DOE F 220.74 Computer Room Air Conditioners

Compliance Statement Energy/Water Conservation Standards for Appliances

220.74 Computer Room Air Conditioners - v5.x - September 2024 Mockup_v2.xlsx

Manufacturers

OMB:

Document [xlsx]
Download: xlsx | pdf

Overview

Certification
Headers
Product Group Code


Sheet 1: Certification

OMB Control Number: 1910-1400 (Expiration Date: XXXXXX XX, XXXX)









Version 5.x
DOE F 220.74











Computer Room Air Conditioners
Product Type: Computer Room Air Conditioners Status of This Certification Sheet No Data
5.x








Overall Status of Template No Data



Click here for instructions for completing this form




















Each Importer and U.S. Manufacturer is legally required to certify the compliance of the products it imports, produces, assembles or manufactures. This party is the "Certifier" on this form.
This certification may be submitted by the Importer or U.S. manufacturer or by a Third Party Representative. This party is the "Submitter" on this form.


Certifier - Party Legally Obligated to Certify Compliance




Submitter - Party Submitting This Report





The party responsible for certification is (select one only):




The party submitting this report is (select one only):






Please enter required data



Please enter required data























Certifier Contact Information




Third Party Representative Contact Information, if Applicable

















Full Legal Name of Individual
Please enter required data
Full Legal Name of Individual
Please enter required data

Full Legal Name of Company
Please enter required data
Full Legal Name of Company
Please enter required data

Complete Company Mailing Address
Please enter required data
Complete Company Mailing Address
Please enter required data

Phone Number
Please enter required data
Phone Number
Please enter required data

Email Address
Please enter required data
Email Address
Please enter required data




























Compliance Statement











Select one of the options for 'Submitter - Party Submitting This Report' above















Submitter Signature (Type your Full Legal Name)
Please enter required data


Date (MM/DD/YYYY)
Please enter required data









































OMB Control Number: 1910-1400 (Expiration Date: XXXXXX XX, XXXX)
























Paperwork Reduction Act Statement











OMB Burden Disclosure Statement
























This data is being collected for manufacturers to certify compliance to DOE's energy conservation, water conservation, or design standards. The data you supply will be used by the Department to monitor compliance with the energy conservation, water conservation, and design standards and testing requirements for the consumer products and commercial and industrial equipment mandated by the Energy Policy and Conservation Act, as amended.

Public reporting burden for this collection of information is estimated to average 35 hours per response, including the time for reviewing instructions, searching existing data sources, gathering and maintaining the data needed, and completing and reviewing the collection of information. Send comments regarding this burden estimate or any other aspect of this collection of information, including suggestions for reducing this burden, to Office of the Chief Information Officer, Records Management Division, IM-23, Paperwork Reduction Project (1910-1400), U.S. Department of Energy, 1000 Independence Ave SW, Washington, DC, 20585-1290; and to the Office of Management and Budget (OMB), OIRA, Paperwork Reduction Project (1910-1400), Washington, DC 20503.

Notwithstanding any other provision of the law, no person is required to respond to, nor shall any person be subject to a penalty for failure to comply with a collection of information subject to the requirements of the Paperwork Reduction Act unless that collection of information displays a currently valid OMB control number.

Submission of this data is mandatory.




