StatA

CFR-2002-title46-vol1-part25.30-10.pdf

Certificates of Compliance, Boiler/Pressure Vessel Repairs, Cargo Gear Records, Shipping Papers, and NFPA 10 Certificates

StatA

OMB: 1625-0037

Document [pdf]
Download: pdf | pdf
Coast Guard, DOT
§ 25.26–50

§ 25.30–10

[CGD 87–016a, 58 FR 13367, Mar. 10, 1993; 58 FR
27658, May 11, 1993]

§ 25.26–60

Subpart 25.30—Fire Extinguishing
Equipment

Servicing of EPIRBs.

(a) The master of each vessel required to have an EPIRB under this
subpart shall ensure that each EPIRB
on board is tested and serviced as required by this section.
(b) The EPIRB must be tested immediately after installation and at least
once each month thereafter, unless it
is an EPIRB installed in a Coast Guard
approved inflatable liferaft that is tested annually during the servicing of the
liferaft by an approved servicing facility. The test shall be conducted in accordance with the manufacturer’s instructions, using the visual or audio indicator on the EPIRB. If the EPIRB is
not operating, it must be repaired or
replaced with an operating EPIRB.
(c) The battery of the EPIRB must be
replaced—
(1) Immediately after the EPIRB is
used for any purpose other than being
tested; and
(2) Before the expiration date that is
marked on the battery.

Exemptions.

(a) A skiff or work boat is not required to carry an EPIRB if—
(1) Its ‘‘mother ship’’ is required to
carry an EPIRB under this subpart;
and
(2) When not in use, the skiff or work
boat is carried on board the mother
ship.
(b) Each Coast Guard District Commander may, on a case-by-case basis,
grant exemptions from the carriage requirements of EPIRBs in this subpart
for certain geographic areas within the
boundaries of his or her own district if
the District Commander determines
that an EPIRB will not significantly
enhance the overall safety of the vessel
and crew. Exemptions may be limited
to specific time periods. Exemptions
granted under this paragraph must be:
(1) Issued in writing by the cognizant
Coast Guard District Commander for
each individual application; and
(2) For geographic locations and may
be limited to specific time periods.

§ 25.30–1 Application.
(a) The provisions of this subpart,
with the exception of § 25.30–90, shall
apply to all vessels contracted for on or
after November 19, 1952. Vessels contracted for prior to that date shall
meet the requirements of § 25.30–90.
§ 25.30–5 General provisions.
(a) Where equipment in this subpart
is required to be of an approved type,
such equipment requires the specific
approval of the Commandant. Such approvals are published in the FEDERAL
REGISTER, and in addition, are contained in Coast Guard publication
COMDTINST M16714.3 (Series), Equipment Lists.
(b) All hand portable fire extinguishers, semiportable fire extinguishing systems, and fixed fire extinguishing systems shall be of an approved type.
[CGFR 65–50, 30 FR 16653, Dec. 30, 1965, as
amended by CGD 96–041, 61 FR 50726, Sept. 27,
1996]

§ 25.30–10 Hand portable fire extinguishers and semiportable fire extinguishing systems.
(a) Hand portable fire extinguishers
and semiportable fire extinguishing
systems are classified by a combination letter and number symbol. The
letter indicating the type of fire which
the unit could be expected to extinguish, and the number indicating the
relative size of the unit.
(b) For the purpose of this subchapter, all required hand portable fire
extinguishers and semiportable fire extinguishing systems are of the ‘‘B’’
type; i.e., suitable for extinguishing
fires involving flammable liquids,
greases, etc.
(c) The number designations for size
will start with ‘‘I’’ for the smallest to
‘‘V’’ for the largest. For the purpose of
this subchapter, only sizes I through
III will be considered. Sizes I and II are
considered hand portable fire extinguishers and sizes III, IV, and V are
considered semiportable fire extinguishing systems which shall be fitted
with suitable hose and nozzle or other
practicable means so that all portions

317

VerDate 0ct<02>2002

14:50 Oct 10, 2002

Jkt 197179

PO 00000

Frm 00317

Fmt 8010

Sfmt 8010

Y:\SGML\197179T.XXX

197179T

§ 25.30–15

46 CFR Ch. I (10–1–02 Edition)

of the space concerned may be covered.
Examples of size graduations for some
of the typical hand portable fire extinguishers and semiportable fire extinguishing systems are set forth in Table
25.30–10(c).
TABLE 25.30–10(c)
Classification
Type

Size

B ...........
B ...........
B ...........

