6), lists the ASME BPV Code, Section III and Section XI, Code Cases and ASME OM Code Cases that the NRC has not approved for generic use.
Purpose of This Regulatory Guide
This RG is incorporated into 10 CFR 50.55a by reference. The RG contains new OM Code Cases and revisions to existing OM Code Cases that the staff has approved for use, as listed in Tables 1 and 2 of this guide. The RG also states the requirements governing the use of OM Code Cases. Applicants or licensees may voluntarily use OM Code Cases the NRC has approved as an alternative to compliance with OM Code provisions that have been incorporated by reference into 10 CFR 50.55a. Because of continuing change in the status of OM Code Cases, the staff plans periodic updates to 10 CFR 50.55a and to this guide to accommodate new OM Code Cases and any revisions of existing OM Code Cases.
Paperwork Reduction Act
This RG provides voluntary guidance for implementing the mandatory information collections in 10 CFR Parts 50 and 52 that are subject to the Paperwork Reduction Act of 1995 (44 U.S.C. 3501 et. seq.). These information collections were approved by the Office of Management and Budget (OMB), under control numbers 3150-0011 and 3150-0151, respectively. Send comments regarding this information collection to the FOIA, Library, and Information Collections Branch (T6-A10M), Office of the Chief Information Officer, U.S. Nuclear Regulatory Commission, Washington, DC 20555‑0001, or by e-mail to [email protected], or to the OMB reviewer at: OMB Office of Information and Regulatory Affairs (3150–0011 and 3150-0151), Attn: Desk Officer for the Nuclear Regulatory Commission, 725 17th Street, NW, Washington, DC 20503; email: [email protected].
Public Protection Notification
The NRC may not conduct or sponsor, and a person is not required to respond to, a collection of information unless the document requesting or requiring the collection displays a currently valid OMB control number.
B. DISCUSSION
Reason for Revision
RG 1.192, Revision 5, includes information reviewed by the NRC on OM Code Cases listed in the 2022 Edition of the OM Code and on the ASME Codes & Standards (C&S) Connect website. This revision updates and supersedes RG 1.192, Revision 4, which included information from the 2020 Edition of the OM Code.
Background
Provisions of the ASME BPV Code have been used since 1971 as one part of the framework to establish the necessary design, fabrication, construction, testing, and performance requirements for structures, systems, and components important to safety in nuclear power plants. Among other things, ASME standards committees develop improved methods for the construction, inservice inspection, and inservice testing (IST) of ASME Class 1, 2, 3, metal containment (MC), and concrete containment (CC) nuclear power plant components. A broad spectrum of stakeholders participates in the ASME process to help ensure consideration of the various interests.
In 1990, ASME published the initial edition of the OM Code that provides rules for IST and inservice examination of pumps, valves, and dynamic restraints (snubbers). The ASME Committee on Operation and Maintenance of Nuclear Power Plants maintains the OM Code, which it developed in response to the ASME Board on Nuclear Codes and Standards directive. The directive transferred responsibility for development and maintenance of rules for the IST and inservice examination of pumps, valves, and dynamic restraints (snubbers) from the ASME Section XI Subcommittee on Nuclear Inservice Inspection to the ASME OM Committee on Operation and Maintenance of Nuclear Power Plants. ASME intended the OM Code to replace Section XI, rules for IST and inservice examination of pumps, valves, and dynamic restraints (snubbers), and the Section XI rules for IST and inservice examination of these components that had been incorporated by reference into NRC regulations have been deleted from Section XI. The NRC endorsed the OM Code for the first time in an amendment to 10 CFR 50.55a (Volume 64 of the Federal Register, page 51370 (64 FR 51370), September 22, 1999)). The NRC endorsed OM Code Cases through this guide for the first time in June 2003. Beginning with the 2009 Edition, ASME changed the title of the OM Code to “Operation and Maintenance of Nuclear Power Plants.”
