Stata

CFR-2008-title46-vol1-sec25-30-20.pdf

Certificates of Compliance, Boiler/Pressure Vessel Repairs, Cargo Gear Records, Shipping Papers, and NFPA 10 Certificates

Stata

OMB: 1625-0037

Document [pdf]
Download: pdf | pdf
Coast Guard, DHS

§ 25.30–20

TABLE 25.30–10(C)—Continued
Classification

dwashington3 on PRODPC61 with CFR

B-V ...............

Foam,
liters
(gallons)

Carbon dioxide,
kilograms
(pounds)

Dry chemical,
kilograms
(pounds)

45 (100)

23 (50)

150 (40)

(d) All hand portable fire extinguishers and semiportable fire extinguishing systems shall have permanently attached thereto a metallic
name plate giving the name of the
item, the rated capacity in gallons,
quarts, or pounds, the name and address of the person or firm for whom
approved, and the identifying mark of
the actual manufacturer.
(e) Vaporizing-liquid type fire extinguishers containing carbon tetrachloride or chlorobromomethane or
other toxic vaporizing liquids are not
acceptable as equipment required by
this subchapter.
(f) Hand portable or semiportable extinguishers which are required on their
name plates to be protected from freezing shall not be located where freezing
temperatures may be expected.
(g) The use of dry chemical, stored
pressure, fire extinguishers not fitted
with pressure gauges or indicating devices, manufactured prior to January 1,
1965, may be permitted on motorboats
and other vessels so long as such extinguishers are maintained in good and
serviceable condition. The following
maintenance and inspections are required for such extinguishers:
(1) When the date on the inspection
record tag on the extinguishers shows
that 6 months have elapsed since last
weight check ashore, then such extinguisher is no longer accepted as meeting required maintenance conditions
until reweighed ashore and found to be
in a serviceable condition and within
required weight conditions.
(2) If the weight of the container is 1⁄4
ounce less than that stamped on container, it shall be serviced.
(3) If the outer seal or seals (which
indicate tampering or use when broken) are not intact, the boarding officer or marine inspector will inspect
such extinguisher to see that the frangible disc in neck of the container is
intact; and if such disc is not intact,
the container shall be serviced.
(4) If there is evidence of damage,
use, or leakage, such as dry chemical

powder observed in the nozzle or elsewhere on the extinguisher, the container shall be replaced with a new one
and the extinguisher properly serviced
or the extinguisher replaced with another approved extinguisher.
(h) The dry chemical, stored pressure, fire extinguishers without pressure gauges or indicating devices manufactured after January 1, 1965, shall
not be labeled with the marine type
label bed in § 162.028–4 of this title nor
shall such extinguishers manufactured
after January 1, 1965, be carried on
board motorboats or other vessels as
required equipment.
[CGFR 65–50, 30 FR 16653, Dec. 30, 1965, as
amended by CGFR 68–32, 33 FR 5711, Apr. 12,
1968; CGFR 69–18, 34 FR 5723, Mar. 27, 1969;
USCG-2000–6931, 68 FR 22611, Apr. 29, 2003; 69
FR 34068, June 18, 2004]

§ 25.30–15
tems.

Fixed fire-extinguishing sys-

(a) When a fixed fire-extinguishing
system is installed, it must be a type
approved or accepted by the Commandant (G-MSE) or the Commanding
Officer, U.S. Coast Guard Marine Safety Center.
(b) If the system is a carbon-dioxide
type, then it must be designed and installed in accordance with subpart 76.15
of part 76 of subchapter H (Passenger
Vessels) of this chapter.
[USCG-2000–6931, 69 FR 34069, June 18, 2004]

§ 25.30–20 Fire extinguishing
ment required.

(a) Motorboats. (1) All motorboats
shall carry at least the minimum number of hand portable fire extinguishers
set forth in Table 25.30–20(a)(1), except
that motorboats less than 26 feet in
length, propelled by outboard motors
and not carrying passengers for hire,
need not carry such portable fire extinguishers if the construction of such
motorboats will not permit the entrapment of explosive or flammable gases
or vapors.