Sheet 2: Headers

Computer Room Air Conditioners - v5.x






















































Column Headers: Status Manufacturer Brand Name(s) Basic Model Number Individual Model Number Covered by Basic Model (Indoor Unit or Package Unit) Individual Model Number Covered by Basic Model (Outdoor Unit), if Applicable Have Any of the
Model Numbers
Been Identified
as Private by
the
Manufacturer?
Action Product Group Code Sample Size (Number of Units Tested) Is the Certification for this Basic Model Based on a Waiver of DOE's Test Procedure Requirements? Date of Test Procedure Waiver, if Applicable Is the Certification based upon any Exception Relief from an Applicable Standard by DOE's Office of Hearing and Appeals? Date of Exception Relief, if Applicable Is Certification Based on the use of an Alternative Efficiency Determination Method (AEDM)? Name of AEDM (If Applicable) Does the Manufacturer Elect the Witness Test Option for Verification Testing? (If Applicable) Is This Basic Model Split System or Single-Package? Net Sensible Coefficient of Performance (NSenCOP) Net Sensible Cooling Capacity (Btu/hour) Net Total Cooling Capacity (Btu/hour) Rated Airflow (Standard cubic feet per minute (SCFM)) Configuration (Downflow, Upflow Ducted, Upflow Non-Ducted, Horizontal Flow, Ceiling-Mounted Ducted, or Ceiling-Mounted Non-Ducted) Fluid Economizer Present? (Yes/No) Condenser Heat Rejection Medium (Air, Water, or Glycol-Cooled) Refrigerant Used to Determine the Represented Values Supplemental Testing Instructions PDF Filename




























Pop-Up Headers Status Manufacturer Brand Name(s) Basic Model Number Individual Model Number Ind. Model Number Outdoor Unit Private Model
Numbers?
Action Product Group Code Sample Size Certification Based on Waiver? Date of Waiver, if Applicable Cert. Based on Exception Relief? Date of Relief, if Applicable Certification Based on an AEDM? Name of AEDM, If Applicable Witness Test Option? Split System or Single Package? Net Sensible Coeff. of Perf. Net Sensible Cooling Capacity Net Total Cooling Capacity Rated Airflow Configuration Fluid Economizer Present? Condenser Heat Rejection Medium Refrigerant Used Testing Instructions Filename




























Pop-Up Contents The cells below show whether there are any issues with the data on that line. If the status is "ok," there are no issues. If the status is "Error," there are issues with the data. See columns to the right for an indication of the issues with the data. Enter the Manufacturer name in the cells below. Enter the Brand Name(s) in the cells below. Enter the Basic Model Number in the cells below. For single-package units, enter the Individual Model Number Covered by the Basic Model in the cells below.

For split-systems, enter the Indoor Unit Individual Model Number Covered by the Basic Model in the cells below.
For split-systems only, enter the Outdoor unit Individual Model Number Covered by the Basic Model in the cells below.

For single-package units, make no entry.



Enter whether any
Model Numbers
Have Been
Identified as
Private by the
Manufacturer in
the cells below.
See 10 CFR
429.7(b) for the
private model
number
requirements.

An affirmative
entry can be "yes"
or "y", and a
negative entry can
be "no" or "n".
Enter one of following in cells below:

N new model
ETO engineered to order
D discontinued model
C correction to previous CCMS submission
E submit report on existing (carryover) model
F failed Industry Certification Program





.
Enter an integer between 1 and 120 in the cells below.

See the Product Group Codes worksheet for details on product group codes.


Enter the sample size (number of units tested) in the cells below. If the answer to the AEDM question is yes, the entry should be 0, otherwise this should be an integer greater than zero. Answer whether the certification for the basic model was based on a waiver of DOE's test procedure requirements in the cells below.

An affirmative answer can be either 'yes' or 'y' and a negative answer can be either 'no' or 'n'.



.
If you enter 'yes' under "Is the certification for this basic model based on a waiver of DOE's test procedure requirements?", enter the date of the waiver in the cells below. The entry should be in the M/D/YYYY format.



.
Answer whether the certification was based upon any exception relief from an applicable standard by DOE's Office of Hearing and Appeals in the cells below.

An affirmative answer can be either 'yes' or 'y' and a negative answer can be either 'no' or 'n'.
If you enter 'yes' under "Is the certification based upon any exception relief from an applicable standard by DOE's Office of Hearing and Appeals?", enter the date of the exception relief in the cells below. The entry should be in the M/D/YYYY format. Answer whether the certification was based on the use of an Alternative Efficiency Determination Method in the cells below.

An affirmative answer can be either 'yes' or 'y' and a negative answer can be either 'no' or 'n'.
If you enter 'yes' under "Is Certification Based on the use of an Alternative Efficiency Determination Method (AEDM)?", enter the name of the AEDM in the cells below.