I .............
II ............
III ...........

Foam, gallons

Carbon Dioxide,
pounds

Dry chemical,
pounds

13⁄4
21⁄2
12

4
15
35

2
10
20

(d) All hand portable fire extinguishers and semiportable fire extinguishing systems shall have permanently attached thereto a metallic
name plate giving the name of the
item, the rated capacity in gallons,
quarts, or pounds, the name and address of the person or firm for whom
approved, and the identifying mark of
the actual manufacturer.
(e) Vaporizing-liquid type fire extinguishers containing carbon tetrachloride or chlorobromomethane or
other toxic vaporizing liquids are not
acceptable as equipment required by
this subchapter.
(f) Hand portable or semiportable extinguishers which are required on their
name plates to be protected from freezing shall not be located where freezing
temperatures may be expected.
(g) The use of dry chemical, stored
pressure, fire extinguishers not fitted
with pressure gauges or indicating devices, manufactured prior to January 1,
1965, may be permitted on motorboats
and other vessels so long as such extinguishers are maintained in good and
serviceable condition. The following
maintenance and inspections are required for such extinguishers:
(1) When the date on the inspection
record tag on the extinguishers shows
that 6 months have elapsed since last
weight check ashore, then such extinguisher is no longer accepted as meeting required maintenance conditions
until reweighed ashore and found to be
in a serviceable condition and within
required weight conditions.

(2) If the weight of the container is 1⁄4
ounce less than that stamped on container, it shall be serviced.
(3) If the outer seal or seals (which
indicate tampering or use when broken) are not intact, the boarding officer or marine inspector will inspect
such extinguisher to see that the frangible disc in neck of the container is
intact; and if such disc is not intact,
the container shall be serviced.
(4) If there is evidence of damage,
use, or leakage, such as dry chemical
powder observed in the nozzle or elsewhere on the extinguisher, the container shall be replaced with a new one
and the extinguisher properly serviced
or the extinguisher replaced with another approved extinguisher.
(h) The dry chemical, stored pressure, fire extinguishers without pressure gauges or indicating devices manufactured after January 1, 1965, shall
not be labeled with the marine type
label bed in § 162.028–4 of this title nor
shall such extinguishers manufactured
after January 1, 1965, be carried on
board motorboats or other vessels as
required equipment.
[CGFR 65–50, 30 FR 16653, Dec. 30, 1965, as
amended by CGFR 68–32, 33 FR 5711, Apr. 12,
1968; CGFR 69–18, 34 FR 5723, Mar. 27, 1969]

§ 25.30–15 Fixed fire extinguishing systems.
(a) When a fixed fire extinguishing
system is installed, it shall be of an approved carbon dioxide type, designed
and installed in agreement with the applicable provisions of subpart 76.15 of
subchapter H (Passenger Vessels) of
this chapter.
§ 25.30–20 Fire extinguishing equipment required.
(a) Motorboats. (1) All motorboats
shall carry at least the minimum number of hand portable fire extinguishers
set forth in Table 25.30–20(a)(1), except
that motorboats less than 26 feet in
length, propelled by outboard motors
and not carrying passengers for hire,
need not carry such portable fire extinguishers if the construction of such
motorboats will not permit the entrapment of explosive or flammable gases
or vapors.