ASME periodically publishes a new edition of the OM Code. The latest editions and addenda of the OM Code that the NRC has approved for use are referenced in 10 CFR 50.55a(a)(1)(iv). ASME also periodically publishes OM Code Cases, which provide alternatives to existing OM Code requirements that ASME developed and approved. This RG identifies the OM Code Cases that the NRC has determined to be acceptable alternatives to applicable parts of the OM Code. Applicants or licensees may use these OM Code Cases without requesting authorization from the NRC, provided that they are used with any identified limitations or modifications. Under 10 CFR 50.55a(z), a licensee or applicant may request authorization to use OM Code Cases that the NRC has not yet endorsed. That section permits the use of alternatives to the OM Code requirements referenced in 10 CFR 50.55a, provided that the proposed alternatives result in an acceptable level of quality and safety and their use is authorized by the Director of the Office of Nuclear Reactor Regulation.
The OM Code is incorporated by reference into 10 CFR 50.55a. The regulation at 10 CFR 50.55a(b)(6) states the requirements governing the use of OM Code Cases. Because of continuing change in the status of OM Code Cases, the NRC staff plans periodic updates to 10 CFR 50.55a and to this guide to accommodate new OM Code Cases and any revisions of existing OM Code Cases. OM Code Cases that the NRC approves provide an acceptable voluntary alternative to the mandatory OM Code provisions.
When an applicant or licensee initially implements an OM Code Case, 10 CFR 50.55a requires implementation of the most recent version of that Code Case as listed in Tables 1 and 2. If an applicant or licensee implements an OM Code Case and a later version of the Code Case is incorporated by reference into 10 CFR 50.55a and listed in Tables 1 and 2 during the licensee’s present 120-month IST program interval, that licensee may use either the later version or the previous version. An exception to this provision would be the inclusion of a condition on the use of the OM Code Case that is necessary, for example, to enhance safety. Licensees who choose to continue use of the OM Code Case during the subsequent 120-month IST program interval will be required to implement the latest version incorporated by reference into 10 CFR 50.55a and listed in Tables 1 and 2.
ASME may annul OM Code Cases because the provisions have been incorporated into the OM Code, the application for which it was specifically developed no longer exists, or experience has shown that an examination or testing method is no longer adequate. After ASME has annulled an OM Code Case, and the NRC has amended 10 CFR 50.55a and this guide, applicants or licensees may not implement that OM Code Case for the first time. However, an applicant or licensee who implemented the OM Code Case prior to annulment may continue to use that Code Case through the end of the present IST interval. An annulled OM Code Case cannot be used in the subsequent IST interval unless implemented as an approved alternative under 10 CFR 50.55a(z). If an OM Code Case is incorporated by reference into 10 CFR 50.55a and ASME later annuls it because experience has shown that an examination or testing method is inadequate, the NRC will amend 10 CFR 50.55a and this guide to remove the approval of the annulled Code Case. Applicants or licensees should not begin to implement such annulled OM Code Cases before the rulemaking. Notwithstanding these requirements, the Commission may impose new or revised OM Code requirements, including implementation schedules, which it determines are consistent with the Backfit Rule (10 CFR 50.109, “Backfitting”).
ASME may revise an OM Code Case, for example, to incorporate user experience. The licensee or applicant cannot apply the older or superseded version of the OM Code Case for the first time. If an applicant or a licensee applied a Code Case before it was listed as superseded, the applicant or the licensee may continue to use the Code Case until the applicant or licensee updates its Construction Code of Record (an applicant would update its application) or until the licensee’s 120‑month IST update interval expires, after which the continued use of the OM Code Case is prohibited unless the NRC grants approval under 10 CFR 50.55a(z). If an OM Code Case is incorporated by reference into 10 CFR 50.55a and later ASME issues a revised version because experience has shown that the design analysis, construction method, examination method, or testing method is inadequate, the NRC will amend 10 CFR 50.55a and the relevant RG to remove the approval of the superseded OM Code Case. Applicants and licensees should not begin to implement such superseded OM Code Cases in advance of the rulemaking.
RG 1.193, “ASME Code Cases Not Approved for Use,” lists the OM Code Cases that the NRC determined to be unacceptable. With regard to the use of any OM Code Case, the user is responsible for ensuring that the provisions of the OM Code Case do not conflict with regulatory requirements or licensee commitments.