For basic models rated with an AEDM, answer whether the manufacturer elects the witness test option for verification testing in the cells below (max. 10% of basic models)

An affirmative answer can be 'yes' or 'y' and a negative answer can be 'no' or 'n'.
Enter whether the basic model is Split System or Single-Package in the cells below. An entry can be either "single-package" or "split system".



Enter the Net Sensible Coefficient of Performance (NSenCOP) in the cells below. This should be a decimal number greater than zero.


Enter the Net Sensible Cooling Capacity in Btu per hour in the cells below. This should be a decimal number greater than zero.


Enter the Net Total Cooling Capacity in Btu per hour in the cells below. This should be a decimal number greater than zero.


Enter the Rated Airflow in standard cubic feet per minute in the cells below. This should be a decimal number greater than zero.


Enter the Configuration in the cells below.

Entries can be as follows:

D = downflow
UD = upflow ducted
UN = upflow non-ducted
H = horizontal flow
CD = ceiling-mounted ducted
CN = ceiling-mounted non-ducted


.
Answer whether a Fluid Economizer is present in the model in the cells below.

An affirmative answer can be either 'yes' or 'y' and a negative answer can be either 'no' or 'n'.


Enter one of the following in the
cells below:

A = air-cooled
W = water-cooled
G = glycol-cooled


.
Enter the
refrigerant used to
determine the
represented values
in the cells below.
Entries should be
in the form of "R-"
followed by
numbers and/or
letters.
Enter the name of the PDF file containing supplemental testing instructions. See 429.43(b)(4) for req'd contents.

First 7 characters of the filename must be in the form of "DOExxxx" where "xxxx" is four-digit numerical code assigned to the manufacturer

Sheet 3: Product Group Code

The following is a description of each product group code:








Product Group Code Equipment Type Medium Net Sensible Cooling Capacity Range Configuration
1 Floor-Mounted Computer Room Air Conditioner Air-Cooled <80,000 Btu/h Downflow
2 Floor-Mounted Computer Room Air Conditioner Air-Cooled ≥80,000 Btu/h and <295,000 Btu/h Downflow
3 Floor-Mounted Computer Room Air Conditioner Air-Cooled ≥295,000 Btu/h and <930,000 Btu/h Downflow
4 Floor-Mounted Computer Room Air Conditioner Air-Cooled <80,000 Btu/h Upflow Ducted
5 Floor-Mounted Computer Room Air Conditioner Air-Cooled ≥80,000 Btu/h and <295,000 Btu/h Upflow Ducted
6 Floor-Mounted Computer Room Air Conditioner Air-Cooled ≥295,000 Btu/h and <930,000 Btu/h Upflow Ducted
7 Floor-Mounted Computer Room Air Conditioner Air-Cooled <65,000 Btu/h Upflow Non-Ducted
8 Floor-Mounted Computer Room Air Conditioner Air-Cooled ≥65,000 Btu/h and <240,000 Btu/h Upflow Non-Ducted
9 Floor-Mounted Computer Room Air Conditioner Air-Cooled ≥240,000 Btu/h and <760,000 Btu/h Upflow Non-Ducted
10 Floor-Mounted Computer Room Air Conditioner Air-Cooled <65,000 Btu/h Horizontal Flow
11 Floor-Mounted Computer Room Air Conditioner Air-Cooled ≥65,000 Btu/h and <240,000 Btu/h Horizontal Flow
12 Floor-Mounted Computer Room Air Conditioner Air-Cooled ≥240,000 Btu/h and <760,000 Btu/h Horizontal Flow
13 Floor-Mounted Computer Room Air Conditioner Air-Cooled with Fluid Economizer <80,000 Btu/h Downflow
14 Floor-Mounted Computer Room Air Conditioner Air-Cooled with Fluid Economizer ≥80,000 Btu/h and <295,000 Btu/h Downflow
15 Floor-Mounted Computer Room Air Conditioner Air-Cooled with Fluid Economizer ≥295,000 Btu/h and <930,000 Btu/h Downflow
16 Floor-Mounted Computer Room Air Conditioner Air-Cooled with Fluid Economizer <80,000 Btu/h Upflow Ducted
17 Floor-Mounted Computer Room Air Conditioner Air-Cooled with Fluid Economizer ≥80,000 Btu/h and <295,000 Btu/h Upflow Ducted
18 Floor-Mounted Computer Room Air Conditioner Air-Cooled with Fluid Economizer ≥295,000 Btu/h and <930,000 Btu/h Upflow Ducted
19 Floor-Mounted Computer Room Air Conditioner Air-Cooled with Fluid Economizer <65,000 Btu/h Upflow Non-Ducted
20 Floor-Mounted Computer Room Air Conditioner Air-Cooled with Fluid Economizer ≥65,000 Btu/h and <240,000 Btu/h Upflow Non-Ducted
21 Floor-Mounted Computer Room Air Conditioner Air-Cooled with Fluid Economizer ≥240,000 Btu/h and <760,000 Btu/h Upflow Non-Ducted
22 Floor-Mounted Computer Room Air Conditioner Air-Cooled with Fluid Economizer <65,000 Btu/h Horizontal Flow
23 Floor-Mounted Computer Room Air Conditioner Air-Cooled with Fluid Economizer ≥65,000 Btu/h and <240,000 Btu/h Horizontal Flow
24 Floor-Mounted Computer Room Air Conditioner Air-Cooled with Fluid Economizer ≥240,000 Btu/h and <760,000 Btu/h Horizontal Flow
25 Floor-Mounted Computer Room Air Conditioner Water-Cooled <80,000 Btu/h Downflow
26 Floor-Mounted Computer Room Air Conditioner Water-Cooled ≥80,000 Btu/h and <295,000 Btu/h Downflow
27 Floor-Mounted Computer Room Air Conditioner Water-Cooled ≥295,000 Btu/h and <930,000 Btu/h Downflow
28 Floor-Mounted Computer Room Air Conditioner Water-Cooled <80,000 Btu/h Upflow Ducted
29 Floor-Mounted Computer Room Air Conditioner Water-Cooled ≥80,000 Btu/h and <295,000 Btu/h Upflow Ducted
30 Floor-Mounted Computer Room Air Conditioner Water-Cooled ≥295,000 Btu/h and <930,000 Btu/h Upflow Ducted
31 Floor-Mounted Computer Room Air Conditioner Water-Cooled <65,000 Btu/h Upflow Non-Ducted