315

VerDate Aug<31>2005

09:15 Oct 31, 2008

Jkt 214188

PO 00000

Frm 00325

Fmt 8010

equip-

Sfmt 8010

Y:\SGML\214188.XXX

214188

§ 25.30–20

46 CFR Ch. I (10–1–08 Edition)
3. Buoyant flotation material.
4. Open slatted flooring.
5. Ice chests.

TABLE 25.30–20(a)(1)

No fixed fire
extinguishing
system in machinery space

Fixed fire
extinguishing
system in machinery space

1
1
2

0
0
1

3

2

Under 16 ............................
16 and over, but under 26
26 and over, but under 40
40 and over, but not over
65 ...................................
1 One

B-11 hand portable fire extinguisher may be substituted for two B-I hand portable fire extinguishers.

(2) The intent of this regulation is illustrated in Figure 25.30–20(a1) where
fire extinguishers are required if any
one or more of the specified conditions
exist, and in Figure 25.30–20(a2) where
specified conditions do not, in themselves, require that fire extinguishers
be carried.

dwashington3 on PRODPC61 with CFR

FIGURE 25.30–20(A1)
Fire extinguishers are required if any one
or more of the following conditions exist
(numbers identifying conditions are the
same as those placed in Figure 25.30–20 (a1)):
1. Closed compartment under thwarts and
seats wherein portable fuel tanks may be
stored.
2. Double bottoms not sealed to the hull or
which are not completely filled with flotation material.
3. Close living spaces.
4. Closed stowage compartments in which
combustible or flammable materials are
stowed.
5. Permanently installed fuel tanks.

FIGURE 25.30–20(A2)
The following conditions do not, in themselves, require that fire extinguishers be carried (numbers identifying conditions are the
same as those placed in Figure 25.30–20(a2)):
1. Bait wells.
2. Glove compartments.

(b) Uninspected passenger vessels of at
least 100 gross tons. All uninspected passenger vessels of at least 100 gross tons
must carry onboard hand-portable and
semi-portable fire extinguishers per
Table 76.50–10(a) in § 76.50–10 of this
chapter.
(c) Motor vessels. (1) All motor vessels
shall carry at least the minimum number of hand portable fire extinguishers
set forth in Table 25.30–20(b) (1).
TABLE 25.30–20(b)(1)
Gross tonnage—
Over

Not over

Minimum number of B-II hand portable fire extinguishers

..................
50 .............
100 ...........
500 ...........
1,000 ........

50
100
500
1,000
................

1
2
3
6
8

(2) In addition to the hand portable
fire extinguishers required by paragraph (b)(1) of this section, the following fire-extinguishing equipment
shall be fitted in the machinery space:
(i) One Type B-II hand portable fire
extinguisher shall be carried for each
1,000 B. H. P. of the main engines or
fraction thereof. However, not more
than 6 such extinguishers need be carried.
(ii) On motor vessels of over 300 gross
tons,
either
one
Type
B-III
semiportable fire-extinguishing system
shall be fitted, or alternatively, a fixed
fire-extinguishing system shall be
fitted in the machinery space.
(3) The frame or support of each Type
B-III fire extinguisher required by
paragraph (b)(2)(ii) of this section must
be welded or otherwise permanently attached to a bulkhead or deck.
(4) If an approved semiportable fire
extinguisher has wheels and is not required by this section, it must be securely stowed when not in use to prevent it from rolling out of control
under heavy sea conditions.
(d) Barges carrying passengers. (1)
Every barge of 65 feet in length or less
while carrying passengers when towed
or pushed by a motorboat, motor vessel, or steam vessel shall be fitted with
EC01FE91.067