C. Regulatory Position
RG 1.192, Revision 5, supersedes Revision 4. For Revision 5 of RG 1.192, the NRC reviewed the OM Code Cases listed in an applicability index on the ASME C&S Connect website. ASME prepared the OM Code Case Applicability Index to specify the applicability of each OM Code Case because some new Code Cases do not include a paragraph specifying the editions and addenda of the ASME OM Code to which they are applicable. The NRC staff reviewed the OM Code Case Applicability Index dated July 1, 2022 (ADAMS Accession No. ML22279A967) as part of this revision to RG 1.192. Any conditions related to use of the OM Code Case Applicability Index for specific OM Code Cases are indicated in this revision to RG 1.192 in the applicable table. The tables in this RG refer to the 2022 Edition; however, the specific applicability of each Code Case is provided in the OM Code Case Applicability Index with any conditions specified in this revision to RG 1.192.
Appendix A to this guide gives a complete list of all OM Code Cases published by ASME. The table in Appendix A lists the action ASME has taken (e.g., new or revised OM Code Case), the edition or addenda in which the OM Code Case was published, and the table in the RG that lists each OM Code Case. The following four tables list the OM Code Cases addressed by this RG:
Table 1, “Acceptable OM Code Cases,” lists the OM Code Cases that are acceptable to the NRC for implementation in the IST of light-water-cooled nuclear power plants.
Table 2, “Conditionally Acceptable OM Code Cases,” lists the OM Code Cases that are acceptable, provided that they are used with the identified conditions (i.e., the OM Code Case is generally acceptable, but the NRC has determined that the requirements in the Code Case, which are alternatives to the OM Code, must be supplemented in order to provide an acceptable level of quality and safety).
Table 3, “OM Code Cases That Have Been Superseded by Revised OM Code Cases,” lists OM Code Cases that have been superseded through revision.
Table 4, “Annulled OM Code Cases,” lists the OM Code Cases that have been annulled by ASME.
1. Acceptable OM Code Cases
The OM Code Cases listed in Table 1 are acceptable to the NRC for application in applicant’s or licensee’s IST programs. The OM Code uses two approaches to list revisions of OM Code Cases. The first approach lists OM Code Cases according to edition or addenda (e.g., OMN-6, 2020 Edition). The second approach uses a numbering system (e.g., OMN-1, Revision 1) that states the latest revision number of a Code Case. Thus, the tables below show either the latest edition or addenda in which an OM Code Case was published or the latest revision number of an OM Code Case, in accordance with the requirement in 10 CFR 50.55a that licensees or applicants implement the most recent version of an OM Code Case. The edition and addenda are listed in addition to the revision number because the OM Code in some cases reaffirms OM Code Cases with minor changes. Listing both the revision number and edition or addenda ensures that the latest version of the OM Code Case is implemented. To assist users, new and revised OM Code Cases are shaded in grey to distinguish them from those approved in previous versions of this guide.
Table 1. Acceptable OM Code Cases
Code Case Number |
Table 1 Acceptable OM Code Cases |
OMN-6 (2022 Edition) |
Alternate Rules for Digital Instruments |
OMN-7 (2022 Edition) |
Alternative Requirements for Pump Testing |
OMN-8 (2022 Edition) |
Alternative Rules for Preservice and Inservice Testing of Power-Operated Valves That Are Used for System Control and Have a Safety Function per OM-10, ISTC-1.1, or ISTA-1100 |
OMN-13, Revision 3 (2020 Edition) |
Performance-Based Requirements for Extending Snubber Inservice Visual Examination Interval at LWR Power Plants [OMN-13 Revision 3 incorporated into 2022 Edition] |
OMN-15, Revision 4 (2022 Edition) |
Performance-Based Requirements for Extending the Snubber Operational Readiness Testing Interval at LWR Power Plants |
OMN-16, Revision 2 (2022 Edition) |
Use of a Pump Curve for Testing
|
OMN-17, Revision 1 (2022 Edition) |
Alternative Requirements for Testing ASME Class 1 Pressure Relief/Safety Valves |
OMN-18 (2022 Edition) |
Alternate Testing Requirements for Pumps Tested Quarterly Within ±20% of Design Flow |
OMN-21 (2022 Edition) |
Alternative Requirements for Adjusting Hydraulic Parameters to Specified Reference Points |
