THIS IS THE EXCERPT FROM THE DRAFT MECHANICAL FITTNG FINAL RULE THAT WILL DISCUSS THE CHANGES TO THE GAS DISTRIBUTION ANNUAL REPORT AND THE NEW MECHANICAL FITTING FAILURE FORM.
PRA
In response to the comments received from the 60-day PRA notice contained in the DIMP final rule, PHMSA made a number of revisions to the Gas Distribution Annual Report. To maintain transparency and gather further input, PHMSA published a 30-day notice (June 28, 2010; 75 FR 36615) to seek additional comments on the revised Gas Distribution Annual Report. PHMSA received eight comments which have been reviewed and responded to as follows.
Section of Form |
Comment |
PHMSA Response/Resulting Action |
General |
Standardize information collection terminology used for both Incident and Annual Report Forms.
|
|
Part A. Operator Information Question 6. (Commodity Transported) |
Instructions are unclear as to how operators with multiple gases should respond. |
|
Part C. Total Leaks and Hazardous Leaks Eliminated/Repaired During Year
|
There is no specific entry for collecting mechanical fitting leaks eliminated/repaired during the year in Part C. Since failure data on such fittings is collected in Part F, it would make sense to collect data specifically on them in Part C.
|
|
|
Modify form instructions for Part C to have all mechanical fitting failures included in “Material and Welds” as stated in 192.1007(b). Remove from “Equipment.” |
|
|
For aboveground leaks, clarify the instructions to state that operators should only report hazardous aboveground leaks (the preponderance of aboveground leaks are trivial and represent no threat to the public.) |
|
Part E. EFV Data
|
Operators should simply report all EFVs installed on the distribution system, not just on Single Family Residences. (No records to distinguish commercial and residential.)
|
|
|
The instructions should expressly state that operators can estimate the number of EFVs in service.
|
|
|
The option regarding reporting single-family or single-family branch services is confusing and holds no value. (Should be removed.)
|
|
|
This is a significant change from what was originally proposed, which was to report the number of EFVs that the operator installed during the year, which was easy to capture. Plus no discussion as to why this change was made.
|
|
|
It is not a problem identifying EFVs added to system for the year (w/no distinction to type).
|
|
|
Will successive annual reports require a cumulative total number of EFVs installed or only the number installed for the calendar year reporting period? If cumulative, from what date forward?
|
|
Part F. Mechanical Fitting Failure Data (THIS INFORMATION WILL BE PLACED ON THE NEW MECHANICAL FITTING FAILURE FORM) |
Form a stakeholders group to review the results and decide if the information request should sunset after the three- year OMB approval. Information in Part F is comprehensive and duplicative to other data collection efforts.
|
|
|
A major problem is the enormous expansion of the data. Mechanical fittings encompass an almost infinite universe of fittings. PHMSA’s federal register notice provides no explanation or justification for the expansion of the data request. Expanding the reporting scope increases reporting requirements by several orders of magnitude. There is no information in this OMB approval request regarding the paperwork burden for the great expansion in the data request. (Replace “mechanical fittings” with “compression couplings.”)
|
|
|
The “other” category following stab, nut follower, and bolted couplings should be deleted since they are the only type of compression type fittings.
|
|
|
Delete the line beginning with “Was the Failure a Result of” and the associated subcategories.
|
|
|
Delete “Pull Out” as a choice for “Location of Leak.”
|
“Pull Out” as a choice for “Location of the Leak” and revising “Location of Leak” to “How did the leak occur.”
|
|
Rather than use the bullet outline (“►”, “♦”) throughout Part F, use a numbered outline format so that the subsections of Part F can be clearly referenced if questions arise.
|
|
|
The form should allow “Unavailable” to be entered under “Year Installed,” “Year Manufactured,” and “If Year Unknown, Provide Decade Installed:” This option is provided for in the instructions for the bulleted items after this section.
|
|
|
Part F of the form would be reproduced for each separate event where failure of a compression fitting results in a hazardous leak. PHMSA should provide that the (electronic) form have an index or tracking number to identify separate events within the calendar year (such as 20XX-XXX). Such a mechanism is important, not only to distinguish between reports compiled during the year, but also in the case where information is later determined to require a supplemental report to be filed.
|
|
|
The section titled “Location of Leak” should be relabeled “Type of Failure” with the existing choices: “Leak Through Seal,” “Leak Through Body,” or “Pull Out.”
|
|
|
The subsection “Was the Failure a Result of…” should have a choice of “Unknown” or “Other” since the cause may never be known.
|
|
|
Operators should be able to file Part F throughout the year
|
|
|
Under "Location of Leak" replace "Pull Out" with "Leak at Separation of Pipe and Coupling." (more appropriate and in line with other descriptions.) |
|
|
Annual report should only contain summary data |
|
Regs Text from Mech Fitting Rule
PART 191
A new § 191.12 is added to read as follows:
§ 191.12 Distribution Systems: Mechanical Fitting Failure Reports
Each mechanical fitting failure, as required by § 192.1009, must be submitted on a Mechanical Fitting Failure Report Form PHMSA F 7100.1-2. An operator must submit a mechanical fitting failure report for each mechanical fitting failure that occurs within a calendar year not later than March 15 of the following year (for example, all mechanical failure reports for calendar year 2011 must be submitted no later than March 15, 2012). Alternatively, an operator may elect to submit its reports throughout the year. In addition, an operator must also report this information to the state pipeline safety authority if a state exercises jurisdiction over the operator’s pipeline.
PART 192
Section 192.1009 is revised to read as follows:
§ 192.1009 What must an operator report when a mechanical fitting fails?
(a) Except as provided in paragraph (b) of this section, each operator of a distribution pipeline system must submit a report on each mechanical fitting failure, excluding any failure that results only in a nonhazardous leak, on a Department of Transportation Form PHMSA F 7100.1-2. The report(s) must be submitted in accordance with § 191.12.
(b) The mechanical fitting failure reporting requirements in paragraph (a) do not apply to the following:
(1) Master meter operators;
(2) Small LPG operator as defined in § 192.1001; or
(3) LNG facilities.