Length, feet

316

VerDate Aug<31>2005

09:15 Oct 31, 2008

Jkt 214188

PO 00000

Frm 00326

Fmt 8010

Sfmt 8010

Y:\SGML\214188.XXX

214188

EC01FE91.066

Minimum number of B-1 hand
portable fire extinguishers
required 1

Coast Guard, DHS

§ 25.40–1

hand portable fire extinguishers as required by Table 25.30–20(a)(1), depending upon the length of the barge.
(2) Every barge of over 65 feet in
length while carrying passengers when
towed or pushed by a motorboat, motor
vessel, or steam vessel shall be fitted
with hand portable fire extinguishers
as required by Table 25.30–20(b)(1), depending upon the gross tonnage of the
barge.
[CGFR 65–50, 30 FR 16653, Dec. 30, 1965, as
amended by CGD 77–039, 44 FR 34132, June 14,
1979; CGD 97–057, 62 FR 51042, Sept. 30, 1997;
USCG-1999–5040, 67 FR 34776, May 15, 2002]

§ 25.30–90 Vessels contracted for prior
to November 19, 1952.
(a) Vessels contracted for prior to
November 19, 1952, shall meet the applicable provisions of §§ 25.30–5 through
25.30–20 insofar as the number and general type of equipment is concerned.
Existing items of equipment and installations previously approved but not
meeting the applicable requirements
for type approval may be continued in
service so long as they are in good condition. All new installations and replacements shall meet the requirements of §§ 25.30–5 through 25.30–20.
(b) [Reserved]

Subpart 25.35—Backfire Flame
Control

dwashington3 on PRODPC61 with CFR

§ 25.35–1

Requirements.

(a) Every gasoline engine installed in
a motorboat or motor vessel after April
25, 1940, except outboard motors, shall
be equipped with an acceptable means
of backfire flame control.
(b) Installations made before November 19, 1952, need not meet the detailed
requirements of this subpart and may
be continued in use as long as they are
serviceable and in good condition. Replacements shall meet the applicable
conditions in this section.
(c) Installations consisting of backfire flame arresters bearing basic Approval Nos. 162.015 or 162.041 or engine
air and fuel induction systems bearing
basic Approval Nos. 162.015 or 162.042
may be continued in use as long as
they are serviceable and in good condition. New installations or replacements

must meet applicable requirements of
subpart 58.10 of this chapter.
[CGFR 65–50, 30 FR 16653, Dec. 30, 1965, as
amended by CGD 88–032, 56 FR 35820, July 29,
1991]

Subpart 25.40—Ventilation
§ 25.40–1 Tanks and engine spaces.
(a) All motorboats or motor vessels,
except open boats and as provided in
paragraphs (d) and (e) of this section,
the construction or decking over of
which is commenced after April 25,
1940, and which use fuel having a
flashpoint of 110° F., or less, shall have
at least two ventilator ducts, fitted
with cowls or their equivalent, for the
efficient removal of explosive or flammable gases from the bilges of every
engine and fuel tank compartment.
There shall be at least one exhaust
duct installed so as to extend from the
open atmosphere to the lower portion
of the bilge and at least one intake
duct installed so as to extend to a
point at least midway to the bilge or at
least below the level of the carburetor
air intake. The cowls shall be located
and trimmed for maximum effectiveness and in such a manner so as to prevent displaced fumes from being recirculated.
(b) As used in this section, the term
open boats means those motorboats or
motor vessels with all engine and fuel
tank compartments, and other spaces
to which explosive or flammable gases
and vapors from these compartments
may flow, open to the atmosphere and
so arranged as to prevent the entrapment of such gases and vapors within
the vessel.
(c) Boats built after July 31, 1980,
which are manufactured or used primarily for noncommercial use; which
are leased, rented, or chartered to another for the latter’s noncommercial
use; which are engaged in the carriage
of six or fewer passengers; or which are
in compliance with the requirements of
33 CFR part 183 are exempted from
these requirements.
(d) Boats built after July 31, 1978,
which are manufactured or used primarily for noncommercial use; which
are rented, leased, or chartered to another for the latter’s noncommercial
use; or which engage in conveying six

317

VerDate Aug<31>2005

09:15 Oct 31, 2008

Jkt 214188

PO 00000

Frm 00327

Fmt 8010

Sfmt 8010

Y:\SGML\214188.XXX

214188


File Typeapplication/pdf
File Modified2014-09-30
File Created2014-09-30

© 2024 OMB.report | Privacy Policy