OMN-22 (2020 Edition) |
Smooth Running Pumps [OMN-22 incorporated into 2022 Edition] |
OMN-23 (2022 Edition) |
Alternative Requirements for Testing Pressure Isolation Valves |
OMN-24 (2022 Edition) |
Alternative Requirements for Testing ASME Class 2 and 3 Pressure Relief Valves (For Relief Valves in a Group of One) |
OMN-25 (2022 Edition) |
Alternative Requirements for Testing Appendix I Pressure Relief Valves |
OMN-26 (2022 Edition) |
Alternate Risk-Informed and Margin Based Rules for Inservice Testing of Motor Operated Valves |
OMN-27 (2022 Edition) |
Alternative Requirements for Testing Category A Valves (Non-PIV/CIV) |
OMN-28 (2022 Edition) |
Alternative Valve Position Verification Approach to Satisfy ISTC-3700 for Valves Not Susceptible to Stem-Disk Separation |
OMN-29 (2022 Edition) |
Pump Condition Monitoring Program |
OMN-30 (2022 Edition) |
Alternative Valve Position Verification Approach to Satisfy ISTC-3700 |
2. Conditionally Acceptable OM Code Cases
The OM Code Cases listed in Table 2 are acceptable to the NRC for application in applicant’s or licensee’s IST programs within the conditions indicated by the NRC. The OM Code uses two approaches to list revisions of OM Code Cases. The first approach lists OM Code Cases according to edition or addenda (e.g., OMN-6, 2020 Edition). The second approach uses a numbering system (e.g., OMN-1, Revision 1) that states the latest revision number of a Code Case. Thus, the tables below show either the latest edition or addenda in which an OM Code Case was published or the latest revision number of an OM Code Case, in accordance with the requirement in 10 CFR 50.55a that licensees or applicants implement the most recent version of an OM Code Case. The edition and addenda are listed in addition to the revision number because the OM Code in some cases reaffirms OM Code Cases with minor changes. Listing both the revision number and edition or addenda ensures that the latest version of the OM Code Case is implemented. To assist users, new and revised OM Code Cases are shaded in grey to distinguish them from those approved in previous versions of this guide. In Table 2, where an OM Code Case is specified as acceptable for application at nuclear power plants with a Code of Record of any edition or addenda of the OM Code incorporated by reference in 10 CFR 50.55a(a)(1)(iv), applicants and licensees should verify that the OM Code Case is applied to the proper paragraphs in the OM Code edition or addenda specified as the Code of Record for the specific nuclear power plant, because paragraphs might be re-numbered in newer editions or addenda of the OM Code.
Table 2. Conditionally Acceptable OM Code Cases
3. OM Code Cases Superseded by Revised OM Code Cases
Table 3 lists OM Code Cases that have been superseded by revision.
Table 3. OM Code Cases That Have Been Superseded by Revised OM Code Cases
4. Annulled OM Code Cases
ASME has annulled the OM Code Cases listed in Table 4.
Table 4. Annulled OM Code Cases
Code Case Number and Year Annulled |
Table 4 Annulled OM Code Cases |
OMN-2 2014 |
Thermal Relief Valve Code Case, OM Code 1995, Appendix I
|
OMN-5 2014 |
Testing of Liquid Service Relief Valves Without Insulation
|
OMN-14 2014 |
Alternative Rules for Valve Testing Operations and Maintenance, Appendix I: BWR CRD Rupture Disk Exclusion
|
D. IMPLEMENTATION
The purpose of this section is to provide information to applicants and licensees regarding the NRC staff’s plans for using this regulatory guide. This regulatory guide lists the ASME OM Code Section IST Code Cases that the NRC has approved for use as voluntary alternatives to the mandatory ASME OM Code provisions that are incorporated by reference into 50.55a. The requirements addressing implementation of OM Code Cases are contained in 10 CFR 50.55a(b)(6). An applicant’s or a licensee’s voluntary application of an approved Code Case does not constitute backfitting, inasmuch as there is no imposition of a new requirement or new position. No backfitting is intended or approved in connection with the issuance of this guide.
REFERENCES1
American Society of Mechanical Engineers (ASME) Code for Operation and Maintenance of Nuclear Power Plants, 2020, New York, NY.2
U.S. Code of Federal Regulations (CFR), “Domestic Licensing of Production and Utilization Facilities,” Part 50 Chapter 1, Title 10, “Energy.”
CFR, “Licenses, Certifications, and Approvals for Nuclear Power Plants,” Part 52 Chapter 1, Title 10, “Energy.”