32 Floor-Mounted Computer Room Air Conditioner Water-Cooled ≥65,000 Btu/h and <240,000 Btu/h Upflow Non-Ducted
33 Floor-Mounted Computer Room Air Conditioner Water-Cooled ≥240,000 Btu/h and <760,000 Btu/h Upflow Non-Ducted
34 Floor-Mounted Computer Room Air Conditioner Water-Cooled <65,000 Btu/h Horizontal Flow
35 Floor-Mounted Computer Room Air Conditioner Water-Cooled ≥65,000 Btu/h and <240,000 Btu/h Horizontal Flow
36 Floor-Mounted Computer Room Air Conditioner Water-Cooled ≥240,000 Btu/h and <760,000 Btu/h Horizontal Flow
37 Floor-Mounted Computer Room Air Conditioner Water-Cooled with Fluid Economizer <80,000 Btu/h Downflow
38 Floor-Mounted Computer Room Air Conditioner Water-Cooled with Fluid Economizer ≥80,000 Btu/h and <295,000 Btu/h Downflow
39 Floor-Mounted Computer Room Air Conditioner Water-Cooled with Fluid Economizer ≥295,000 Btu/h and <930,000 Btu/h Downflow
40 Floor-Mounted Computer Room Air Conditioner Water-Cooled with Fluid Economizer <80,000 Btu/h Upflow Ducted
41 Floor-Mounted Computer Room Air Conditioner Water-Cooled with Fluid Economizer ≥80,000 Btu/h and <295,000 Btu/h Upflow Ducted
42 Floor-Mounted Computer Room Air Conditioner Water-Cooled with Fluid Economizer ≥295,000 Btu/h and <930,000 Btu/h Upflow Ducted
43 Floor-Mounted Computer Room Air Conditioner Water-Cooled with Fluid Economizer <65,000 Btu/h Upflow Non-Ducted
44 Floor-Mounted Computer Room Air Conditioner Water-Cooled with Fluid Economizer ≥65,000 Btu/h and <240,000 Btu/h Upflow Non-Ducted
45 Floor-Mounted Computer Room Air Conditioner Water-Cooled with Fluid Economizer ≥240,000 Btu/h and <760,000 Btu/h Upflow Non-Ducted
46 Floor-Mounted Computer Room Air Conditioner Water-Cooled with Fluid Economizer <65,000 Btu/h Horizontal Flow
47 Floor-Mounted Computer Room Air Conditioner Water-Cooled with Fluid Economizer ≥65,000 Btu/h and <240,000 Btu/h Horizontal Flow
48 Floor-Mounted Computer Room Air Conditioner Water-Cooled with Fluid Economizer ≥240,000 Btu/h and <760,000 Btu/h Horizontal Flow
49 Floor-Mounted Computer Room Air Conditioner Glycol-Cooled <80,000 Btu/h Downflow
50 Floor-Mounted Computer Room Air Conditioner Glycol-Cooled ≥80,000 Btu/h and <295,000 Btu/h Downflow
51 Floor-Mounted Computer Room Air Conditioner Glycol-Cooled ≥295,000 Btu/h and <930,000 Btu/h Downflow
52 Floor-Mounted Computer Room Air Conditioner Glycol-Cooled <80,000 Btu/h Upflow Ducted
53 Floor-Mounted Computer Room Air Conditioner Glycol-Cooled ≥80,000 Btu/h and <295,000 Btu/h Upflow Ducted
54 Floor-Mounted Computer Room Air Conditioner Glycol-Cooled ≥295,000 Btu/h and <930,000 Btu/h Upflow Ducted
55 Floor-Mounted Computer Room Air Conditioner Glycol-Cooled <65,000 Btu/h Upflow Non-Ducted
56 Floor-Mounted Computer Room Air Conditioner Glycol-Cooled ≥65,000 Btu/h and <240,000 Btu/h Upflow Non-Ducted
57 Floor-Mounted Computer Room Air Conditioner Glycol-Cooled ≥240,000 Btu/h and <760,000 Btu/h Upflow Non-Ducted
58 Floor-Mounted Computer Room Air Conditioner Glycol-Cooled <65,000 Btu/h Horizontal Flow
59 Floor-Mounted Computer Room Air Conditioner Glycol-Cooled ≥65,000 Btu/h and <240,000 Btu/h Horizontal Flow
60 Floor-Mounted Computer Room Air Conditioner Glycol-Cooled ≥240,000 Btu/h and <760,000 Btu/h Horizontal Flow
61 Floor-Mounted Computer Room Air Conditioner Glycol-Cooled with Fluid Economizer <80,000 Btu/h Downflow
62 Floor-Mounted Computer Room Air Conditioner Glycol-Cooled with Fluid Economizer ≥80,000 Btu/h and <295,000 Btu/h Downflow