318

VerDate 0ct<02>2002

14:50 Oct 10, 2002

Jkt 197179

PO 00000

Frm 00318

Fmt 8010

Sfmt 8010

Y:\SGML\197179T.XXX

197179T

Coast Guard, DOT

§ 25.30–20

Length, feet

No
fixed
fire extinguishing
system
in machinery
space

Fixed
fire extinguishing
system
in machinery
space

1
1
2
3

0
0
1
2

Under 16 ....................................................
16 and over, but under 26 ........................
26 and over, but under 40 ........................
40 and over, but not over 65 ....................

1 One B–11 hand portable fire extinguisher may be substituted for two B–I hand portable fire extinguishers.

(2) The intent of this regulation is illustrated in Figure 25.30–20(a1) where
fire extinguishers are required if any
one or more of the specified conditions
exist, and in Figure 25.30–20(a2) where
specified conditions do not, in themselves, require that fire extinguishers
be carried.

FIGURE 25.30–20(A1)
Fire extinguishers are required if any one
or more of the following conditions exist
(numbers identifying conditions are the
same as those placed in Figure 25.30–20 (a1)):
1. Closed compartment under thwarts and
seats wherein portable fuel tanks may be
stored.
2. Double bottoms not sealed to the hull or
which are not completely filled with flotation material.
3. Close living spaces.
4. Closed stowage compartments in which
combustible or flammable materials are
stowed.
5. Permanently installed fuel tanks.

FIGURE 25.30–20(A2)

(b) Uninspected passenger vessels of at
least 100 gross tons. All uninspected passenger vessels of at least 100 gross tons
must carry onboard hand-portable and
semi-portable fire extinguishers per
Table 76.50–10(a) in § 76.50–10 of this
chapter.
(c) Motor vessels. (1) All motor vessels
shall carry at least the minimum number of hand portable fire extinguishers
set forth in Table 25.30–20(b) (1).
TABLE 25.30–20(b)(1)
Gross tonnage—
Over

Not over

Minimum number of B–II hand
portable fire extinguishers

..................
50 .............
100 ...........
500 ...........
1,000 ........

50
100
500
1,000
................

1
2
3
6
8

(2) In addition to the hand portable
fire extinguishers required by paragraph (b)(1) of this section, the following fire-extinguishing equipment
shall be fitted in the machinery space:
(i) One Type B–II hand portable fire
extinguisher shall be carried for each
1,000 B. H. P. of the main engines or
fraction thereof. However, not more
than 6 such extinguishers need be carried.
(ii) On motor vessels of over 300 gross
tons,
either
one
Type
B–III
semiportable fire-extinguishing system
shall be fitted, or alternatively, a fixed
fire-extinguishing system shall be
fitted in the machinery space.
(3) The frame or support of each Type
B–III fire extinguisher required by
paragraph (b)(2)(ii) of this section must
be welded or otherwise permanently attached to a bulkhead or deck.
(4) If an approved semiportable fire
extinguisher has wheels and is not required by this section, it must be securely stowed when not in use to prevent it from rolling out of control
under heavy sea conditions.
(d) Barges carrying passengers. (1)
Every barge of 65 feet in length or less
EC01FE91.067

Minimum number of B–1 hand
portable fire extinguishers required 1

The following conditions do not, in themselves, require that fire extinguishers be carried (numbers identifying conditions are the
same as those placed in Figure 25.30–20(a2)):
1. Bait wells.
2. Glove compartments.
3. Buoyant flotation material.
4. Open slatted flooring.
5. Ice chests.