U.S. Nuclear Regulatory Commission (NRC), Regulatory Guide (RG) 1.84, “Design, Fabrication, and Materials Code Case Acceptability, ASME Section III,” Washington, DC.
NRC, RG 1.147, “Inservice Inspection Code Case Acceptability, ASME Section XI, Division 1,” Washington, DC.
NRC, RG 1.193, “ASME Code Cases Not Approved for Use,” Washington, DC.
NRC, RG 1.174, “An Approach for Using Probabilistic Risk Assessment in Risk-Informed Decisions on Plant-Specific Changes to the Licensing Basis,” Washington, DC.
NRC, RG 1.175, “An Approach for Plant-Specific, Risk-Informed Decisionmaking: Inservice Testing,” Washington, DC.
NRC, RG 1.200, “An Approach for Determining the Technical Adequacy of Probabilistic Risk Assessment Results for Risk-Informed Activities,” Washington, DC.
NRC, RG 1.201, “Guidelines for Categorizing Structures, Systems, and Components in Nuclear Power Plants According to Their Safety Significance,” Washington, DC.
APPENDIX A
NUMERICAL LISTING OF ASME OPERATION AND MAINTENANCE
CODE CASES
OM Code Case |
ASME Action Regarding Code Case |
Year OM Code Case Was Developed/Revised |
OM Code Case Was Approved in RG 1.192 (Y/N) / Which Revision of RG 1.192 |
Table Where OM Code Case Is Listed in Revision 4 of RG 1.192 |
OMN-1 |
New Reaffirmed5 Reaffirmed Revised Reaffirmed Revised Reaffirmed Reaffirmed |
1996 Addenda 1999 Addenda 2001 Edition 2002 Addenda 2004 Edition 2006 Addenda 2009 Edition 2012 Edition |
50.55a2 Y / Revision 0 N N N Y / Revision 1 N N |
All versions of OMN-1 are listed in Table 3 |
OMN-1, Revision 1 |
New Reaffirmed Reaffirmed |
2009 Edition 2012 Edition 2015 Edition |
N Y / Revision 2 N |
Table 3 Table 3 Table 3 |
OMN-1, Revision 2 |
New Reaffirmed Reaffirmed |
2017 Edition 2020 Edition 2022 Edition |
Y / Revision 3 Y / Revision 4 Y / Revision 5 |
Table 3 Table 3 Table 2 |
OMN-2 |
New Reaffirmed Reaffirmed Reaffirmed Reaffirmed Annulled |
1998 Edition 2001 Edition 2004 Edition 2009 Edition 2012 Edition 2017 Edition |
Y / Revision 0 N Y / Revision 1 N Y / Revision 2 N |
Table 3 Table 3 Table 3 Table 3 Table 3 Table 4 |
OMN-3 |
New Reaffirmed Revised Reaffirmed Reaffirmed Reaffirmed Reaffirmed Reaffirmed Reaffirmed Reaffirmed |
1998 Edition 2001 Edition 2002 Addenda 2004 Edition 2009 Edition 2012 Edition 2015 Edition 2017 Edition 2020 Edition 2022 Edition |
Y/ Revision 0 N N Y / Revision 1 N Y / Revision 2 N Y / Revision 3 Y / Revision 4 Y / Revision 5 |
Table 3 Table 3 Table 3 Table 3 Table 3 Table 3 Table 3 Table 3 Table 3 Table 2 |
OMN-4 |
New Reaffirmed Reaffirmed Reaffirmed Reaffirmed Reaffirmed Reaffirmed Reaffirmed Reaffirmed |
1999 Addenda 2001 Edition 2004 Edition 2009 Edition 2012 Edition 2015 Edition 2017 Edition 2020 Edition 2022 Edition |
Y/ Revision 0 N Y / Revision 1 N Y / Revision 2 N Y / Revision 3 Y / Revision 4 Y / Revision 5 |
Table 3 Table 3 Table 3 Table 3 Table 3 Table 3 Table 3 Table 3 Table 2 |
OMN-5 |
New Reaffirmed Reaffirmed Reaffirmed Reaffirmed Reaffirmed Annulled |
1999 Addenda 2001 Edition 2004 Edition 2006 Addenda 2009 Edition 2012 Edition 2017 Edition |
Y / Revision 0 N N Y / Revision 1 N Y / Revision 2 N |
Table 3 Table 3 Table 3 Table 3 Table 3 Table 3 Table 4 |