63 Floor-Mounted Computer Room Air Conditioner Glycol-Cooled with Fluid Economizer ≥295,000 Btu/h and <930,000 Btu/h Downflow
64 Floor-Mounted Computer Room Air Conditioner Glycol-Cooled with Fluid Economizer <80,000 Btu/h Upflow Ducted
65 Floor-Mounted Computer Room Air Conditioner Glycol-Cooled with Fluid Economizer ≥80,000 Btu/h and <295,000 Btu/h Upflow Ducted
66 Floor-Mounted Computer Room Air Conditioner Glycol-Cooled with Fluid Economizer ≥295,000 Btu/h and <930,000 Btu/h Upflow Ducted
67 Floor-Mounted Computer Room Air Conditioner Glycol-Cooled with Fluid Economizer <65,000 Btu/h Upflow Non-Ducted
68 Floor-Mounted Computer Room Air Conditioner Glycol-Cooled with Fluid Economizer ≥65,000 Btu/h and <240,000 Btu/h Upflow Non-Ducted
69 Floor-Mounted Computer Room Air Conditioner Glycol-Cooled with Fluid Economizer ≥240,000 Btu/h and <760,000 Btu/h Upflow Non-Ducted
70 Floor-Mounted Computer Room Air Conditioner Glycol-Cooled with Fluid Economizer <65,000 Btu/h Horizontal Flow
71 Floor-Mounted Computer Room Air Conditioner Glycol-Cooled with Fluid Economizer ≥65,000 Btu/h and <240,000 Btu/h Horizontal Flow
72 Floor-Mounted Computer Room Air Conditioner Glycol-Cooled with Fluid Economizer ≥240,000 Btu/h and <760,000 Btu/h Horizontal Flow
73 Ceiling-Mounted Computer Room Air Conditioner Air-Cooled with Free Air Discharge Condenser <29,000 Btu/h Ducted
74 Ceiling-Mounted Computer Room Air Conditioner Air-Cooled with Free Air Discharge Condenser ≥29,000 Btu/h and <65,000 Btu/h Ducted
75 Ceiling-Mounted Computer Room Air Conditioner Air-Cooled with Free Air Discharge Condenser ≥65,000 Btu/h Ducted
76 Ceiling-Mounted Computer Room Air Conditioner Air-Cooled with Free Air Discharge Condenser <29,000 Btu/h Non-Ducted
77 Ceiling-Mounted Computer Room Air Conditioner Air-Cooled with Free Air Discharge Condenser ≥29,000 Btu/h and <65,000 Btu/h Non-Ducted
78 Ceiling-Mounted Computer Room Air Conditioner Air-Cooled with Free Air Discharge Condenser ≥65,000 Btu/h Non-Ducted
79 Ceiling-Mounted Computer Room Air Conditioner Air-Cooled with Free Air Discharge Condenser and Fluid Economizer <29,000 Btu/h Ducted
80 Ceiling-Mounted Computer Room Air Conditioner Air-Cooled with Free Air Discharge Condenser and Fluid Economizer ≥29,000 Btu/h and <65,000 Btu/h Ducted
81 Ceiling-Mounted Computer Room Air Conditioner Air-Cooled with Free Air Discharge Condenser and Fluid Economizer ≥65,000 Btu/h Ducted
82 Ceiling-Mounted Computer Room Air Conditioner Air-Cooled with Free Air Discharge Condenser and Fluid Economizer <29,000 Btu/h Non-Ducted
83 Ceiling-Mounted Computer Room Air Conditioner Air-Cooled with Free Air Discharge Condenser and Fluid Economizer ≥29,000 Btu/h and <65,000 Btu/h Non-Ducted
84 Ceiling-Mounted Computer Room Air Conditioner Air-Cooled with Free Air Discharge Condenser and Fluid Economizer ≥65,000 Btu/h Non-Ducted
85 Ceiling-Mounted Computer Room Air Conditioner Air-Cooled with Ducted Condenser <29,000 Btu/h Ducted
86 Ceiling-Mounted Computer Room Air Conditioner Air-Cooled with Ducted Condenser ≥29,000 Btu/h and <65,000 Btu/h Ducted
87 Ceiling-Mounted Computer Room Air Conditioner Air-Cooled with Ducted Condenser ≥65,000 Btu/h Ducted
88 Ceiling-Mounted Computer Room Air Conditioner Air-Cooled with Ducted Condenser <29,000 Btu/h Non-Ducted
89 Ceiling-Mounted Computer Room Air Conditioner Air-Cooled with Ducted Condenser ≥29,000 Btu/h and <65,000 Btu/h Non-Ducted