319

VerDate 0ct<02>2002

14:50 Oct 10, 2002

Jkt 197179

PO 00000

Frm 00319

Fmt 8010

Sfmt 8010

Y:\SGML\197179T.XXX

197179T

EC01FE91.066

TABLE 25.30–20(a)(1)

§ 25.30–90

46 CFR Ch. I (10–1–02 Edition)

while carrying passengers when towed
or pushed by a motorboat, motor vessel, or steam vessel shall be fitted with
hand portable fire extinguishers as required by Table 25.30–20(a)(1), depending upon the length of the barge.
(2) Every barge of over 65 feet in
length while carrying passengers when
towed or pushed by a motorboat, motor
vessel, or steam vessel shall be fitted
with hand portable fire extinguishers
as required by Table 25.30–20(b)(1), depending upon the gross tonnage of the
barge.
[CGFR 65–50, 30 FR 16653, Dec. 30, 1965, as
amended by CGD 77–039, 44 FR 34132, June 14,
1979; CGD 97–057, 62 FR 51042, Sept. 30, 1997;
USCG–1999–5040, 67 FR 34776, May 15, 2002]

§ 25.30–90 Vessels contracted for prior
to November 19, 1952.
(a) Vessels contracted for prior to
November 19, 1952, shall meet the applicable provisions of §§ 25.30–5 through
25.30–20 insofar as the number and general type of equipment is concerned.
Existing items of equipment and installations previously approved but not
meeting the applicable requirements
for type approval may be continued in
service so long as they are in good condition. All new installations and replacements shall meet the requirements of §§ 25.30–5 through 25.30–20.
(b) [Reserved]

Subpart 25.35—Backfire Flame
Control
§ 25.35–1 Requirements.
(a) Every gasoline engine installed in
a motorboat or motor vessel after April
25, 1940, except outboard motors, shall
be equipped with an acceptable means
of backfire flame control.
(b) Installations made before November 19, 1952, need not meet the detailed
requirements of this subpart and may
be continued in use as long as they are
serviceable and in good condition. Replacements shall meet the applicable
conditions in this section.
(c) Installations consisting of backfire flame arresters bearing basic Approval Nos. 162.015 or 162.041 or engine
air and fuel induction systems bearing
basic Approval Nos. 162.015 or 162.042
may be continued in use as long as
they are serviceable and in good condi-

tion. New installations or replacements
must meet applicable requirements of
subpart 58.10 of this chapter.
[CGFR 65–50, 30 FR 16653, Dec. 30, 1965, as
amended by CGD 88–032, 56 FR 35820, July 29,
1991]

Subpart 25.40—Ventilation
§ 25.40–1 Tanks and engine spaces.
(a) All motorboats or motor vessels,
except open boats and as provided in
paragraphs (d) and (e) of this section,
the construction or decking over of
which is commenced after April 25,
1940, and which use fuel having a
flashpoint of 110° F., or less, shall have
at least two ventilator ducts, fitted
with cowls or their equivalent, for the
efficient removal of explosive or flammable gases from the bilges of every
engine and fuel tank compartment.
There shall be at least one exhaust
duct installed so as to extend from the
open atmosphere to the lower portion
of the bilge and at least one intake
duct installed so as to extend to a
point at least midway to the bilge or at
least below the level of the carburetor
air intake. The cowls shall be located
and trimmed for maximum effectiveness and in such a manner so as to prevent displaced fumes from being recirculated.
(b) As used in this section, the term
open boats means those motorboats or
motor vessels with all engine and fuel
tank compartments, and other spaces
to which explosive or flammable gases
and vapors from these compartments
may flow, open to the atmosphere and
so arranged as to prevent the entrapment of such gases and vapors within
the vessel.
(c) Boats built after July 31, 1980,
which are manufactured or used primarily for noncommercial use; which
are leased, rented, or chartered to another for the latter’s noncommercial
use; which are engaged in the carriage
of six or fewer passengers; or which are
in compliance with the requirements of
33 CFR part 183 are exempted from
these requirements.
(d) Boats built after July 31, 1978,
which are manufactured or used primarily for noncommercial use; which
are rented, leased, or chartered to another for the latter’s noncommercial

320

VerDate 0ct<02>2002

14:50 Oct 10, 2002

Jkt 197179

PO 00000

Frm 00320

Fmt 8010

Sfmt 8010

Y:\SGML\197179T.XXX

197179T


File Typeapplication/pdf
File Modified2014-12-08
File Created2014-12-08

© 2024 OMB.report | Privacy Policy