OMN-6 |
New Reaffirmed Reaffirmed Reaffirmed Revised Reaffirmed Reaffirmed Reaffirmed Reaffirmed Reaffirmed Reaffirmed |
1999 Addenda 2001 Edition 2002 Addenda 2004 Edition 2006 Addenda 2009 Edition 2012 Edition 2015 Edition 2017 Edition 2020 Edition 2022 Edition |
Y/ Revision 0 N N N Y/ Revision 1 N Y / Revision 2 N Y / Revision 3 Y / Revision 4 Y / Revision 5 |
Table 3 Table 3 Table 3 Table 3 Table 3 Table 3 Table 3 Table 3 Table 3 Table 3 Table 1 |
OMN-7 |
New Reaffirmed Reaffirmed Reaffirmed Reaffirmed Reaffirmed Reaffirmed Reaffirmed Reaffirmed Reaffirmed Reaffirmed Reaffirmed |
2000 Addenda 2001 Edition 2002 Addenda 2004 Edition 2005 Addenda 2006 Addenda 2009 Edition 2012 Edition 2015 Edition 2017 Edition 2020 Edition 2022 Edition |
Y/ Revision 0 N N N N Y / Revision 1 N Y / Revision 2 N Y / Revision 3 Y / Revision 4 Y / Revision 5 |
Table 3 Table 3 Table 3 Table 3 Table 3 Table 3 Table 3 Table 3 Table 3 Table 3 Table 3 Table 1 |
OMN-8 |
New Reaffirmed Reaffirmed Reaffirmed Reaffirmed Revised Reaffirmed Reaffirmed Reaffirmed Reaffirmed Reaffirmed Reaffirmed |
2000 Addenda 2001 Edition 2003 Addenda 2004 Edition 2005 Addenda 2006 Addenda 2009 Edition 2012 Edition 2015 Edition 2017 Edition 2020 Edition 2022 Edition |
Y/ Revision 0 N N N N Y / Revision 1 N Y / Revision 2 N Y / Revision 3 Y / Revision 4 Y / Revision 5 |
Table 3 Table 3 Table 3 Table 3 Table 3 Table 3 Table 3 Table 3 Table 3 Table 3 Table 3 Table 1 |
OMN-9 |
New Reaffirmed Reaffirmed Reaffirmed Reaffirmed Reaffirmed Reaffirmed Reaffirmed Reaffirmed Reaffirmed |
2000 Addenda 2001 Edition 2003 Addenda 2004 Edition 2009 Edition 2012 Edition 2015 Edition 2017 Edition 2020 Edition 2022 Edition |
Y/ Revision 0 N N Y / Revision 1 N Y / Revision 2 N Y / Revision 3 Y / Revision 4 Y / Revision 5 |
Table 3 Table 3 Table 3 Table 3 Table 3 Table 3 Table 3 Table 3 Table 3 Table 2 |
OMN-10 |
New Reaffirmed Reaffirmed Reaffirmed Reaffirmed Reaffirmed Reaffirmed Reaffirmed Reaffirmed Reaffirmed Reaffirmed |
2000 Addenda 2001 Edition 2003 Addenda 2004 Edition 2006 Addenda 2009 Edition 2012 Edition 2015 Edition 2017 Edition 2020 Edition 2022 Edition |
N N N N N N N N N N N |
Code Case OMN-10 has not been approved for use and is listed in RG 1.193 |
OMN-116 |
New Reaffirmed Reaffirmed |
2001 Edition 2003 Addenda 2004 Edition |
Y / Revision 0 Y / Revision 1 Y / Revision 1 |
Table 3 Table 3 Table 3 |
OMN-12 |
New Reaffirmed Reaffirmed Reaffirmed Reaffirmed Reaffirmed Reaffirmed Reaffirmed |
2001 Edition 2004 Edition 2009 Edition 2012 Edition 2015 Edition 2017 Edition 2020 Edition 2022 Edition |
Y / Revision 0 Y / Revision 1 N Y / Revision 2 N Y / Revision 3 Y / Revision 4 Y / Revision 5 |
Table 3 Table 3 Table 3 Table 3 Table 3 Table 3 Table 3 Table 2 |
OMN-13 |
New Reaffirmed Reaffirmed Reaffirmed Reaffirmed |
2001 Edition 2001 Edition 2004 Edition 2009 Edition 2012 Edition |
Y/ Revision 0 N Y / Revision 1 N N |
All versions of OMN-13 are listed in Table 3 |
OMN-13, Revision 1 |
New Reaffirmed |
2009 Edition 2012 Edition |
N N |
All versions of OMN‑13, Revision 1, are listed in Table 3 |
OMN-13, Revision 2 |