90 Ceiling-Mounted Computer Room Air Conditioner Air-Cooled with Ducted Condenser ≥65,000 Btu/h Non-Ducted
91 Ceiling-Mounted Computer Room Air Conditioner Air-Cooled with Fluid Economizer and Ducted Condenser <29,000 Btu/h Ducted
92 Ceiling-Mounted Computer Room Air Conditioner Air-Cooled with Fluid Economizer and Ducted Condenser ≥29,000 Btu/h and <65,000 Btu/h Ducted
93 Ceiling-Mounted Computer Room Air Conditioner Air-Cooled with Fluid Economizer and Ducted Condenser ≥65,000 Btu/h Ducted
94 Ceiling-Mounted Computer Room Air Conditioner Air-Cooled with Fluid Economizer and Ducted Condenser <29,000 Btu/h Non-Ducted
95 Ceiling-Mounted Computer Room Air Conditioner Air-Cooled with Fluid Economizer and Ducted Condenser ≥29,000 Btu/h and <65,000 Btu/h Non-Ducted
96 Ceiling-Mounted Computer Room Air Conditioner Air-Cooled with Fluid Economizer and Ducted Condenser ≥65,000 Btu/h Non-Ducted
97 Ceiling-Mounted Computer Room Air Conditioner Water-Cooled <29,000 Btu/h Ducted
98 Ceiling-Mounted Computer Room Air Conditioner Water-Cooled ≥29,000 Btu/h and <65,000 Btu/h Ducted
99 Ceiling-Mounted Computer Room Air Conditioner Water-Cooled ≥65,000 Btu/h Ducted
100 Ceiling-Mounted Computer Room Air Conditioner Water-Cooled <29,000 Btu/h Non-Ducted
101 Ceiling-Mounted Computer Room Air Conditioner Water-Cooled ≥29,000 Btu/h and <65,000 Btu/h Non-Ducted
102 Ceiling-Mounted Computer Room Air Conditioner Water-Cooled ≥65,000 Btu/h Non-Ducted
103 Ceiling-Mounted Computer Room Air Conditioner Water-Cooled with Fluid Economizer <29,000 Btu/h Ducted
104 Ceiling-Mounted Computer Room Air Conditioner Water-Cooled with Fluid Economizer ≥29,000 Btu/h and <65,000 Btu/h Ducted
105 Ceiling-Mounted Computer Room Air Conditioner Water-Cooled with Fluid Economizer ≥65,000 Btu/h Ducted
106 Ceiling-Mounted Computer Room Air Conditioner Water-Cooled with Fluid Economizer <29,000 Btu/h Non-Ducted
107 Ceiling-Mounted Computer Room Air Conditioner Water-Cooled with Fluid Economizer ≥29,000 Btu/h and <65,000 Btu/h Non-Ducted
108 Ceiling-Mounted Computer Room Air Conditioner Water-Cooled with Fluid Economizer ≥65,000 Btu/h Non-Ducted
109 Ceiling-Mounted Computer Room Air Conditioner Glycol-Cooled <29,000 Btu/h Ducted
110 Ceiling-Mounted Computer Room Air Conditioner Glycol-Cooled ≥29,000 Btu/h and <65,000 Btu/h Ducted
111 Ceiling-Mounted Computer Room Air Conditioner Glycol-Cooled ≥65,000 Btu/h Ducted
112 Ceiling-Mounted Computer Room Air Conditioner Glycol-Cooled <29,000 Btu/h Non-Ducted
113 Ceiling-Mounted Computer Room Air Conditioner Glycol-Cooled ≥29,000 Btu/h and <65,000 Btu/h Non-Ducted
114 Ceiling-Mounted Computer Room Air Conditioner Glycol-Cooled ≥65,000 Btu/h Non-Ducted
115 Ceiling-Mounted Computer Room Air Conditioner Glycol-Cooled with Fluid Economizer <29,000 Btu/h Ducted
116 Ceiling-Mounted Computer Room Air Conditioner Glycol-Cooled with Fluid Economizer ≥29,000 Btu/h and <65,000 Btu/h Ducted
117 Ceiling-Mounted Computer Room Air Conditioner Glycol-Cooled with Fluid Economizer ≥65,000 Btu/h Ducted
118 Ceiling-Mounted Computer Room Air Conditioner Glycol-Cooled with Fluid Economizer <29,000 Btu/h Non-Ducted
119 Ceiling-Mounted Computer Room Air Conditioner Glycol-Cooled with Fluid Economizer ≥29,000 Btu/h and <65,000 Btu/h Non-Ducted
120 Ceiling-Mounted Computer Room Air Conditioner Glycol-Cooled with Fluid Economizer ≥65,000 Btu/h Non-Ducted