New Reaffirmed Reaffirmed Reaffirmed |
2009 Edition 2012 Edition 2015 Edition 2017 Edition |
N Y / Revision 2 N Y / Revision 3 |
Table 3 Table 3 Table 3 Table 3 |
OMN-13, Revision 3 |
New Annulled |
2020 Edition 2022 Edition |
Y / Revision 4 N |
Table 1
|
OMN-14 |
New Reaffirmed Reaffirmed Reaffirmed Annulled |
2003 Addenda 2004 Edition 2009 Edition 2012 Edition 2017 Edition |
N Y / Revision 1 N Y / Revision 2 N |
Table 3 Table 3 Table 3 Table 3 Table 4 |
OMN-15 |
New Revised Reaffirmed Reaffirmed |
2004 Edition 2006 Addenda 2009 Edition 2012 Edition |
N N N N |
Code Case OMN-15 has not been approved for use and is listed in RG 1.193 |
OMN-15, Revision 27 |
New Reaffirmed Reaffirmed Reaffirmed |
2011 Addenda 2012 Edition 2015 Edition 2017 Edition |
N Y / Revision 2 N Y / Revision 3 |
Table 3 Table 3 Table 3 Table 3 |
OMN-15, Revision 3 |
New Reaffirmed |
2020 Edition 2022 Edition |
Y / Revision 4 Y / Revision 5 |
Table 3 Table 1 |
OMN-16 |
New Reaffirmed Reaffirmed |
2006 Addenda 2009 Edition 2012 Edition |
Y / Revision 1 N N |
Table 3 Table 3 Table 3 |
OMN-16, Revision 1 |
New Reaffirmed |
2012 Edition 2015 Edition |
Y / Revision 2 N |
Table 3 Table 3 |
OMN-16, Revision 2 |
New Reaffirmed Reaffirmed |
2017 Edition 2020 Edition 202 Edition |
Y / Revision 3 Y / Revision 4 Y / Revision 5 |
Table 3 Table 3 Table 1 |
OMN-17 |
New Reaffirmed Reaffirmed Reaffirmed |
2009 Edition 2012 Edition 2015 Edition 2017 Edition |
N Y / Revision 2 N Y / Revision 3 |
Table 3 Table 3 Table 3 Table 3 |
OMN-17, Revision 1 |
New Reaffirmed |
2020 Edition 2022 Edition |
Y / Revision 4 Y / Revision 5 |
Table 3 Table 1 |
OMN-18 |
New Reaffirmed Reaffirmed Reaffirmed Reaffirmed Reaffirmed |
2009 Edition 2012 Edition 2015 Edition 2017 Edition 2020 Edition 2022 Edition |
N Y / Revision 2 N Y / Revision 3 Y / Revision 4 Y / Revision 5 |
Table 3 Table 3 Table 3 Table 3 Table 3 Table 1 |
OMN-19 |
New Reaffirmed Reaffirmed Reaffirmed Reaffirmed Reaffirmed |
2011 Addenda 2012 Edition 2015 Edition 2017 Edition 2020 Edition 2022 Edition |
N Y / Revision 2 N Y / Revision 3 Y / Revision 4 Y / Revision 5 |
Table 3 Table 3 Table 3 Table 3 Table 3 Table 2 |
OMN-20 |
New Reaffirmed Reaffirmed Reaffirmed Reaffirmed |
2012 Edition 2015 Edition 2017 Edition 2020 Edition 2022 Edition |
Y / Revision 2 N Y / Revision 3 Y / Revision 4 Y / Revision 5 |
Table 3 Table 3 Table 3 Table 3 Table 2 |
OMN-21 |
New Reaffirmed Reaffirmed Reaffirmed |
2015 Edition 2017 Edition 2020 Edition 2022 Edition |
N Y / Revision 3 Y / Revision 4 Y / Revision 5 |
Table 3 Table 3 Table 3 Table 1 |
OMN-22 |
New Annulled |
2020 Edition 2022 Edition |
Y / Revision 4 N |
Table 1
|
OMN-23 |
New Reaffirmed |
2020 Edition 2022 Edition |
Y / Revision 4 Y / Revision 5 |
Table 3 Table 1 |
OMN-24 |
New Reaffirmed |
2020 Edition 2022 Edition |
Y / Revision 4 Y / Revision 5 |
Table 3 Table 1 |
OMN-25 |
New Reaffirmed |
2020 Edition 2022 Edition |
Y / Revision 4 Y / Revision 5 |
Table 3 Table 1 |
OMN-26 |
New Reaffirmed |
2020 Edition 2022 Edition |
Y / Revision 4 Y / Revision 5 |
Table 3 Table 1 |
OMN-27 |
New Reaffirmed |
2020 Edition 2022 Edition |
Y / Revision 4 Y / Revision 5 |
Table 3 Table 1 |
OMN-28 |
New |
2022 Edition |
Y / Revision 5 |
Table 1 |
OMN-29 |
New |
2022 Edition |
Y / Revision 5 |
Table 1 |
OMN-30 |
New |
2022 Edition |
Y / Revision 5 |
Table 1 |
OMN-31 |
New |
2022 Edition |
Y / Revision 5 |
Table 2 |
2Publicly available NRC published documents are available electronically through the NRC Library on the NRC’s public Web site at http://www.nrc.gov/reading-rm/doc-collections/ and through the NRC’s Agencywide Documents Access and Management System (ADAMS) at http://www.nrc.gov/reading-rm/adams.html. The documents can also be viewed online or printed for a fee in the NRC’s Public Document Room at 11555 Rockville Pike, Rockville, MD. For problems with ADAMS, contact the Public Document Room staff at 301-415-4737 or (800) 397-4209; fax (301) 415-3548; or e-mail [email protected].
2Copies may be purchased from the American Society of Mechanical Engineers, Two Park Avenue, New York, NY 10016-5990; telephone (800) 843-2763. Purchase information is available through the ASME Web-based store at https://www.asme.org/publications-submissions/publishing-information.
5 In some cases, clarifications or editorial changes were made in reaffirmed ASME OM Code Cases, and notations on where those changes occurred may not have been provided with the ASME OM Code Case.
6 OM Code Case OMN-11 in the 2006 Addenda and later Editions to the OM Code is no longer applicable because the requirements of OM Code Case OMN-11 have been merged into OM Code Case OMN-1.
7 It should be noted that a different number convention was used with respect to OMN-15; Revision 1 to this OM Code Case does not exist.
This RG is being issued in draft form to involve the public in the development of regulatory guidance in this area. It has not received final staff review or approval and does not represent an NRC final staff position. Public comments are being solicited on this DG and its associated regulatory analysis. Comments should be accompanied by appropriate supporting data. Comments may be submitted through the Federal rulemaking Web site, http://www.regulations.gov, by searching for draft regulatory guide DG-1407. Alternatively, comments may be submitted to Office of the Secretary, U.S. Nuclear Regulatory Commission, Washington, DC 20555-0001, ATTN: Rulemakings and Adjudications Staff. Comments must be submitted by the date indicated in the Federal Register notice.
Electronic copies of this DG, previous versions of this guide, and other recently issued guides are available through the NRC’s public Web site under the Regulatory Guides document collection of the NRC Library at https://nrcweb.nrc.gov/reading-rm/doc-collections/reg-guides/. The DG is also available through the NRC’s Agencywide Documents Access and Management System (ADAMS) at http://www.nrc.gov/reading-rm/adams.html, under Accession No. ML22196A063. The regulatory analysis is associated with rulemaking and may be found in ADAMS under Accession No. ML22243A006. |
File Type | application/vnd.openxmlformats-officedocument.wordprocessingml.document |
Author | Wallace Norris |
File Modified | 0000-00-00 |
File Created | 2023-08-29 |